63 laporan ditemukan · 0 belum selesai
| NO | Tanggal / Petugas | Lokasi | Keterangan Aktivitas | Kondisi & Rekomendasi | Notifikasi | Dokumentasi | Status | Aksi |
|---|---|---|---|---|---|---|---|---|
| 1 |
21 Nov 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Pengukuran suhu Auxtrafo GSU-04
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 2 |
21 Nov 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Pengukuran suhu main trafo GSU-04
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 3 |
21 Nov 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Pengukuran suhu ruang elektrik GSU 04
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 4 |
21 Nov 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Pengukuran suhu motor Gsu-04
Holding Drive 46 Bearing 38 Fan 45 Closing Drive 54 Bearing 40 Fan 45 Trolley Drive 52 Bearing 37 Fan 46 Suhu Motor belt feeder GSU 04 Drive 35 |
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 5 |
21 Nov 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Cleaning dan Penggantian filter motor fan holding closing trolley GSU-04
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 6 |
21 Nov 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Lubrikasi roll festune cabin operator GSU 04
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 7 |
14 Nov 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Pengukuran suhu motor belt feeder GSU-04 :
Drive 38,8 derajat celcius Bearing 37,8 derajat celcius |
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 8 |
14 Nov 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Lubrikasi zerospeed GSU-04
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 9 |
11 Nov 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Pengukuran suhu trafo GSU-04
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 10 |
11 Nov 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Pengukuran suhu ruang panel elektrik GSU-04
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 11 |
11 Nov 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Lubrikasi roll festune cabin operator GSU 04
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 12 |
11 Nov 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Grounding di area Motor creeper gantry tidak terpasang GSU 04
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
PANTAU | Ready to Use |
||
| 13 |
11 Nov 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Cleaning motor powerpack gate feeder GSU 04
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 14 |
28 Oct 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Pengukuran jalur input zerospeed GSU-04 sistem 2 PBCN 02 (hasil ok)
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 15 |
28 Oct 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Cleaning motor powerpack belt feeder hopper GSU-04
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 16 |
28 Oct 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Cleaning dan lubrikasi zerospeed sistem 1 dan 2 di GSU-04
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 17 |
12 Oct 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Lubrikasi roll festune cabin operator GSU 04
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 18 |
12 Oct 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Lubrikasi motor creeper brake gantry sisi laut dan darat.
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 19 |
30 Sep 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Kontaktor brake trolley pong sebelah laut nomor 1 pcs, Rekues ganti GSU-04
|
LAIK PAKAI
REQUEST GANTI
|
Medium 130000019073 |
Completed |
||
| 20 |
30 Sep 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Kontaktor brake holding pong. Panel nomor 2 sebelah anyer
|
LAIK PAKAI
REQUEST GANTI
|
Medium 130000019070 |
Completed |
||
| 21 |
23 Sep 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Inspeksi dan Pengukuran suhu ruang panel elektrik GSU-04 : 28.9°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 22 |
23 Sep 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Inspeksi dan Pengukuran suhu panel Closing GSU-04 : 27.7°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 23 |
23 Sep 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Inspeksi dan Pengukuran suhu panel Holding inverter GSU-04 : 32.7°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 24 |
23 Sep 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Inspeksi dan Pengukuran suhu panel Gantry GSU-04 : 29.2°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 25 |
07 Sep 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Cleaning dan Penggantian filter motor fan holding closing trolley GSU-04 before dan after
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 26 |
07 Sep 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Pengecekkan lidah kontaktor holding closing trolley GSU-04 (kondisi kontaktor ok)
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 27 |
07 Sep 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Cleaning dan lubrikasi zerospeed GSU-04
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 28 |
