1
21 Nov 2026
Anton Diki W
GSU-04
CIGADING 1
Pengukuran suhu Auxtrafo GSU-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
2
21 Nov 2026
Anton Diki W
GSU-04
CIGADING 1
Pengukuran suhu main trafo GSU-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
3
21 Nov 2026
Anton Diki W
GSU-04
CIGADING 1
Pengukuran suhu ruang elektrik GSU 04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
4
21 Nov 2026
Anton Diki W
GSU-04
CIGADING 1
Pengukuran suhu motor Gsu-04

Holding
Drive 46
Bearing 38
Fan 45

Closing
Drive 54
Bearing 40
Fan 45

Trolley
Drive 52
Bearing 37
Fan 46

Suhu Motor belt feeder GSU 04
Drive 35
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
5
21 Nov 2026
Anton Diki W
GSU-04
CIGADING 1
Motor drive closing terpantau Kotor di GSU 04 butuh di cleaning
KOTOR
REQUEST BERSIHKAN
Medium
130000019653
Dokumentasi Dokumentasi
In Process
6
21 Nov 2026
Anton Diki W
GSU-04
CIGADING 1
Main trafo GSU 04 butuh di cleaning
KOTOR
REQUEST BERSIHKAN
Medium
130000019652
Dokumentasi Dokumentasi
In Process
7
21 Nov 2026
Anton Diki W
GSU-04
CIGADING 1
Cleaning dan Penggantian filter motor fan holding closing trolley GSU-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
8
21 Nov 2026
Anton Diki W
GSU-04
CIGADING 1
Lubrikasi roll festune cabin operator GSU 04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
9
21 Nov 2026
Anton Diki W
GSU-04
CIGADING 1
Menghidupkan jalur lampu yg mati di area boom GSU 04
Setelah di cek lampu yg mati hanya 1pcs di sebelah anyer
RUSAK RINGAN
REQUEST GANTI
Medium
130000019651
Dokumentasi Dokumentasi
In Process
10
21 Nov 2026
Anton Diki W
GSU-04
CIGADING 1
Motor creeper gantry GSU 04 tidak 2pcs, 1pcs sebelah laut dan 1pcs sebelah darat
RUSAK RINGAN
PREVENTIVE MAINTENANCE
Medium
130000019650
Dokumentasi Dokumentasi
In Process
11
21 Nov 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Pengukuran suhu motor Gsu-01

Motor drive belt feeder 36
Holding
Drive 59
Bearing 40
Fan 36

Closing
Drive 51
Bearing 39
Fan 46

Trolley
Drive 49
Bearing 38
Fan 47
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
12
21 Nov 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Penggantian filter motor fan holding closing trolley GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
13
21 Nov 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Lampu LED 18 watt ruang panel elektrik mati 5 pcs GSU-01, rekues ganti
LAIK PAKAI
REQUEST GANTI
Medium
130000019648
Dokumentasi Dokumentasi
In Process
14
21 Nov 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Kontaktor EH700 dengung posisi di panel drive trolley/boom GSU-01, rekues servis
RUSAK RINGAN
REQUEST SERVICE
Medium
130000019649
Dokumentasi Dokumentasi
In Process
15
20 Nov 2026
Anton Diki W
Feeding SGT
CIGADING 1
Hasil tes running setelah di cleaning bucket elevator SGT
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
16
20 Nov 2026
Anton Diki W
Feeding SGT
CIGADING 1
Cleaning fan motor bucket feeder before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
17
19 Nov 2026
Anton Diki W
Dermaga 5
CIGADING 2
Pengukuran suhu ruang trafo dermaga 05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
18
19 Nov 2026
Hasyim Alhabsyi
Dermaga 5
CIGADING 2
Inspeksi lampu penerangan dermaga 5, kondisi lampu ok terang semua
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
19
18 Nov 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Lampu indikator RST (warna Merah) di panel gate hooper terbakar (meleleh). Req. Ganti
RELEASE
BY EXECUTOR
Medium
130000019628
Dokumentasi Dokumentasi
Completed
20
18 Nov 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Kontak emergency button di panel gate hooper terbakar (meleleh). Req. Ganti
RELEASE
BY EXECUTOR
Medium
130000019629
Dokumentasi Dokumentasi
Completed
21
18 Nov 2026
Anton Diki W
DLLC-04
CIGADING 1
Pengukuran suhu ruang elektrik DLLC 04 26,6 derajat celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
22
18 Nov 2026
Anton Diki W
DLLC-04
CIGADING 1
Pengukuran suhu ruang trafo DLLC 04 32,0 derajat celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
23
18 Nov 2026
Anton Diki W
DLLC-04
CIGADING 1
Suhu ruang gantry 30.6 derajat celcius DLLC-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
24
18 Nov 2026
Anton Diki W
DLLC-04
CIGADING 1
Cleaning panel cabin desk operator DLLC-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
25
18 Nov 2026
Anton Diki W
DLLC-04
CIGADING 1
Kondisi ruang cabin operator banyak putung rokok, rekues cleaning DLLC-04
RELEASE
BY EXECUTOR
Medium
Dokumentasi
Completed
26
18 Nov 2026
Anton Diki W
DLLC-04
CIGADING 1
Grounding yang ada di dalem pintu panel ruang elektrik putus 2pcs request ganti , DLLC 04
- panel SLM 1 cubicle
- Hold MM cubicle
RUSAK RINGAN
REQUEST GANTI
Medium
130000019624
Dokumentasi Dokumentasi
In Process
27
18 Nov 2026
Anton Diki W
DLLC-04
CIGADING 1
Lampu led 15watt yg ada di dalem panel elektrik mati 1pcs request ganti DLLC 04
- panel Slew/Gantry Switch Cubicle
RUSAK RINGAN
REQUEST GANTI
Medium
130000019625
Dokumentasi Dokumentasi
In Process
28
18 Nov 2026
Anton Diki W
DLLC-04
CIGADING 1
Kondisi Slipring DLLC 04 untuk saat ini masih terpantau amann
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
29
18 Nov 2026
Anton Diki W
DLLC-04
CIGADING 1
Baut chamswitch holding baut lepas 1 pcs, sementara di tyrap DLLC-04
RUSAK RINGAN
REQUEST PENAMBAHAN
Medium
130000019626
Dokumentasi
In Process
30
18 Nov 2026
Anton Diki W
DLLC-04
CIGADING 1
Relay impulse di panel gantry terpantau dengung ( =14C-K24 ) , request ganti DLLC 04
RUSAK RINGAN
REQUEST GANTI
Medium
130000019627
Dokumentasi
In Process
31
18 Nov 2026
Anton Diki W
DLLC-04
CIGADING 1
kondisi slipring kabel drum 6kV untuk saat ini masih terpantau amann dan bersih DLLC 04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
32
18 Nov 2026
Anton Diki W
DLLC-04
CIGADING 1
Grounding area gantry DLLC 04 terpantau lengkap
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
33
18 Nov 2026
Anton Diki W
DLLC-04
CIGADING 1
Motor vibro Hopper DLLC 04 tidak terpasang 1pcs sebelah laut bagian merak
RELEASE
BY EXECUTOR
PANTAU
Dokumentasi
Completed
34
18 Nov 2026
Anton Diki W
DLLC-04
CIGADING 1
Pengetesan gate Hooper open / close : OK DLLC 04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
35
18 Nov 2026
Anton Diki W
DLLC-04
CIGADING 1
Cleaning panel gate hopper before & after DLLC-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
36
18 Nov 2026
Anton Diki W
DLLC-04
CIGADING 1
Cleaning dan lubrikasi motor creeper gantry DLLC 04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
37
18 Nov 2026
Anton Diki W
DLLC-04
CIGADING 1
Cleaning dan lubrikasi roll pendulum medium voltage DLLC-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
38
18 Nov 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Chamswitch holding closing baut lengkap, kondisi aman
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
39
18 Nov 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Cleaning dan lubrikasi roll pendulum medium voltage
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
40
18 Nov 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Ruang cabin operator banyak putung rokok, rekues cleaning
LAIK PAKAI
REQUEST BERSIHKAN
Medium
Dokumentasi Dokumentasi
Outstanding
41
18 Nov 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Kondisi slipring terpantau aman
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
42
17 Nov 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Lampu stadion mati 3 pcs rekues ganti LED posisi Merak Conv A101
RUSAK RINGAN
REQUEST GANTI
Medium
130000018880
Dokumentasi Dokumentasi
In Process
43
17 Nov 2026
Anton Diki W
Conveyor A101
CIGADING 2
Pengukuran suhu panel P1A 30,5 derajat Celcius.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
44
17 Nov 2026
Anton Diki W
Conveyor A102
CIGADING 2
Cleaning underspeed posisi tail conveyor A102
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
45
17 Nov 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Lampu stadion mati 3 pcs rekues ganti LED posisi Anyer conv A101
RUSAK RINGAN
REQUEST GANTI
Medium
Dokumentasi Dokumentasi
Outstanding
46
17 Nov 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Cleaning underspeed posisi tail Conv A101
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
47
16 Nov 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Lampu indikator cabin operator mati 3 pcs GSU-06.
RUSAK RINGAN
REQUEST GANTI
Medium
130000019594
Dokumentasi
In Process
48
16 Nov 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Tombol Sakelar untuk Cabin Flood Light di panel ruang cabin operator rusak. Req. Ganti
RUSAK RINGAN
REQUEST GANTI
Medium
130000019600
Dokumentasi Dokumentasi
In Process
49
16 Nov 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Stop kontak 220VAC di cabin operator pong. Req. Ganti
RUSAK RINGAN
REQUEST GANTI
Medium
130000019602
Dokumentasi Dokumentasi
In Process
50
16 Nov 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Lampu indikator untuk tombol Hopper Gate Open di cabin operator mati 1 pcs. Req. Ganti
RUSAK RINGAN
REQUEST GANTI
Medium
130000019601
Dokumentasi Dokumentasi
In Process
51
16 Nov 2026
Anton Diki W
GSU-05
CIGADING 2
Chamswitch closing
kondisi ok di GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
52
16 Nov 2026
Anton Diki W
GSU-05
CIGADING 2
Chamswitch holding,
kondisi ok di GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
53
16 Nov 2026
Anton Diki W
GSU-05
CIGADING 2
Chamswitch boom
kondisi ok di GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
54
16 Nov 2026
Anton Diki W
GSU-05
CIGADING 2
Lampu LED 18 watt ruang motor room mati 6 pcs GSU-05, rekues ganti
RUSAK RINGAN
REQUEST GANTI
Medium
130000019593
Dokumentasi Dokumentasi
In Process
55
16 Nov 2026
Anton Diki W
GSU-05
CIGADING 2
Pengukuran suhu ruang panel elektrik GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
56
16 Nov 2026
Anton Diki W
GSU-05
CIGADING 2
Lubrikasi roll festune cabin operator GSU 05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
57
16 Nov 2026
Anton Diki W
GSU-05
CIGADING 2
Pengencangan baud panel LSA CPA Gantry GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
58
16 Nov 2026
Anton Diki W
GSU-06
CIGADING 2
Cleaning dan lubrikasi roll pendulum medium voltage GSU 06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
59
16 Nov 2026
Anton Diki W
GSU-06
CIGADING 2
Cleaning dan lubrikasi zerospeed GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
60
16 Nov 2026
Anton Diki W
CCSU
CIGADING 1
Suhu fan CC3 kiri
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
61
16 Nov 2026
Anton Diki W
CCSU
CIGADING 1
Suhu fan CC3 kanan
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
62
16 Nov 2026
Anton Diki W
CCSU
CIGADING 1
Suhu Motor drive CC3
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
63
16 Nov 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Cleaning dan lubrikasi roll pendulum medium voltage
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
64
16 Nov 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Panel lift GSU-05 kotor, rekues cleaning
Fan panel GSU-05 kotor, rekues cleaning
LAIK PAKAI
REQUEST BERSIHKAN
Medium
130000019598
Dokumentasi Dokumentasi
In Process
65
16 Nov 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Lampu LED motor room mati 4 pcs, rekues ganti
Dudukan lampu di motor room ada yang patah, rekues servis
LAIK PAKAI
REQUEST GANTI
Medium
130000019599
Dokumentasi
In Process
66
16 Nov 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Lampu LED 18 watt walkway boom mati 38 pcs, rekues ganti
RUSAK RINGAN
REQUEST GANTI
Medium
130000019593
Dokumentasi Dokumentasi
In Process
67
16 Nov 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Cleaning dan lubrikasi zerospeed GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
68
16 Nov 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Cleaning panel cabin desk operator
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
69
16 Nov 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Kabel vibrating GSU-06 sobek akibat tergesek, rekues servis
RUSAK RINGAN
REQUEST SERVICE
Medium
130000019595
Dokumentasi Dokumentasi
In Process
70
16 Nov 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Panel lift GSU-06 kotor, rekues cleaning
Fan panel GSU-06 kotor, rekues cleaning
LAIK PAKAI
REQUEST BERSIHKAN
Medium
130000019597
Dokumentasi Dokumentasi
In Process
71
16 Nov 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Pengencangan baut LSA CPA Gantry
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
72
14 Nov 2026
Anton Diki W
Conveyor BCNO
CIGADING 1
Pengecekan suhu motor BCNO :
Motor 1
Drive 47
Bearing 45
Brake 46

