| 1 |
09 Nov 2026
Anton Diki W
|
DLLC-01
CIGADING 1
|
Pengukuran suhu ruang elektrik 26,9 derajat Celcius.
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 2 |
09 Nov 2026
Anton Diki W
|
DLLC-01
CIGADING 1
|
Pengukuran suhu ruang trafo 33,2 derajat Celcius.
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 3 |
09 Nov 2026
Anton Diki W
|
DLLC-01
CIGADING 1
|
Pengukuran suhu panel gantry 31,1 derajat Celcius.
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 4 |
09 Nov 2026
Anton Diki W
|
DLLC-01
CIGADING 1
|
Kondisi Slipring DLLC 01 untuk saat ini masih terpantau amann
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 5 |
09 Nov 2026
Anton Diki W
|
DLLC-01
CIGADING 1
|
Chamswitch holding DLLC 01 terpantau lengkap
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 6 |
09 Nov 2026
Anton Diki W
|
DLLC-01
CIGADING 1
|
Grounding area gantry DLLC 01 terpantau Oke
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 7 |
09 Nov 2026
Anton Diki W
|
DLLC-01
CIGADING 1
|
Cleaning dan lubrikasi roll pendulum medium voltage DLLC-01
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 8 |
09 Nov 2026
Anton Diki W
|
DLLC-01
CIGADING 1
|
Cleaning dan lubrikasi motor creeper gantry DLLC 01
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 9 |
09 Nov 2026
Anton Diki W
|
DLLC-01
CIGADING 1
|
Cleaning powerpack gate Hooper dan panel gate Hooper DLLC 01
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 10 |
03 Sep 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel Luffing: 30.6°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 11 |
03 Sep 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 29.3°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 12 |
03 Sep 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 32.6°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 13 |
03 Sep 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 30.1°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 14 |
03 Sep 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-01 : 33.3°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 15 |
03 Sep 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu trafo DLLC-01 : 40.5°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 16 |
03 Sep 2026
Anton Diki W
|
DLLC-01
CIGADING 1
|
Kondisi Slipring DLLC 01 untuk saat ini masih terpantau OK
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 17 |
03 Sep 2026
Anton Diki W
|
DLLC-01
CIGADING 1
|
Cleaning panel cabin desk operator DLLC-01
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 18 |
08 Aug 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel Luffing: 32.3°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 19 |
08 Aug 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 29.6°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 20 |
08 Aug 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 29.2°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 21 |
08 Aug 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 34.5°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 22 |
08 Aug 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-01 : 29.5°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 23 |
08 Aug 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu trafo DLLC-01 : 48.6°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 24 |
08 Aug 2026
Anton Diki W
|
DLLC-01
CIGADING 1
|
Hasil Megger Motor gantry DLLC 01 no 04 sebelah darat
U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm
Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 25 |
29 Jul 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel Luffing: 31.0°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 26 |
29 Jul 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 34.7°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 27 |
29 Jul 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 28.7°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 28 |
29 Jul 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 30.8°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 29 |
29 Jul 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-01 : 30.8°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 30 |
29 Jul 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu trafo DLLC-01 : 45.2°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 31 |
29 Jul 2026
Anton Diki W
|
DLLC-01
CIGADING 1
|
Kondisi Slipring DLLC 01 untuk saat ini masih terpantau amann
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 32 |
29 Jul 2026
Anton Diki W
|
DLLC-01
CIGADING 1
|
Cleaning motor powerpack gate Hooper DLLC 01 before dan after
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 33 |
29 Jul 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Cleaning cabin desk operator DLLC-01
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 34 |
22 Jun 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel Luffing: 29.9°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 35 |
22 Jun 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 33.5°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 36 |
22 Jun 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 33.0°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 37 |
22 Jun 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 31.7°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 38 |
22 Jun 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-01 : 29.8°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 39 |
22 Jun 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu trafo DLLC-01 : 49.5°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 40 |
22 Jun 2026
Anton Diki W
|
DLLC-01
CIGADING 1
|
kondisi slipring kabel drum 6kV untuk saat ini masih terpantau amann DLLC 01
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 41 |
22 Jun 2026
Anton Diki W
|
DLLC-01
CIGADING 1
|
Kondisi Slipring DLLC 01 untuk saat ini masih terpantau amann
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 42 |
22 Jun 2026
Anton Diki W
|
DLLC-01
CIGADING 1
|
Cleaning Motor kabel drum medium voltage DLLC 01
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 43 |
22 Jun 2026
Anton Diki W
|
DLLC-01
CIGADING 1
|
Cleaning motor creeper gantry DLLC 01 , before dan after
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 44 |
22 Jun 2026
Anton Diki W
|
DLLC-01
CIGADING 1
|
Cleaning motor powerpack gate Hooper DLLC 01
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 45 |
10 Jun 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Preventive elektrik program Megger / Pengujian tahanan (resistansi) isolasi di DLLC-01 :
1. Megger insulation tes motor drive Holding. Ground-ground, ground-phase, phase-phase hasil 550Mohm
2. Megger insulation tes motor drive Closing. Ground-ground, ground-phase, phase-phase hasil 550Mohm
3. Megger insulation tes motor drive slewing 1. Ground-ground, ground-phase, phase-phase hasil 550Mohm
4. Megger insulation tes motor drive slewing 2. Ground-ground, ground-phase, phase-phase hasil 550Mohm
5. Megger insulation tes motor brake holding. Ground-ground, ground-phase, phase-phase hasil 550Mohm
6. Megger insulation tes motor brake closing. Ground-ground, ground-phase, phase-phase hasil 550Mohm
7. Megger insulation tes motor brake slewing 1&2 Ground-ground, ground-phase, phase-phase hasil 550Mohm
8. Megger insulation tes motor drive luffing. Ground-ground, ground-phase, phase-phase hasil 550Mohm
9. Megger insulation tes motor fan holding, closing. Ground-ground, ground-phase, phase-phase hasil 550Mohm
10. Megger insulation tes motor fan luffing. Ground-ground, ground-phase, phase-phase hasil 550Mohm
11. Cleaning semua motor yang di Megger
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 46 |
11 May 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel Luffing: 29.4°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 47 |
11 May 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 29.3°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 48 |
11 May 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 33.0°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 49 |
11 May 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 34.2°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|
| 50 |
11 May 2026
Hasyim Alhabsyi
|
DLLC-01
CIGADING 1
|
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-01 : 29.2°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK |
|
Ready to Use |
|