07 Sep 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Cleaning motor gate power pack dan panel gate powerpack GSU-04
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 29 |
31 Aug 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Inspeksi dan Pengukuran suhu ruang panel elektrik GSU-04 : 30.7°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 30 |
31 Aug 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Inspeksi dan Pengukuran suhu panel Closing GSU-04 : 28.1°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 31 |
31 Aug 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Inspeksi dan Pengukuran suhu panel Holding inverter GSU-04 : 27.3°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 32 |
31 Aug 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Inspeksi dan Pengukuran suhu panel Gantry GSU-04 : 26.2°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 33 |
31 Aug 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Pengukuran suhu motor Gsu-04
Holding Drive 53 Bearing 41 Fan 44 Closing Drive 57 Bearing 42 Fan 46 Trolley Drive 49 Bearing 42 Fan 45 Suhu Motor belt feeder GSU 04 Motor 01 Drive 32 |
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 34 |
01 Aug 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Program megger motor drive BOOM GSU-04 :
GROUND-GROUND pengukuran 0 Mohm, GROUND-POSITIF, GROUND-NEGATIF hasil pengukuran 550Mohm POSITIF - NEGATIF hasil pengukuran 0 Mohm Exsitasi Ground F1 Ground F2 Hasil pengukuran 550Mohm |
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 35 |
01 Aug 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Hasil Megger Motor cabel reel medium voltage GSU 04 :
U1 - G : 550 Mohm V1 - G : 550 Mohm W1 - G : 550 Mohm U2 - G : 550 Mohm V2 - G : 550 Mohm W2 - G : 550 Mohm Antar Phase U1 - U2 : 0 Mohm U1 - V2 : 550 Mohm U1 - W2 : 550 Mohm V1 - V2 : 0 Mohm V1 - U2 : 550 Mohm V1 - W2 : 550 Mohm W1 - W2 : 0 Mohm W1 - U2 : 550 Mohm W1 - V2 : 550 Mohm |
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 36 |
01 Aug 2026
Anton Diki W
|
GSU-04
CIGADING 1
|
Cleaning dan Penggantian filter motor fan holding closing trolley GSU-04 before dan after
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 37 |
25 Jul 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Inspeksi dan Pengukuran suhu ruang panel elektrik GSU-04 : 32.2°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 38 |
25 Jul 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Inspeksi dan Pengukuran suhu panel Closing GSU-04 : 28.4°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 39 |
25 Jul 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Inspeksi dan Pengukuran suhu panel Holding inverter GSU-04 : 30.5°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 40 |
25 Jul 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Inspeksi dan Pengukuran suhu panel Gantry GSU-04 : 26.7°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 41 |
08 Jul 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Lubrikasi roll festun cabin operator GSU-04
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 42 |
08 Jul 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Cleaning motor power pack
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 43 |
17 Jun 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Program megger motor drive TROLLEY GSU-04 :
Antar Phase GROUND - GROUND = 0 MOhm, GROUND - POSITIF = 550 MOhm GROUND - NEGATIF = 550 MOhm POSITIF - NEGATIF = 0 MOhm Exsitasi Ground - F1 : 550 MOhm Ground - F2 : 550 MOhm Kode Motor : M6 |
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 44 |
13 Jun 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Inspeksi dan Pengukuran suhu ruang panel elektrik GSU-04 : 27.3°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 45 |
13 Jun 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Inspeksi dan Pengukuran suhu panel Closing GSU-04 : 38.8°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 46 |
13 Jun 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Inspeksi dan Pengukuran suhu panel Holding inverter GSU-04 : 31.2°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 47 |
13 Jun 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Inspeksi dan Pengukuran suhu panel Gantry GSU-04 : 26.9°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 48 |
13 Jun 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Cleaning dan Penggantian filter motor fan holding closing trolley GSU-04 (dokumentasi before dan after)
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |
||
| 49 |
13 Jun 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Program megger motor drive HOLDING GSU-04 :
Antar Phase GROUND - GROUND = 0 MOhm, GROUND - POSITIF = 46 MOhm GROUND - NEGATIF = 47 MOhm POSITIF - NEGATIF = 0 MOhm Exsitasi Ground - F1 : 550 MOhm Ground - F2 : 550 MOhm Pantau berkala Kode Motor : M4 |
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
PANTAU | Ready to Use |
||
| 50 |
14 May 2026
Hasyim Alhabsyi
|
GSU-04
CIGADING 1
|
Inspeksi dan Pengukuran suhu ruang panel elektrik GSU-04 : 29.3°C
|
LAIK PAKAI
PREVENTIVE MAINTENANCE
|
TIDAK | Ready to Use |