Motor 2
Drive 45
Bearing 43
Brake 50
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
73
14 Nov 2026
Anton Diki W
Conveyor C02
CIGADING 1
Pengecekan suhu motor C02 :
Motor 1
Drive 49
Bearing 44
Brake 47

Motor 2
Drive 48
Bearing 46
Brake 48
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
74
14 Nov 2026
Anton Diki W
Conveyor PBCN 1
CIGADING 1
Pengukuran suhu ruang panel tower 11
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
75
14 Nov 2026
Anton Diki W
Conveyor PBCN 1
CIGADING 1
Pengukuran suhu motor :
PBCN-01 :
Drive 49
Bearing 41
Brake 46

PBCN-02 :
Drive 54
Bearing 48
Brake 54
Fan 41
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
76
14 Nov 2026
Anton Diki W
Conveyor C02
CIGADING 1
Proses cleaning motor drive C02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
77
14 Nov 2026
Anton Diki W
Tower 2
CIGADING 1
Fan di panel kapasitor mati lokasi di tower 2 , request service
RUSAK RINGAN
REQUEST SERVICE
Medium
130000019554
Dokumentasi
In Process
78
14 Nov 2026
Anton Diki W
Conveyor PBCN 1
CIGADING 1
Cleaning motor drive PBCN 01 dan PBCN 02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
79
14 Nov 2026
Anton Diki W
GSU-01
CIGADING 1
Lubrikasi underspeed GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
80
14 Nov 2026
Anton Diki W
GSU-01
CIGADING 1
Pengukuran suhu motor belt feeder GSU-01 :
Drive 37,9 derajat celcius
Bearing 35,7 derajat celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
81
14 Nov 2026
Anton Diki W
Conveyor PBCN 2
CIGADING 1
Dudukan sling pullcord di conveyor PBCN 02 tidak terpasang di conveyor nomor 80 , rekues pasang
RELEASE
BY EXECUTOR
Medium
130000019553
Dokumentasi Dokumentasi
Completed
82
14 Nov 2026
Hasyim Alhabsyi
Conveyor C02
CIGADING 1
Cleaning motor drive 1&2 C02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
83
14 Nov 2026
Hasyim Alhabsyi
Conveyor BCNO
CIGADING 1
Cleaning motor drive 1&2 BCNO
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
84
14 Nov 2026
Hasyim Alhabsyi
Conveyor C02
CIGADING 1
Pengukuran suhu VSD motor 1 & 2
Hasil pengukuran sebesar 43,7 & 44,8
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
85
14 Nov 2026
Hasyim Alhabsyi
Conveyor PBCN 1
CIGADING 1
Cleaning motor drive
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
86
14 Nov 2026
Hasyim Alhabsyi
Conveyor PBCN 2
CIGADING 1
Cleaning motor drive
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
87
14 Nov 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Pengukuran suhu motor belt feeder GSU-04 :
Drive 38,8 derajat celcius
Bearing 37,8 derajat celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
88
14 Nov 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Lubrikasi zerospeed GSU-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
89
13 Nov 2026
Hasyim Alhabsyi
Dermaga 1
CIGADING 1
Pemasangan alat SS Monitoring suhu dan kelembapan di Capasitor Bank
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
90
12 Nov 2026
Anton Diki W
GSU-05
CIGADING 2
Pengukuran suhu ruang panel elektrik GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
91
12 Nov 2026
Anton Diki W
GSU-05
CIGADING 2
Chamswitch closing terpantau OK GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
92
12 Nov 2026
Anton Diki W
GSU-05
CIGADING 2
Chamswitch holding terpantau OK GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
93
12 Nov 2026
Anton Diki W
GSU-05
CIGADING 2
Chamswitch boom terpantau OK GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
94
12 Nov 2026
Anton Diki W
GSU-05
CIGADING 2
Lampu LED walkways boom 18watt mati 35 pcs. GSU-05 request ganti
RUSAK RINGAN
REQUEST GANTI
Medium
Dokumentasi Dokumentasi
Outstanding
95
12 Nov 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Lampu LED motor room mati 8 pcs
RUSAK RINGAN
REQUEST GANTI
Medium
Dokumentasi
Outstanding
96
12 Nov 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Dudukan lampu motor room patah, rekues repair
RUSAK RINGAN
REQUEST REPAIR
Medium
Dokumentasi
Outstanding
97
12 Nov 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Chamswitch boom terpantau aman
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
98
12 Nov 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Chamswitch closing terpantau aman
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
99
12 Nov 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Kondisi chamswitch holding terpantau aman
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
100
12 Nov 2026
Anton Diki W
GSU-05
CIGADING 2
Lubrikasi motor gate Hooper GSU 05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
101
12 Nov 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Lubrikasi roll pendulum medium voltage
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
102
12 Nov 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Lubrikasi roll festune area belakang cabin operator.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
103
12 Nov 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Cleaning dan lubrikasi 4 titik motor creeper brake gantry.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
104
11 Nov 2026
Anton Diki W
GSU-04
CIGADING 1
Pengukuran suhu trafo GSU-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
105
11 Nov 2026
Anton Diki W
GSU-01
CIGADING 1
Pengukuran suhu trafo GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
106
11 Nov 2026
Anton Diki W
GSU-04
CIGADING 1
Pengukuran suhu ruang panel elektrik GSU-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
107
11 Nov 2026
Anton Diki W
GSU-04
CIGADING 1
Lubrikasi roll festune cabin operator GSU 04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
108
11 Nov 2026
Anton Diki W
GSU-04
CIGADING 1
Grounding di area Motor creeper gantry tidak terpasang GSU 04
LAIK PAKAI
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi
Ready to Use
109
11 Nov 2026
Anton Diki W
GSU-04
CIGADING 1
Motor creeper gantry GSU 04 tidak terpasang 2pcs, 1pcs sebelah laut dan 1pcs sebelah darat
RUSAK RINGAN
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi Dokumentasi
Ready to Use
110
11 Nov 2026
Anton Diki W
GSU-04
CIGADING 1
Cleaning motor powerpack gate feeder GSU 04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
111
10 Nov 2026
Anton Diki W
Conveyor A101
CIGADING 2
Pengukuran suhu motor drive A101 :
Drive 40
Bearing 37
Fan 38
Brake 43
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
112
10 Nov 2026
Anton Diki W
Conveyor A101
CIGADING 2
Dudukan sling pullcord A101 patah di tiang nomor 200 , rekues repair
RUSAK RINGAN
REQUEST REPAIR
Medium
Dokumentasi
Outstanding
113
10 Nov 2026
Anton Diki W
Conveyor A101
CIGADING 2
Cleaning dan lubrikasi safety device area conveyor A101
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
114
10 Nov 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Lubrikasi safety device area conveyor
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
115
10 Nov 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Pengukuran suhu trafo panel P1A 36,0 derajat celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
116
10 Nov 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Pengukuran suhu ruang panel P1A 30,5 derajat celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
117
10 Nov 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Tray kabel pada tiang no 13 & 14 patah & korosi, rekues ganti tray
LAIK PAKAI
REQUEST GANTI
Low
Dokumentasi Dokumentasi
Outstanding
118
10 Nov 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Tray kabel tiang nomor 9 struktur ujung tray rekues di pasang pengaman, agar terhindar dari luka pada kabel
LAIK PAKAI
REQUEST PENAMBAHAN
PANTAU
Dokumentasi
Ready to Use
119
09 Nov 2026
Anton Diki W
DLLC-01
CIGADING 1
Pengukuran suhu ruang elektrik 26,9 derajat Celcius.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
120
09 Nov 2026
Anton Diki W
DLLC-01
CIGADING 1
Pengukuran suhu ruang trafo 33,2 derajat Celcius.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
121
09 Nov 2026
Anton Diki W
DLLC-01
CIGADING 1
