17 laporan ditemukan · 0 belum selesai
| NO | Tanggal / Petugas | Lokasi | Keterangan Aktivitas | Kondisi & Rekomendasi | Notifikasi | Dokumentasi | Status | Aksi |
|---|---|---|---|---|---|---|---|---|
| 1 |
07 Nov 2026
Hasyim Alhabsyi
|
PHC-01
CIGADING 1
|
Ruang trafo kotor, rekues cleaning
|
RELEASE
BY EXECUTOR
|
TIDAK | Completed |
||
| 2 |
19 Oct 2026
Anton Diki W
|
PHC-01
CIGADING 1
|
Kondisi slipring PHC-01 untuk saat ini terpantau Kotor , request cleaning
|
RELEASE
BY EXECUTOR
|
Low | Completed |
||
| 3 |
08 Oct 2026
Hasyim Alhabsyi
|
PHC-01
CIGADING 1
|
Kondisi konekan dan dudukan motor pinlock PHC 01 sebelah darat korosi. request service.
|
RELEASE
BY EXECUTOR
|
Medium 130000019183 |
Completed |
||
| 4 |
08 Oct 2026
Anton Diki W
|
PHC-01
CIGADING 1
|
Kondisi konekan dan dudukan motor pinlock PHC 01 sebelah laut korosi request service, ( note nilai tahanan Oke )
|
RELEASE
BY EXECUTOR
|
Medium 130000019182 |
Completed |
||
| 5 |
24 Aug 2026
Anton Diki W
|
PHC-01
CIGADING 1
|
Ruang trafo phc-01 dinding arah laut ada yang bolong 2 titik. Ditakutkan masuk air, rekues repair/foam
|
RELEASE
REQUEST REPAIR
|
Medium | Completed |
||
| 6 |
27 Jul 2026
Anton Diki W
|
PHC-01
CIGADING 1
|
Slipring PHC 01 kotor request cleaning
|
RELEASE
BY EXECUTOR
|
Medium | Completed |
||
| 7 |
27 Jul 2026
Anton Diki W
|
PHC-01
CIGADING 1
|
Ruang trafo PHC-01 kotor, rekues cleaning
|
RELEASE
BY EXECUTOR
|
Medium | Completed |
||
| 8 |
25 Apr 2026
Hasyim Alhabsyi
|
PHC-01
CIGADING 1
|
Lampu penerangan di depan ruang trafo PHC-01 berkedip, Request Ganti
|
RELEASE
REQUEST GANTI
|
Medium 130000017978 |
Completed |
||
| 9 |
25 Apr 2026
Hasyim Alhabsyi
|
PHC-01
CIGADING 1
|
Cooling fan oil tidak terpasang di motor Powerpack gate hooper PHC-01
|
RELEASE
REQUEST REPAIR
|
Medium 130000016236 |
Completed |
||
| 10 |
15 Apr 2026
Hasyim Alhabsyi
|
PHC-01
CIGADING 1
|
Perbaiki jalur lampu frame lights dan MCB 203f3 yg rusak di PHC 01
|
RELEASE
REQUEST REPAIR
|
Medium 130000017912<br/> 130000017907 |
Completed |
||
| 11 |
15 Apr 2026
Hasyim Alhabsyi
|
PHC-01
CIGADING 1
|
Grounding area gantry tidak terpasang 2 pcs, rekues pasang PHC-01
|
RELEASE
REQUEST PENAMBAHAN
|
Medium | Completed |
||
| 12 |
02 Mar 2026
Hasyim Alhabsyi
|
PHC-01
CIGADING 1
|
Dinding Ruang motor room PHC-01 bolong atau keropos. request repair
|
RELEASE
REQUEST REPAIR
|
Medium 130000017589 |
Completed |
||
| 13 |
02 Mar 2026
Hasyim Alhabsyi
|
PHC-01
CIGADING 1
|
Kontaktor di panel luffing (486K2) PHC-01 terdapat kelainan bunyi/pong. req ganti
|
RELEASE
REQUEST GANTI
|
Medium 130000017590 |
Completed |
||
| 14 |
02 Mar 2026
Hasyim Alhabsyi
|
PHC-01
CIGADING 1
|
fan panel di panel room elektrik mati 7pcs. req perbaiki instalasi dan ganti fan yang mati. PHC 01
- panel rectifier 1pcs - panel holding 2pcs - panel closing 1pcs - panel luffing 2pcs - panel spreader 1pcs |
RELEASE
BY EXECUTOR
|
Medium 130000017581 |
Completed |
||
| 15 |
02 Mar 2026
Hasyim Alhabsyi
|
PHC-01
CIGADING 1
|
Isolasi kabel power 6 KV rusak PHC-01. Req. raychem kabel ulang (Service)
|
RELEASE
REQUEST SERVICE
|
Medium 130000017573 |
Completed |
||
| 16 |
02 Mar 2026
Hasyim Alhabsyi
|
PHC-01
CIGADING 1
|
Ruang trafo PHC-01 dinding bolong 3 titik, rekues repair
|
RELEASE
REQUEST REPAIR
|
Medium 130000017361 |
Completed |
||
| 17 |
02 Mar 2026
Hasyim Alhabsyi
|
PHC-01
CIGADING 1
|
Kabel Grounding area gantry PHC 01 hilang 2 pcs, Posisi sebelah darat. Req. Tambahkan
|
RELEASE
REQUEST TAMBAHKAN
|
Medium 130000014469 |
Completed |