Beranda  ›  Dashboard  ›  Rekap Kondisi Alat  ›  Ready to Use

Rekap Ready to Use

80 laporan ditemukan · 0 belum selesai

Reset
Elektrik 80 0 belum selesai · 80 lainnya

Elektrik

80 laporan · 0 belum selesai
NO Tanggal / Petugas Lokasi Keterangan Aktivitas Kondisi & Rekomendasi Notifikasi Dokumentasi Status Aksi
1
21 Nov 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Pengukuran suhu motor Gsu-01

Motor drive belt feeder 36
Holding
Drive 59
Bearing 40
Fan 36

Closing
Drive 51
Bearing 39
Fan 46

Trolley
Drive 49
Bearing 38
Fan 47
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
2
21 Nov 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Penggantian filter motor fan holding closing trolley GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
3
14 Nov 2026
Anton Diki W
GSU-01
CIGADING 1
Lubrikasi underspeed GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
4
14 Nov 2026
Anton Diki W
GSU-01
CIGADING 1
Pengukuran suhu motor belt feeder GSU-01 :
Drive 37,9 derajat celcius
Bearing 35,7 derajat celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
5
11 Nov 2026
Anton Diki W
GSU-01
CIGADING 1
Pengukuran suhu trafo GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
6
28 Oct 2026
Anton Diki W
GSU-01
CIGADING 1
Pengukuran jalur input zerospeed GSU-01 sistem 1 PBCN 01 (hasil ok)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
7
28 Oct 2026
Anton Diki W
GSU-01
CIGADING 1
Pengukuran jalur input zerospeed GSU-01 sistem 2 PBCN 02 (hasil ok)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
8
28 Oct 2026
Anton Diki W
GSU-01
CIGADING 1
Cleaning motor drive closing GSU 01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
9
28 Oct 2026
Anton Diki W
GSU-01
CIGADING 1
Cleaning magnet switch GSU 01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
10
28 Oct 2026
Anton Diki W
GSU-01
CIGADING 1
Cleaning zerospeed sistem 1&2 GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
11
28 Oct 2026
Anton Diki W
GSU-01
CIGADING 1
Cleaning motor gate power pack dan panel gate powerpack GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
12
28 Oct 2026
Anton Diki W
GSU-01
CIGADING 1
Motor creeper gantry GSU 01 tidak 3pcs, 1pcs sebelah laut dan 2pcs sebelah darat
RUSAK RINGAN
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi Dokumentasi
Ready to Use
13
28 Oct 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Cleaning motor drive trolley GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
14
30 Sep 2026
Anton Diki W
GSU-01
CIGADING 1
Lubrikasi roll festune cabin operator GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
15
30 Sep 2026
Anton Diki W
GSU-01
CIGADING 1
Cleaning motor drive holding, closing dan trolley GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
16
23 Sep 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Holding GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
17
23 Sep 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Boom trolley Inverter GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
18
23 Sep 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Gantry Inverter GSU-01 : 34.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
19
23 Sep 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Trafo GSU-01 : 42.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
20
23 Sep 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel PLC Control GSU-01 : 41.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
21
07 Sep 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Penggantian filter motor fan holding, closing, dan trolley di area motor room GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
22
07 Sep 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Lubrikasi roll festune cabin operator GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
23
31 Aug 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Holding GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
24
31 Aug 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Boom trolley Inverter GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
25
31 Aug 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Gantry Inverter GSU-01 : 27.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
26
31 Aug 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Trafo GSU-01 : 43.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
27
31 Aug 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel PLC Control GSU-01 : 29.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
28
25 Jul 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Holding GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
29
25 Jul 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Boom trolley Inverter GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
30
25 Jul 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Gantry Inverter GSU-01 : 30.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
31
25 Jul 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Trafo GSU-01 : 42.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
32
25 Jul 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel PLC Control GSU-01 : 34.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
33
25 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Cleaning dan Penggantian filter motor fan holding closing trolley GSU-01 before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
34
09 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Hasil Megger Motor gantry GSU 01 sebelah darat no.08:

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
35
09 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Hasil Megger Motor gantry GSU 01 sebelah darat no.07:

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
36
09 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Hasil Megger Motor gantry GSU 01 sebelah darat no.06:

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
37
09 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Hasil Megger Motor gantry GSU 01 sebelah darat no.05:

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
38
09 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Hasil Megger Motor gantry GSU 01 sebelah darat no.04:

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
39
09 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Hasil Megger Motor gantry GSU 01 sebelah darat no.03:

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
40
09 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Hasil Megger Motor gantry GSU 01 sebelah darat no.02:

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
41
09 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Hasil Megger Motor gantry GSU 01 sebelah darat no.01:

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
42
08 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Pengecekkan lidah kontaktor holding closing trolley GSU-01 (kondisi kontaktor ok)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
43
08 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Cleaning motor drive holding closing dan trolley GSU 01
Note: filter GSU 01 terpantau masih Oke
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
44
08 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Cleaning motor gate power pack GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
45
27 Jun 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Motor Gantry Nomor 2 (Sisi Laut arah Anyer)

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm

Hasil Megger motor dinyatakan bagus (OK)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
46
27 Jun 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Pengecekan & Cleaning seluruh Motor Gantry sisi darat di GSU-01 (Hasil Megger OK = 550 MOhm)
Untuk motor gantry sebelah darat yang mengalami korosi sudah di bersihkan dan di amplas.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
47
13 Jun 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Holding GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
48
13 Jun 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Boom trolley Inverter GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
49
13 Jun 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Gantry Inverter GSU-01 : 34.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
50
13 Jun 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Trafo GSU-01 : 36.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
Menampilkan 50 laporan terbaru dari 80. Tampilkan semua