Pengukuran suhu panel gantry 31,1 derajat Celcius.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
122
09 Nov 2026
Anton Diki W
DLLC-01
CIGADING 1
Selektor auto manual pada panel powerpack terbakar akibat kemasukan air dan kotoran Karena pintu panel tidak tertutup rapat dan kunci nya tidak ada , request ganti , DLLC 01
RUSAK RINGAN
REQUEST GANTI
Medium
130000019501
Dokumentasi Dokumentasi
In Process
123
09 Nov 2026
Anton Diki W
DLLC-01
CIGADING 1
Lampu led 15watt yg ada di dalem panel elektrik mati 2pcs request ganti DLLC 01
- panel cubicle
- panel slew/Gantry MM cubicle
RUSAK RINGAN
REQUEST GANTI
Medium
130000019504
Dokumentasi Dokumentasi
In Process
124
09 Nov 2026
Anton Diki W
DLLC-01
CIGADING 1
CPU di ruang panel elektrik kondisi mati butuh di service
RUSAK RINGAN
REQUEST SERVICE
Medium
130000019503
Dokumentasi Dokumentasi
In Process
125
09 Nov 2026
Anton Diki W
DLLC-01
CIGADING 1
Kondisi Slipring DLLC 01 untuk saat ini masih terpantau amann
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
126
09 Nov 2026
Anton Diki W
DLLC-01
CIGADING 1
Chamswitch holding DLLC 01 terpantau lengkap
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
127
09 Nov 2026
Anton Diki W
DLLC-01
CIGADING 1
Trafo DLLC 01 kondisi kotor, request cleaning
KOTOR
REQUEST BERSIHKAN
Medium
130000019500
Dokumentasi
In Process
128
09 Nov 2026
Anton Diki W
DLLC-01
CIGADING 1
Roll pendulum medium voltage DLLC-01 macet 4 Pcs , request service
RUSAK RINGAN
REQUEST SERVICE
Medium
130000019497
Dokumentasi
In Process
129
09 Nov 2026
Anton Diki W
DLLC-01
CIGADING 1
Grounding area gantry DLLC 01 terpantau Oke
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
130
09 Nov 2026
Anton Diki W
DLLC-01
CIGADING 1
Cleaning dan lubrikasi roll pendulum medium voltage DLLC-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
131
09 Nov 2026
Anton Diki W
DLLC-01
CIGADING 1
Cleaning dan lubrikasi motor creeper gantry DLLC 01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
132
09 Nov 2026
Anton Diki W
DLLC-01
CIGADING 1
Cleaning powerpack gate Hooper dan panel gate Hooper DLLC 01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
133
09 Nov 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Buzzer indikator di ruang cabin operator mati, rekues ganti
RUSAK RINGAN
REQUEST GANTI
Medium
130000019494
Dokumentasi
In Process
134
09 Nov 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Kondisi slipring terpantau aman (ok)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
135
09 Nov 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Terdapat percikan bunga api pada relay 24V di panel gate hooper DLLC-02 sisi kanan.
Req. Ganti
RELEASE
BY EXECUTOR
Medium
130000019496
Dokumentasi Dokumentasi
Completed
136
09 Nov 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Push button untuk gate corong sisi laut di hopper DLLC-02 tidak berfungsi. Power dari pushbutton tidak sampai ke Selenoid, sehingga tidak bisa menggerakan gate untuk buka / tutup. Req. Service
RELEASE
BY EXECUTOR
Medium
130000019495
Dokumentasi Dokumentasi
Completed
137
09 Nov 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Chamswitch holding closing terpantau aman, baut lengkap
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
138
09 Nov 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Cleaning dan lubrikasi roll pendulum medium voltage
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
139
09 Nov 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Cleaning dan lubrikasi motor creeper gantry,
Motor creeper gantry tidak terpasang 1 pcs
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
140
09 Nov 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Cleaning motor powerpack gate hopper
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
141
09 Nov 2026
Anton Diki W
DLLC-02
CIGADING 1
motor eldro brake gantry DLLC 02 No. 1 sebelah laut anyer belum terpasang. req. pasang
RUSAK RINGAN
REQUEST GANTI
Medium
130000017481
Dokumentasi
In Process
142
09 Nov 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Motor gantry di DLLC-02 sisi laut anyer, belum terpasang. Request pasang
RUSAK RINGAN
REQUEST PENAMBAHAN
Medium
130000016734
Dokumentasi Dokumentasi
In Process
143
07 Nov 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan cleaning motor drive holding, closing, slewing
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
144
07 Nov 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi kontrol elektrik dan mekanis gate hooper PHC-01. Proses buka-tutup gate normal, tidak ada kendala.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
145
07 Nov 2026
Anton Diki W
PHC-02
CIGADING 1
Pengukuran suhu ruang elektrik 30,2 derajat Celcius.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
146
07 Nov 2026
Anton Diki W
PHC-02
CIGADING 1
Pengukuran suhu ruang trafo 44,8 derajat Celcius.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
147
07 Nov 2026
Anton Diki W
PHC-02
CIGADING 1
Pengukuran suhu ruang gantry 42,1 derajat Celcius.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
148
07 Nov 2026
Anton Diki W
PHC-02
CIGADING 1
Inspeksi dan pengencangan baud di ruang panel elektrik
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
149
07 Nov 2026
Anton Diki W
PHC-02
CIGADING 1
Dinding motor room di bagian merak ( dekat pintu ) ada yg bolong , request repair
LAIK PAKAI
REQUEST REPAIR
Low
Dokumentasi
Outstanding
150
07 Nov 2026
Anton Diki W
PHC-02
CIGADING 1
Grounding area gantry terpantau terpasang semua PHC 02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
151
07 Nov 2026
Anton Diki W
PHC-02
CIGADING 1
Bridge crane PHC 02 kondisi OK
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
152
07 Nov 2026
Anton Diki W
PHC-02
CIGADING 1
Cleaning motor kabel drum medium voltage PHC 02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
153
07 Nov 2026
Anton Diki W
PHC-02
CIGADING 1
Kondisi Slipring PHC 02 untuk saat ini masih terpantau amann
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
154
07 Nov 2026
Anton Diki W
PHC-02
CIGADING 1
cleaning power pack break holding , closing dan luffing PHC 02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
155
07 Nov 2026
Anton Diki W
PHC-02
CIGADING 1
exhaust fan noise kasar req. service PHC 02
RUSAK RINGAN
REQUEST SERVICE
Medium
130000018901
Dokumentasi
In Process
156
07 Nov 2026
Anton Diki W
PHC-02
CIGADING 1
Exhaust fan ruang trafo mati 1 sebelah anyer PHC 02
RUSAK RINGAN
REQUEST SERVICE
Medium
130000019291
Dokumentasi
In Process
157
07 Nov 2026
Anton Diki W
PHC-02
CIGADING 1
Motor creeper No.3 sebalah darat anyer tidak terpasang req. Pasang , PHC 02
RUSAK RINGAN
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi
Ready to Use
158
07 Nov 2026
Anton Diki W
PHC-02
CIGADING 1
Motor gantry No.5 sebalah darat merak tidak terpasang req. Pasang
PHC 02
RUSAK RINGAN
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi
Ready to Use
159
07 Nov 2026
Anton Diki W
PHC-02
CIGADING 1
Cleaning motor powerpack gate Hooper dan panel powerpack gate Hooper PHC 02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
160
07 Nov 2026
Anton Diki W
PHC-02
CIGADING 1
Cleaning dan lubrikasi motor creeper gantry PHC 02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
161
07 Nov 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Cleaning dan lubrikasi motor creeper gantry
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
162
07 Nov 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Cleaning motor powerpack gate hopper
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
163
07 Nov 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Cleaning dan lubrikasi roll pendulum medium voltage
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
164
07 Nov 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Ruang trafo kotor, rekues cleaning
RELEASE
BY EXECUTOR
TIDAK
Dokumentasi
Completed
165
06 Nov 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Preventive program running inspeksi CCSU, pengukuran suhu motor CCSU :
Semua keterangan suhu menggunakan Celcius.

• Motor main pump 45,7 derajat
• Motor emergency pump 49,8 derajat
• ⁠Motor feeding pump 44,4 derajat
• ⁠Motor fan 49.3 derajat

Motor CC3
Fan 1 46,7 derajat
Fan 2 49,2 derajat
Drive 41,8 derajat
Bearing 40,8 derajat
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
166
05 Nov 2026
Anton Diki W
Conveyor A101
CIGADING 2
Cleaning baterai 12V untuk panel charging yang mengalami oksidasi
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
167
05 Nov 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Kabel tray korosi di sisi kanan trafo room Conveyor A101. Kabel tray di ganjel besi tanpa siku penahan. Req. Ganti
RUSAK RINGAN
REQUEST GANTI
Medium
130000019434
Dokumentasi Dokumentasi
In Process
168
05 Nov 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Titik ke 2 untuk kabel tray yang korosi di sisi kanan trafo room Conveyor A101. Request ganti
RUSAK RINGAN
REQUEST GANTI
Medium
130000019433
Dokumentasi Dokumentasi
In Process
169
05 Nov 2026
Anton Diki W
Conveyor A101
CIGADING 2
Pengukuran suhu panel VCB 30,3 derajat Celcius.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
170
05 Nov 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Kabel tray di belakang Trafo Conveyor A101 korosi. Req. Ganti
RUSAK RINGAN
REQUEST GANTI
Medium
130000019008
Dokumentasi Dokumentasi
In Process
171
05 Nov 2026
Anton Diki W
Conveyor A101
CIGADING 2
Kontaktor panel charging (ruangan VCB) dengung, request ganti
RUSAK RINGAN
REQUEST GANTI
Medium
130000019482
Dokumentasi
In Process
172
05 Nov 2026
Anton Diki W
Conveyor A101
CIGADING 2
Pengukuran suhu panel P1A 29,2 derajat Celcius. Kondisi sedang running
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
173
05 Nov 2026
Anton Diki W
Conveyor A101
CIGADING 2
Pengukuran suhu motor drive A101 :
Drive 39
Bearing 37
Fan 37
Brake 43
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
174
04 Nov 2026
Anton Diki W
DLLC-03
CIGADING 1
Pengukuran suhu ruang panel elektrik 24.4 derajat Celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
175
04 Nov 2026
Anton Diki W
DLLC-03
CIGADING 1
Pengukuran suhu ruang trafo 34.6 derajat Celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
176
04 Nov 2026
Anton Diki W
DLLC-03
CIGADING 1
Pengukuran suhu ruang panel gantry 30.6 derajat Celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
177
04 Nov 2026
Anton Diki W
DLLC-03
CIGADING 1
Kondisi Slipring DLLC 03 untuk saat ini masih terpantau amann
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
178
04 Nov 2026
Anton Diki W
DLLC-03
CIGADING 1
Grounding di area luffing terpantau lengkap ( oke )
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
179
04 Nov 2026
Anton Diki W
DLLC-03
CIGADING 1
Baut chamswitch holding DLLC 03 terpantau lengkap
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
180
04 Nov 2026
Anton Diki W
DLLC-03
CIGADING 1
Lubrikasi dan cleaning motor creeper gantry DLLC 03
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
181
04 Nov 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Lampu boom mati 1 pcs, rekues ganti
RELEASE
BY EXECUTOR
Medium
Dokumentasi
Completed
182
04 Nov 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Kondisi slipring terpantau aman (ok)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
183
04 Nov 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Cleaning motor creeper gantry
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
184
04 Nov 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Cleaning dan lubrikasi roll pendulum medium voltage
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
185
04 Nov 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Cleaning panel gate hopper
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
186
04 Nov 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
area ruang panel gantry DLLC-04 mati. Pengecekan Sakelar, ada Power nya.

Req. Pengecekan jalur kabel dan penggantian lampu TL 8W (jika dibutuhkan)
RELEASE
BY EXECUTOR
Medium
Dokumentasi Dokumentasi
Completed
187
03 Nov 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Pengukuran lampu penerangan ruang panel P1C, kondisi lampu LED menyala semua (ok)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
188
03 Nov 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Pengukuran lampu penerangan ruang panel P1B, kondisi lampu LED menyala semua (ok)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
189
03 Nov 2026
Anton Diki W
Conveyor A103
CIGADING 2
Pengukuran suhu panel P1C 30.5 derajat Celcius. Kondisi sedang running
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
190
03 Nov 2026
Anton Diki W
Conveyor A102
CIGADING 2
Pengukuran suhu panel P1B 29.5 derajat Celcius. Kondisi sedang running
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
191
02 Nov 2026
Hasyim Alhabsyi
Dermaga 1
CIGADING 1
Lampu penerangan dermaga 1.1 mati 1 pcs tiang no 2 dari anyer, rekues ganti
RUSAK RINGAN
REQUEST GANTI
Medium
Dokumentasi Dokumentasi
Outstanding
192
02 Nov 2026
Anton Diki W
Dermaga 1
CIGADING 1
Terminal power area dermaga 1.1 kondisi ok
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
193
02 Nov 2026
Hasyim Alhabsyi
Conveyor PBCN 1
CIGADING 1
Cleaning motor drive pbcn
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
194
02 Nov 2026
Anton Diki W
Conveyor PBCN 1
CIGADING 1
Underspeed conveyor PBCN 01 dan PBCN 02 Kondisi Oke
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
195
02 Nov 2026
Anton Diki W
Conveyor PBCN 1
CIGADING 1
Beltsway dan emergency berfungsi dengan aman dan ok✅
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
196
02 Nov 2026
Hasyim Alhabsyi
Conveyor C02
CIGADING 1
Dudukan underspeed C02 patah (korosi), rekues repai
RELEASE
BY EXECUTOR
Medium
130000019386
Dokumentasi Dokumentasi
Completed
197
31 Oct 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Cleaning panel elektrik mainpump
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
198
31 Oct 2026
Anton Diki W
CCSU
CIGADING 1
Cleaning ruang panel elektrik CSU
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
199
31 Oct 2026
Anton Diki W
CCSU
CIGADING 1
Cleaning dan Penggantian filter fan ruang trafo CSU (before) dan ( after )
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
200
31 Oct 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Cleaning paddleswitch CC3
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
201
31 Oct 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Rotary Lamp indikator Traveling mati di 3 titik.
sisi Merak -Darat mati,
sisi Anyer - Darat mati,
sisi Anyer - Laut mati.
RUSAK RINGAN
REQUEST SERVICE
Medium
130000019360
Dokumentasi Dokumentasi
In Process
202
31 Oct 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Cleaning sensor sink in & sink out HL SKT CCSU
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
203
29 Oct 2026
Hasyim Alhabsyi
Dermaga 6
CIGADING 2
Fotocell lampu Threstle Dermaga 6 panel Nomor 2 dan Nomor 7 dari arah Darat rusak. Req. Ganti

note : secara fungsi, fotocell masih bagus
RUSAK RINGAN
REQUEST GANTI
Medium
130000019347
Dokumentasi Dokumentasi
In Process
204
29 Oct 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Melakukan pengukuran Megger Motor CC2 CSU di Workshop
Note : motor CC2 rembes. Rekues ganti seal
U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
RUSAK RINGAN
REQUEST GANTI
Medium
130000019344
Dokumentasi Dokumentasi
In Process
205
29 Oct 2026
Anton Diki W
Dermaga 6
CIGADING 2
Pengecekan Lampu penerangan Threstle Dermaga 6
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
206
29 Oct 2026
Anton Diki W
Dermaga 6
CIGADING 2
Lampu penerangan Threstle Dermaga 6 tiang ke 10 panel no 05 dari arah darat mati 1pcs
Note : power di kabel on
LAIK PAKAI
PREVENTIVE MAINTENANCE
Medium
Dokumentasi Dokumentasi
Outstanding
207
29 Oct 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Lubrikasi dan cleaning area safety device conveyor A102
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
208
28 Oct 2026
Anton Diki W
GSU-05
CIGADING 2
Chamswitch closing terpantau OK GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
209
28 Oct 2026
Anton Diki W
GSU-05
CIGADING 2
Chamswitch holding terpantau OK GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
210
28 Oct 2026
Anton Diki W
GSU-05
CIGADING 2
Chamswitch boom terpantau OK GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
211
28 Oct 2026
Anton Diki W
GSU-05
CIGADING 2
Lubrikasi roll festune cabin operator GSU 05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
212
28 Oct 2026
Anton Diki W
GSU-05
CIGADING 2
Kabel glend motor vibrating GSU 05 untuk saat ini masih terpantau amann
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
213
28 Oct 2026
Anton Diki W
GSU-05
CIGADING 2
Lubrikasi roll pendulum medium voltage GSU 05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
214
28 Oct 2026
Anton Diki W
GSU-06
CIGADING 2
Chamswitch closing terpantau OK GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
215
28 Oct 2026
Anton Diki W
GSU-06
CIGADING 2
Chamswitch holding terpantau OK GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
216
28 Oct 2026
Anton Diki W
GSU-06
CIGADING 2
Chamswitch boom terpantau OK GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
217
28 Oct 2026
Anton Diki W
GSU-06
CIGADING 2
Lubrikasi roll festune cabin operator GSU 06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
218
28 Oct 2026
Anton Diki W
GSU-06
CIGADING 2
Kabel glend motor vibrating GSU 06 luka/sobek , langsung action , sementara di rubber lalu di vinyl
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
219
28 Oct 2026
Anton Diki W
GSU-06
CIGADING 2
Lubrikasi roll pendulum medium voltage GSU 06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
220
28 Oct 2026
Anton Diki W
GSU-06
CIGADING 2
Pengencangan baud LSA CPA GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
221
28 Oct 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Pintu panel auxiliary engselnya patah, rekues repair
RELEASE
BY EXECUTOR
Medium
130000019327
Dokumentasi
Completed
222
28 Oct 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Cleaning dan lubrikasi underspeed GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
223
28 Oct 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Pengencengan baut panel LSA CPA Gantry GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
224
28 Oct 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Lampu boom sebelah anyer GSU-05 mati 1 pcs
RELEASE
BY EXECUTOR
Medium
130000019326
Dokumentasi
Completed
225
28 Oct 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Lampu boom sebelah anyer GSU-06 mati 1 pcs
RELEASE
BY EXECUTOR
Medium
130000019324
Dokumentasi
Completed
226
28 Oct 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Cleaning dan lubrikasi underspeed GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
227
28 Oct 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Cleaning dan lubrikasi roll pendulum medium voltage GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
228
28 Oct 2026
Anton Diki W
GSU-01
CIGADING 1
Pengukuran jalur input zerospeed GSU-01 sistem 1 PBCN 01 (hasil ok)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
229
28 Oct 2026
Anton Diki W
GSU-01
CIGADING 1
Pengukuran jalur input zerospeed GSU-01 sistem 2 PBCN 02 (hasil ok)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
230
28 Oct 2026
Anton Diki W
GSU-04
CIGADING 1
Pengukuran jalur input zerospeed GSU-04 sistem 2 PBCN 02 (hasil ok)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
231
28 Oct 2026
Anton Diki W
GSU-01
CIGADING 1
Cleaning motor drive closing GSU 01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
232
28 Oct 2026
Anton Diki W
GSU-01
CIGADING 1
Cleaning magnet switch GSU 01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
233
28 Oct 2026
Anton Diki W
GSU-01
CIGADING 1
Inspeksi Jalur sling komunikasi cabin operator no 2 dari cabin kondisi sling rantas GSU 01 , request ganti
RELEASE
REQUEST GANTI
Low
130000019329
Dokumentasi
Completed
234
28 Oct 2026
Anton Diki W
GSU-01
CIGADING 1
Rapihkan kabel yg muai / terbakar ( potong ) zerospeed sebelah laut PBCN 01
Request repair
RELEASE
REQUEST REPAIR
Low
130000019328
Dokumentasi
Completed
235
28 Oct 2026
Anton Diki W
GSU-01
CIGADING 1
Cleaning zerospeed sistem 1&2 GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
236
28 Oct 2026
Anton Diki W
GSU-01
CIGADING 1
Cleaning motor gate power pack dan panel gate powerpack GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
237
28 Oct 2026
Anton Diki W
GSU-01
CIGADING 1
Motor creeper gantry GSU 01 tidak 3pcs, 1pcs sebelah laut dan 2pcs sebelah darat
RUSAK RINGAN
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi Dokumentasi
Ready to Use
238
28 Oct 2026
Anton Diki W
GSU-01
CIGADING 1
Motor gantry GSU 01 tidak terpasang 3pcs sebelah laut
RELEASE
BY EXECUTOR
PANTAU
Dokumentasi Dokumentasi
Completed
239
28 Oct 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Grounding area Motor creeper gantry sebelah laut hilang, rekues pasang
RUSAK RINGAN
REQUEST PENAMBAHAN
PANTAU
130000019654
Dokumentasi
In Process
240
28 Oct 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Motor creeper gantry tidak terpasang 3 pcs, rekues pasang
RUSAK RINGAN
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
241
28 Oct 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Cleaning motor drive trolley GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
242
28 Oct 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Cleaning motor powerpack belt feeder hopper GSU-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
243
28 Oct 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Cleaning dan lubrikasi zerospeed sistem 1 dan 2 di GSU-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
244
27 Oct 2026
Anton Diki W
Conveyor A101
CIGADING 2
Pengukuran suhu motor drive A101 :
Drive 44
Bearing 44
Fan 38
Brake 43
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
245
27 Oct 2026
Anton Diki W
Conveyor A101
CIGADING 2
Dudukan sling pullcord A101 patah di tiang nomor 200 , rekues repair
LAIK PAKAI
REQUEST REPAIR
Medium
130000019309
Dokumentasi
In Process
246
27 Oct 2026
Anton Diki W
Conveyor A101
CIGADING 2
Pengukuran suhu ruang panel elektrik
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
247
27 Oct 2026
Anton Diki W
Conveyor A101
CIGADING 2
Lubrikasi safety device area conveyor A101
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
248
27 Oct 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Pengecekan lampu penerangan area tail conveyor A101. Semua lampu dalam kondisi OK
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
249
27 Oct 2026
Hasyim Alhabsyi
Dermaga 6
CIGADING 2
Lampu penerangan 120W di Dermaga 6 pada tiang No.10 (dihitung dari arah Anyer), nyala sebagian (rusak). Request Ganti
RELEASE
BY EXECUTOR
Medium
130000018596
Dokumentasi Dokumentasi
Completed
250
26 Oct 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Pengukuran pencahayaan panel room elektrik dengan alat Lux meter di PHC-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
251
26 Oct 2026
Anton Diki W
PHC-02
CIGADING 1
Pengukuran suhu ruang trafo 48 derajat Celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
252
26 Oct 2026
Anton Diki W
PHC-02
CIGADING 1
Pengukuran suhu ruang panel gantry 42 derajat Celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
253
26 Oct 2026
Anton Diki W
PHC-02
CIGADING 1
Pengukuran suhu motor PHC-02 :

HOLDING
drive 42
Bearing 41
Fan 51
Brake 1 & 2 45 43

CLOSING
Drive 48
Bearing 44
Fan 52
Brake 1 & 2 48 47

SLEWING 1
Drive 42
Bearing 40
Fan 41
Brake 45

SLEWING 2
Drive 47
Bearing 42
Fan 41
Brake 48

LUFFING
Drive 39
Bearing 35
Fan 38
Brake 40
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
254
26 Oct 2026
Anton Diki W
PHC-02
CIGADING 1
cleaning power pack break holding , closing dan luffing PHC 02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
255
26 Oct 2026
Anton Diki W
PHC-02
CIGADING 1
exhaust fan noise kasar req. service PHC 02
RUSAK RINGAN
REQUEST SERVICE
Medium
130000018901
Dokumentasi
In Process
256
26 Oct 2026
Anton Diki W
PHC-02
CIGADING 1
Exhaust fan ruang trafo mati 1 sebelah anyer PHC 02
RUSAK RINGAN
REQUEST SERVICE
Medium
130000019291
Dokumentasi
In Process
257
26 Oct 2026
Anton Diki W
PHC-02
CIGADING 1
Motor creeper No.3 sebalah darat anyer tidak terpasang req. Pasang , PHC 02
RUSAK RINGAN
REQUEST SERVICE
Medium
Dokumentasi
Outstanding
258
26 Oct 2026
Anton Diki W
PHC-02
CIGADING 1
Motor gantry No.5 sebelah darat merak tidak terpasang req. Pasang
PHC 02
RUSAK RINGAN
REQUEST SERVICE
Medium
Dokumentasi Dokumentasi
Outstanding
259
26 Oct 2026
Anton Diki W
PHC-02
CIGADING 1
Kondisi Slipring PHC 02 terpantau OK
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
260
26 Oct 2026
Anton Diki W
PHC-02
CIGADING 1
Cleaning motor powerpack gate Hooper dan panel powerpack gate Hooper PHC 02 before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
261
26 Oct 2026
Anton Diki W
PHC-02
CIGADING 1
Cleaning motor creeper gantry PHC 02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
262
26 Oct 2026
Anton Diki W
PHC-02
CIGADING 1
Kabel power incoming Drive VSD Closed/gantry PHC-02 kabel power indikasi muai/terbakar. Suhu kabel 48 ⁰C sebelum panel di buka, setelah panel dibuka menjadi 40 ⁰C. Perbandingan dengan yang lain 30 ⁰C. Req.repair

Sudah di infokan ke.
Cc-elektrik cg1
Pak haykal
Mas suleman

(Akan dilakukan perbaikan setelah bongkaran gandum selesai est.2 hari, sementara dilakukan pengecekan suhu secara berkala oleh elektrik shift)
RELEASE
BY EXECUTOR
Medium
130000019292
Dokumentasi
Completed
263
26 Oct 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Kondisi ruang trafo kotor, rekues cleaning
LAIK PAKAI
REQUEST BERSIHKAN
PANTAU
Dokumentasi Dokumentasi
Ready to Use
264
26 Oct 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Kondisi slipring PHC-01 terpantau aman
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
265
26 Oct 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Pengukuran suhu motor PHC-01
HOLDING
Fan 47
Drive 40
Bearing 40
Brake 1 & 2 41 & 41

CLOSING
Fan 50
Drive 47
Bearing 51
Brake 1 & 2 52 & 51

SLEWING 1
Fan 40
Drive 45
Bearing 43
Brake 1 50

SLEWING 2
Fan 41
Drive 47
Bearing 43
Brake 1 51

LUFFING
Fan 40
Drive 37
Bearing 36
Brake 1 37
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
266
24 Oct 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Pengukuran pencahayaan ruang panel room dengan alat Lux meter di DLLC-03
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
267
24 Oct 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Pengecekan lampu penerangan di seluruh titik Crane DLLC-03, kondisi OK dan kondisi Normal semua.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
268
24 Oct 2026
Anton Diki W
DLLC-04
CIGADING 1
Pengukuran suhu motor DLLC-04:
HOLDING
Fan 48
Drive 47
Bearing 42
Brake 1 & 2 49 & 50

CLOSING
Fan 47
Drive 45
Bearing 40
Brake 1 & 2 51 & 54

SLEWING 1
Fan 49
Drive 41
Bearing 40
Brake 1 45

SLEWING 2
Fan 50
Drive 42
Bearing 40
Brake 1 46

LUFFING
Fan 42
Drive 41
Bearing 34
Brake 1 40
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
269
24 Oct 2026
Anton Diki W
DLLC-04
CIGADING 1
Pengukuran suhu ruang panel elektrik 31 derajat Celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
270
24 Oct 2026
Anton Diki W
DLLC-04
CIGADING 1
Pengukuran suhu ruang trafo 32 derajat Celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
271
24 Oct 2026
Anton Diki W
DLLC-04
CIGADING 1
Pengukuran suhu ruang panel Gantry 29 derajat Celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
272
24 Oct 2026
Anton Diki W
DLLC-04
CIGADING 1
Kondisi Slipring DLLC 04 untuk saat ini masih terpantau OK
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
273
24 Oct 2026
Anton Diki W
DLLC-04
CIGADING 1
Cleaning motor creeper gantry DLLC 04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
274
24 Oct 2026
Anton Diki W
DLLC-04
CIGADING 1
Cleaning panel gate Hooper DLLC-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
275
24 Oct 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
exhaust fan motor room berdengung, kemungkinan sementara dari bearing fan motornya. Rekues servis
RUSAK RINGAN
REQUEST SERVICE
Medium
130000019284
Dokumentasi
In Process
276
24 Oct 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Pengukuran suhu motor DLLC-03:
HOLDING
Fan 46
Drive 43
Bearing 40
Brake 1 & 2 53 & 55

SLEWING 2
Fan 45
Drive 39
Bearing 38
Brake 1 37

LUFFING
Fan 40
Drive 38
Bearing 36
Brake 1 40
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
277
24 Oct 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Pengukuran suhu motor fan closing 45 derajat celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
278
24 Oct 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Pengukuran suhu motor drive closing 44 derajat celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
279
24 Oct 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Kondisi slipring terpantau aman (bersih) DLLC-03
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
280
24 Oct 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Pengukuran suhu bearing motor slewing 1 36 derajat celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
281
24 Oct 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Pengukuran suhu ruang panel elektrik 25 derajat celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
282
24 Oct 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Pengukuran suhu motor fan slewing 45 derajat celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
283
24 Oct 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Pengukuran suhu brake slewing 41 derajat celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
284
24 Oct 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Pengukuran suhu drive motor slewing 1 arah laut 37 derajat Celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
285
24 Oct 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Pengukuran suhu ruang trafo 29 derajat Celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
286
24 Oct 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Pengencangan baud panel gantry yang kendor (berakibat getaran saat running)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
287
24 Oct 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Pengukuran suhu ruang panel gantry 23 derajat Celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
288
23 Oct 2026
Anton Diki W
Feeding SGT
CIGADING 1
Cleaning motor bucket elevator SGT before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
289
23 Oct 2026
Hasyim Alhabsyi
Feeding SGT
CIGADING 1
Cleaning safety device area bucket conveyor SGT
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
290
23 Oct 2026
Hasyim Alhabsyi
Feeding SGT
CIGADING 1
Pengecekan kontrol fan blower dan cleaning panel kontrolnya.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
291
23 Oct 2026
Hasyim Alhabsyi
Feeding SGT
CIGADING 1
Pengencangan baut-baut di panel Feeding SGT
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
292
22 Oct 2026
Anton Diki W
Dermaga 5
CIGADING 2
Kontaktor lampu dermaga 5 terpantau dengung , pantau
LAIK PAKAI
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi
Ready to Use
293
22 Oct 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Melakukan inspeksi elektrik di area Dermaga 5, Pengecekan trafo, Panel power lampu penerangan, dan lampu penerangan. Kondisi lampu penerang D5 sudah OK (nyala) untuk semua tiang.

Tiang 1 dan 3 dari Anyer menggunakan fotocell (beda jalur dengan tiang lainnya).
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
294
21 Oct 2026
Anton Diki W
CCSU
CIGADING 1
Cleaning motor fan CC3
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
295
21 Oct 2026
Anton Diki W
CCSU
CIGADING 1
Cleaning motor drive CC3
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
296
20 Oct 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Tray kabel conveyor A103 kabel bagian merak rusak. req. repair jalur
RUSAK RINGAN
REQUEST REPAIR
Medium
130000019255
Dokumentasi Dokumentasi
In Process
297
20 Oct 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Lampu penerangan Conveyor A103 mati 3 pcs.
Sebelah anyer mati 1 Pcs No. 4 dari laut
Sebelah merak 2 Pcs No. 1 dan No. 5 dari laut
RELEASE
BY EXECUTOR
Medium
130000019254
Dokumentasi Dokumentasi
Completed
298
20 Oct 2026
Hasyim Alhabsyi
TFH & Feeding
CIGADING 2
Lampu LED Conveyor TFH mati 3 pcs, sebelah anyer 1 pcs. Sebelah darat 2 pcs, rekues ganti
LAIK PAKAI
REQUEST GANTI
Medium
130000019254
Dokumentasi Dokumentasi
In Process
299
20 Oct 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Main trafo P1C banyak sawangnya dan kotor, rekues cleaning
RELEASE
BY EXECUTOR
Medium
130000019253
Dokumentasi Dokumentasi
Completed
300
20 Oct 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Lubrikasi seluruh safety device di area Conveyor A103
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
301
20 Oct 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Ruang panel P1C dinding banyak yang retak dan ada lubang di sisi ac, rekues repair
RELEASE
BY EXECUTOR
PANTAU
Dokumentasi Dokumentasi
Completed
302
20 Oct 2026
Hasyim Alhabsyi
TFH & Feeding
CIGADING 2
Cover fan motor drive TFH korosi, rekues ganti
RELEASE
BY EXECUTOR
PANTAU
Dokumentasi
Completed
303
20 Oct 2026
Anton Diki W
Conveyor A103
CIGADING 2
Pengukuran suhu motor drive A103
Motor 1
Drive 41
Fan 39
Bearing 36
Brake 40

Motor 2
Drive 37
Bearing 32
Fan 33
Brake 36
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
304
19 Oct 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Pengukuran suhu ruang trafo PHC-02 saat Shutdown Inspection.
Hasil pengukuran berada di range normal.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
305
19 Oct 2026
Anton Diki W
PHC-01
CIGADING 1
Cleaning panel cabin desk operator PHC 01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
306
19 Oct 2026
Anton Diki W
PHC-01
CIGADING 1
Kondisi slipring PHC-01 untuk saat ini terpantau Kotor , request cleaning
RELEASE
BY EXECUTOR
Low
Dokumentasi
Completed
307
19 Oct 2026
Anton Diki W
PHC-01
CIGADING 1
Pengetesan gate Hooper open / close : OK , PHC 01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
308
19 Oct 2026
Anton Diki W
PHC-01
CIGADING 1
Cleaning dan lubrikasi creeper gantry PHC 01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
309
19 Oct 2026
Anton Diki W
PHC-01
CIGADING 1
Cleaning motor powerpack gate Hooper dan panel powerpack gate Hooper PHC 01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
310
19 Oct 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Kondisi slipring PHC-02 terpantau aman
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
311
19 Oct 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Cleaning motorpowerpack gate hopper PHC-02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
312
17 Oct 2026
Anton Diki W
DLLC-04
CIGADING 1
Hasil Megger Motor gantry DLLC 04 no 08 sebelah merak

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
313
17 Oct 2026
Anton Diki W
DLLC-04
CIGADING 1
Hasil Megger Motor gantry DLLC 04 no 02 sebelah laut

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
314
17 Oct 2026
Anton Diki W
DLLC-04
CIGADING 1
Hasil Megger Motor gantry DLLC 04 no 06 sebelah darat

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
315
17 Oct 2026
Anton Diki W
DLLC-04
CIGADING 1
Hasil Megger Motor gantry DLLC 04 no 04 sebelah laut oke

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
316
14 Oct 2026
Anton Diki W
DLLC-04
CIGADING 1
Pengukuran suhu motor DLLC-04:
HOLDING
Fan 45
Drive 42
Bearing 40
Brake 1 & 2 42 & 43

CLOSING
Fan 45
Drive 42
Bearing 40
Brake 1 & 2 43 & 42

SLEWING 1
Fan 44
Drive 39
Bearing 36
Brake 1 39

SLEWING 2
Fan 45
Drive 41
Bearing 38
Brake 1 37

LUFFING
Fan 41
Drive 38
Bearing 36
Brake 1 40
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
317
13 Oct 2026
Anton Diki W
Conveyor A102
CIGADING 2
Pengukuran suhu motor drive A102
Motor kanan
Drive 41
Fan 42
Bearing 39

Motor kiri
Drive 42
Bearing 38
Fan 40
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
318
13 Oct 2026
Anton Diki W
Conveyor A102
CIGADING 2
Pengukuran suhu motor single drive A102 :
Drive 39
Fan 37
Bearing 38
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
319
12 Oct 2026
Anton Diki W
GSU-04
CIGADING 1
Lubrikasi roll festune cabin operator GSU 04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
320
12 Oct 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Lubrikasi motor creeper brake gantry sisi laut dan darat.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
321
09 Oct 2026
Anton Diki W
Feeding SGT
CIGADING 1
Cleaning motor bucket elevator SGT before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
322
08 Oct 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Kondisi konekan dan dudukan motor pinlock PHC 01 sebelah darat korosi. request service.
RELEASE
BY EXECUTOR
Medium
130000019183
Dokumentasi
Completed
323
08 Oct 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Hasil Megger Motor pinlock phc-01 sebelah darat, Oke
U1 - G : 110 Mohm
V1 - G : 110 Mohm
W1 - G : 110 Mohm
U2 - G : 110 Mohm
V2 - G : 110 Mohm
W2 - G : 110 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 110 Mohm
U1 - W2 : 110 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 110 Mohm
V1 - W2 : 110 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 110 Mohm
W1 - V2 : 110 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
324
08 Oct 2026
Anton Diki W
PHC-01
CIGADING 1
Kondisi konekan dan dudukan motor pinlock PHC 01 sebelah laut korosi request service, ( note nilai tahanan Oke )
RELEASE
BY EXECUTOR
Medium
130000019182
Dokumentasi
Completed
325
08 Oct 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Cleaning motor gantry PHC-02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
326
08 Oct 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Hasil Megger Motor gantry phc-02 No. 7 sebelah darat, Oke
U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
327
08 Oct 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Hasil Megger Motor MV. Cable drum PHC-01 sebelah anyer , Oke
U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
328
08 Oct 2026
Anton Diki W
PHC-01
CIGADING 1
Hasil Megger Motor pinlock phc-01 sebelah laut , Oke

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
329
08 Oct 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Hasil Megger Motor gantry phc-02 no 7 sebelah darat , Oke
U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
330
08 Oct 2026
Anton Diki W
PHC-01
CIGADING 1
Hasil Megger Motor MV. Cable drum phc-01 sebelah merak , Oke

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
331
08 Oct 2026
Anton Diki W
PHC-02
CIGADING 1
Hasil Megger Motor gantry phc-02 no 4 sebelah laut , Oke

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
332
08 Oct 2026
Anton Diki W
PHC-02
CIGADING 1
Hasil Megger Motor gantry phc-02 no 1 sebelah laut , Oke

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
333
08 Oct 2026
Anton Diki W
PHC-02
CIGADING 1
Hasil Megger Motor gantry phc-02 no 2 sebelah laut , Oke

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
334
07 Oct 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Pengukuran suhu panel holding,slewing,closing,luffing DLLC-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
335
07 Oct 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Pengukuran suhu ruang panel elektrik DLLC-04
Hasil pengukuran ruang panel elektrik DLLC-04 30.5 derajat celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
336
07 Oct 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Pengukuran suhu ruang trafo DLLC-04
Suhu ruang trafo 44.0 derajat celcius.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
337
07 Oct 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Pengukuran panel LV DLLC-04 41.8 derajat celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
338
07 Oct 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Pengukuran suhu panel gantry DLLC-04.
Hasil pengukuran panel gantry DLLC-04 37.9 derajat celcius.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
339
07 Oct 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Pengencengan baud chamswitch holding yang kendor di DLLC-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
340
07 Oct 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Kondisi slipring DLLC-04 terpantau aman
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
341
07 Oct 2026
Anton Diki W
DLLC-04
CIGADING 1
Cleaning panel cabin desk operator DLLC-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
342
07 Oct 2026
Anton Diki W
DLLC-04
CIGADING 1
Cleaning panel gate hopper DLLC-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
343
06 Oct 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Pengukuran suhu panel P1B 27.3 derajat Celcius. Kondisi sedang running
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
344
06 Oct 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Pengukuran suhu trafo P1B 38.3 derajat Celcius.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
345
06 Oct 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Pengukuran suhu ruang panel P1C 28.5 derajat Celcius. Kondisi sedang running
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
346
06 Oct 2026
Anton Diki W
Conveyor A103
CIGADING 2
Pengukuran suhu motor drive A103
Motor 1
Drive 41
Fan 39
Bearing 38
Brake 41

Motor 2
Drive 41
Bearing 35
Fan 36
Brake 38
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
347
06 Oct 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Lubrikasi safety device area conveyor A103
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
348
05 Oct 2026
Anton Diki W
CCSU
CIGADING 1
Suhu motor main pump hidrolik CSU
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
349
05 Oct 2026
Anton Diki W
CCSU
CIGADING 1
Suhu fan CC3 kiri
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
350
05 Oct 2026
Anton Diki W
CCSU
CIGADING 1
Suhu fan CC3 kanan
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
351
05 Oct 2026
Anton Diki W
CCSU
CIGADING 1
Suhu Motor drive CC3
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
352
05 Oct 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Pengukuran suhu motor feeding pump 58.2 derajat Celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
353
05 Oct 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Pengukuran suhu motor emergency pump CSU 63.9 derajat Celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
354
05 Oct 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Pengukuran suhu motor fan CSU 60.8 Derajat Celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
355
02 Oct 2026
Hasyim Alhabsyi
Tower 2
CIGADING 1
Pengukuran suhu panel TTN-1 Tower 2.
27,4 derajat celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
356
02 Oct 2026
Hasyim Alhabsyi
Conveyor PBCN 1
CIGADING 1
Pengukuran suhu panel TTN-1 tower 11. 33,6 derajat Celcius
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
357
01 Oct 2026
Anton Diki W
Conveyor A102
CIGADING 2
Lubrikasi safety device area conveyor A102
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
358
01 Oct 2026
Anton Diki W
Conveyor A102
CIGADING 2
Pengukuran suhu motor drive A102
Motor kanan
Drive 38
Fan 39
Bearing 38

Motor kiri
Drive 40
Bearing 39
Fan 39
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
359
01 Oct 2026
Anton Diki W
Conveyor A102
CIGADING 2
Pengukuran suhu motor single drive A102 :
Drive 40
Fan 38
Bearing 36
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
360
30 Sep 2026
Anton Diki W
GSU-01
CIGADING 1
Lubrikasi roll festune cabin operator GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
361
30 Sep 2026
Anton Diki W
GSU-01
CIGADING 1
Cleaning motor drive holding, closing dan trolley GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
362
30 Sep 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Kontaktor brake trolley pong sebelah laut nomor 1 pcs, Rekues ganti GSU-04
LAIK PAKAI
REQUEST GANTI
Medium
130000019073
Dokumentasi Dokumentasi
Completed
363
30 Sep 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Kontaktor brake holding pong. Panel nomor 2 sebelah anyer
LAIK PAKAI
REQUEST GANTI
Medium
130000019070
Dokumentasi Dokumentasi
Completed
364
30 Sep 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Kontaktor brake holding pong 2 pcs dan ada indikasi terbakar. Panel sebelah anyer nomor 1
RELEASE
REQUEST GANTI
Medium
Dokumentasi Dokumentasi
Completed
365
28 Sep 2026
Anton Diki W
CCSU
CIGADING 1
Cleaning sensor sink in sink out HL SKT CSU
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
366
26 Sep 2026
Anton Diki W
DLLC-03
CIGADING 1
Hasil Megger Motor gantry DLLC-03 no 8 sebelah darat , Oke
U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
367
26 Sep 2026
Anton Diki W
DLLC-03
CIGADING 1
Hasil Megger Motor gantry DLLC-03 no 7 sebelah darat , Oke
U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
368
26 Sep 2026
Anton Diki W
DLLC-03
CIGADING 1
Hasil Megger Motor gantry DLLC-03 no 6 sebelah darat , Oke
U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
369
26 Sep 2026
Anton Diki W
DLLC-03
CIGADING 1
Hasil Megger Motor gantry DLLC-03 no 5 sebelah darat , Oke
U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
370
26 Sep 2026
Anton Diki W
DLLC-03
CIGADING 1
Hasil Megger Motor gantry DLLC-03 no 4 sebelah laut , Oke
U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
371
26 Sep 2026
Anton Diki W
DLLC-03
CIGADING 1
Hasil Megger Motor gantry DLLC-03 no 3 sebelah laut , Oke
U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
372
26 Sep 2026
Anton Diki W
DLLC-03
CIGADING 1
Hasil Megger Motor gantry DLLC-03 no 2 sebelah laut , Oke
U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
373
26 Sep 2026
Anton Diki W
DLLC-03
CIGADING 1
Hasil Megger Motor gantry DLLC-03 no 01 sebelah laut , Oke
U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
374
24 Sep 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1B Motor 3
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
375
24 Sep 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1B Motor 2
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
376
24 Sep 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1B Motor 1
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
377
24 Sep 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu ruang Trafo P1B
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
378
24 Sep 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu ruang panel elektrik P1B
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
379
23 Sep 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Holding GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
380
23 Sep 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Boom trolley Inverter GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
381
23 Sep 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Gantry Inverter GSU-01 : 34.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
382
23 Sep 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Trafo GSU-01 : 42.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
383
23 Sep 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu ruang panel elektrik GSU-04 : 28.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
384
23 Sep 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu panel Closing GSU-04 : 27.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
385
23 Sep 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu panel Holding inverter GSU-04 : 32.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
386
23 Sep 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu panel Gantry GSU-04 : 29.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
387
23 Sep 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel PLC Control GSU-01 : 41.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
388
23 Sep 2026
Anton Diki W
GSU-01
CIGADING 1
Lidah kontaktor coil brake trolley pong 1pcs ( sebelah laut ) GSU 01, request ganti
RELEASE
REQUEST GANTI
Medium
130000019069
Dokumentasi
Completed
389
23 Sep 2026
Anton Diki W
GSU-01
CIGADING 1
Lidah kontaktor coil brake closing pong 1pcs ( sebelah Anyer panel no 02 ) GSU 01, request ganti
RELEASE
REQUEST GANTI
Medium
130000019066
Dokumentasi
Completed
390
23 Sep 2026
Anton Diki W
GSU-01
CIGADING 1
Lidah kontaktor coil brake holding pong 1pcs ( sebelah anyer panel no. 01 ) GSU 01, request ganti
RELEASE
REQUEST GANTI
Medium
130000019067
Dokumentasi
Completed
391
23 Sep 2026
Anton Diki W
GSU-04
CIGADING 1
Lidah kontaktor coil brake trolley pong 1pcs ( kontaktor sebelah laut ) GSU 04, request ganti
RELEASE
REQUEST GANTI
Medium
130000019073
Dokumentasi
Completed
392
23 Sep 2026
Anton Diki W
GSU-04
CIGADING 1
Lidah kontaktor coil brake closing pong 1pcs ( sebelah merak panel no 01 ) GSU 04, request ganti
RELEASE
REQUEST GANTI
Medium
130000019071
Dokumentasi
Completed
393
23 Sep 2026
Anton Diki W
GSU-04
CIGADING 1
Lidah kontaktor coil brake holding pong 2pcs ( panel sebelah anyer no. 01 dan no. 02 ) GSU 04, request ganti
RELEASE
REQUEST GANTI
Medium
130000019070
Dokumentasi Dokumentasi
Completed
394
22 Sep 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Inspeksi dan Pengukuran suhu Vibrating (Motor 2)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
395
22 Sep 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Inspeksi dan Pengukuran suhu Vibrating (Motor 1)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
396
22 Sep 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Pengukuran suhu ruang panel GSU-05 : 34.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
397
22 Sep 2026
Anton Diki W
GSU-05
CIGADING 2
Pipa kabel lampu handrail hopper GSU-05 patah dan posisi ngegantung ke bawah (langsung action, pipa kabel sudah pada posisi sebelumnya)
LAIK PAKAI
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi Dokumentasi
Ready to Use
398
22 Sep 2026
Anton Diki W
GSU-05
CIGADING 2
Lubrikasi roll festune cabin operator GSU 05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
399
21 Sep 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Pengukuran suhu motor Feeding Pump : 34.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
400
21 Sep 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Inspeksi dan Pengukuran suhu Motor Main Pump : 39.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
401
21 Sep 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Inspeksi dan Pengukuran suhu Panel 2 CCSU : 27.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
402
21 Sep 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Inspeksi dan Pengukuran suhu Panel 1 CCSU : 23.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
403
21 Sep 2026
Anton Diki W
CCSU
CIGADING 1
Cleaning ruang panel elektrik CSU
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
404
21 Sep 2026
Anton Diki W
CCSU
CIGADING 1
Cleaning dan Penggantian filter fan ruang trafo CSU (before) dan ( after )
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
405
21 Sep 2026
Anton Diki W
CCSU
CIGADING 1
Trafo CSU kondisi kotor , request cleaning
RELEASE
REQUEST BERSIHKAN
Medium
130000019019
Dokumentasi Dokumentasi
Completed
406
21 Sep 2026
Anton Diki W
CCSU
CIGADING 1
Cleaning slipring CSU
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
407
21 Sep 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Cleaning paddleswitch CC3 CCSU
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
408
21 Sep 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Cleaning sink in sink out HL SKT CCSU
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
409
19 Sep 2026
Anton Diki W
PHC-01
CIGADING 1
Pengukuran suhu motor PHC-01 :

HOLDING
drive 43
Bearing 41
Fan 52
Brake 1 & 2 43 44

CLOSING
Drive 47
Bearing 45
Fan 50
Brake 1 & 2 50 49

SLEWING 1
Drive 42
Bearing 40
Fan 45
Brake 48

SLEWING 2
Drive 45
Bearing 41
Fan 43
Brake 48

LUFFING
Drive 38
Bearing 36
Fan 40
Brake 41
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
410
19 Sep 2026
Anton Diki W
PHC-01
CIGADING 1
Cleaning motor powerpack gate Hooper dan panel powerpack gate Hooper PHC 01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
411
17 Sep 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1A
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
412
17 Sep 2026
Anton Diki W
GSU-05
CIGADING 2
Hasil Megger Motor gantry GSU 05 no 01 sebelah laut , Oke

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
413
17 Sep 2026
Anton Diki W
GSU-06
CIGADING 2
Hasil Megger Motor gantry GSU 06 no 14 sebelah darat, Oke

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
414
17 Sep 2026
Anton Diki W
GSU-06
CIGADING 2
Hasil Megger Motor gantry GSU 06 no 16 sebelah darat , Oke

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
415
17 Sep 2026
Anton Diki W
GSU-05
CIGADING 2
Pengencangan baud panel LSA CPA Gantry GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
416
17 Sep 2026
Anton Diki W
GSU-05
CIGADING 2
Karet coupling motor kabel drum GSU 05 tipis , request ganti
RELEASE
BY EXECUTOR
Medium
130000019005
Dokumentasi Dokumentasi
Completed
417
17 Sep 2026
Anton Diki W
GSU-06
CIGADING 2
Chamswitch closing terpantau OK GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
418
17 Sep 2026
Anton Diki W
GSU-06
CIGADING 2
Chamswitch holding terpantau OK GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
419
17 Sep 2026
Anton Diki W
GSU-06
CIGADING 2
Lampu LED 18W motor room GSU-06 mati 6pcs dan tidak terpasang 6pcs , req ganti
LAIK PAKAI
REQUEST GANTI
-
130000018995
Dokumentasi
In Process
420
17 Sep 2026
Anton Diki W
GSU-06
CIGADING 2
Lubrikasi roll festune cabin operator GSU 06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
421
17 Sep 2026
Anton Diki W
GSU-05
CIGADING 2
Kabel glend motor vibrating GSU 05 luka/sobek , langsung action , sementara di rubber lalu di vinyl
LAIK PAKAI
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi Dokumentasi
Ready to Use
422
16 Sep 2026
Anton Diki W
DLLC-03
CIGADING 1
gate hopper DLLC-03 sebelah darat limit switch request di setting ulang
LAIK PAKAI
REQUEST SERVICE
PANTAU
Dokumentasi
Ready to Use
423
16 Sep 2026
Anton Diki W
DLLC-03
CIGADING 1
Slipring DLLC 03 untuk saat ini masih terpantau amann ( ok )
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
424
16 Sep 2026
Anton Diki W
DLLC-03
CIGADING 1
Cleaning panel cabin desk operator DLLC-03
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
425
16 Sep 2026
Anton Diki W
DLLC-03
CIGADING 1
Cleaning motor powerpack gate Hooper dan panel powerpack gate Hooper DLLC 03 before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
426
15 Sep 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Proses lubrikasi safety device di sepanjang Conveyor A102
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
427
15 Sep 2026
Anton Diki W
Conveyor A102
CIGADING 2
Pengukuran suhu motor drive A102
Motor kanan
Drive 37
Fan 38
Bearing 37

Motor kiri
Drive 40
Bearing 36
Fan 39
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
428
15 Sep 2026
Anton Diki W
Conveyor A102
CIGADING 2
Pengukuran suhu motor single drive A102 :
Drive 40
Fan 36
Bearing 37
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
429
14 Sep 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
TL LED 8W untuk penerangan di Panel room DLLC-02 mati 2 Pcs.
RELEASE
REQUEST GANTI
Medium
130000019016
Dokumentasi Dokumentasi
Completed
430
14 Sep 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Preventive elektrik area slipring DLLC-02, terpantau masih OK.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
431
14 Sep 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Cleaning dan Inspeksi Preventive area panel trafo room DLLC-02. Kondisi sementara masih OK
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
432
14 Sep 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Cleaning dan lubrikasi motor truster brake DLLC-02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
433
14 Sep 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Cleaning dan preventive panel elektrik dan operator control di hopper DLLC-02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
434
14 Sep 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Cleaning dan Preventive motor Powerpack DLLC-02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
435
10 Sep 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Inspeksi dan Pengukuran suhu Trafo P1C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
436
10 Sep 2026
Anton Diki W
Conveyor A103
CIGADING 2
Posisi Underspeed conveyor A103 berada di bawah, sehingga sering terkena Grease dan percikan material, antisipasi terjadi Error/ salah pembacaan. Req. Pindahkan lokasi kebagian atas
LAIK PAKAI
REQUEST REPAIR
-
Dokumentasi Dokumentasi
Outstanding
437
10 Sep 2026
Hasyim Alhabsyi
TFH & Feeding
CIGADING 2
Lampu penerangan LED 19W di Conveyor TFH mati 3 titik.
Sisi darat : Tiang Nomor 1 dan 5
Sisi laut : Tiang Nomor 5

Request Ganti
RELEASE
BY EXECUTOR
Medium
Dokumentasi Dokumentasi
Completed
438
10 Sep 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Lampu penerangan bulb 19W di Conveyor A103 mati 3 titik.
Sisi Anyer : Tiang Nomor 3
Sisi Merak : Tiang Nomor 1 dan 5
(Posisi dihitung dari arah Laut ke Darat)

Request Ganti
RUSAK RINGAN
REQUEST GANTI
Medium
Dokumentasi Dokumentasi
Outstanding
439
09 Sep 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing PHC-01 : 42.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
440
09 Sep 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Slewing PHC-01 : 32.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
441
09 Sep 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Closing PHC-01 : 32.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
442
09 Sep 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Holding PHC-01 : 33.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
443
09 Sep 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Power Panel PHC-01 : 31.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
444
09 Sep 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Inspeksi dan Pengukuran suhu panel gantry PHC-02 : 38.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
445
09 Sep 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Inspeksi dan Pengukuran suhu trafo PHC-02 : 41.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
446
09 Sep 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu trafo PHC-01 : 43.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
447
09 Sep 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Supporting elektrik eksekutor// Pemasangan kabel baru Medium Volatge 6KV di PHC-02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
448
08 Sep 2026
Anton Diki W
PHC-02
CIGADING 1
Motor kabel drum sebelah merak PHC-02 noise bearing kasar , couple macet pada saat di putar ke arah merak , request service
RUSAK RINGAN
REQUEST SERVICE
Medium
130000018946
Dokumentasi
In Process
449
08 Sep 2026
Anton Diki W
PHC-02
CIGADING 1
Motor kabel drum sebelah anyer PHC-02 noise bearing kasar, request service
RELEASE
REQUEST SERVICE
Medium
130000018947
Dokumentasi
Completed
450
08 Sep 2026
Anton Diki W
PHC-02
CIGADING 1
Motor cabel drum medium voltage PHC 02 sebelah merak hasil nilai 18,20Mohm ( no oke / tahanan kecil ) , request service
RUSAK RINGAN
REQUEST SERVICE
Medium
130000018948
Dokumentasi
In Process
451
08 Sep 2026
Anton Diki W
PHC-02
CIGADING 1
Motor cabel drum medium voltage PHC 02 sebelah Anyer hasil nilai 3,25Mohm - 10,39Mohm ( no oke / tahanan kecil ) , request service
RELEASE
REQUEST SERVICE
Medium
130000018949
Dokumentasi Dokumentasi
Completed
452
07 Sep 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Cleaning motorpowerpack belt feeder, rekues add motorpowerpack belt feeder dikasih atap agar tidak tertumpuk material di GSU-01
RELEASE
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Completed
453
07 Sep 2026
Anton Diki W
GSU-04
CIGADING 1
Lampu indikator running di panel gate powerpack GSU-04 tidak terpasang
RELEASE
REQUEST GANTI
Medium
Dokumentasi Dokumentasi
Completed
454
07 Sep 2026
Anton Diki W
GSU-04
CIGADING 1
Cleaning dan Penggantian filter motor fan holding closing trolley GSU-04 before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
455
07 Sep 2026
Anton Diki W
GSU-04
CIGADING 1
Pengecekkan lidah kontaktor holding closing trolley GSU-04 (kondisi kontaktor ok)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
456
07 Sep 2026
Anton Diki W
GSU-04
CIGADING 1
Cleaning dan lubrikasi zerospeed GSU-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
457
07 Sep 2026
Anton Diki W
GSU-04
CIGADING 1
Cleaning motor gate power pack dan panel gate powerpack GSU-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
458
07 Sep 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Penggantian filter motor fan holding, closing, dan trolley di area motor room GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
459
07 Sep 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Lubrikasi roll festune cabin operator GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
460
05 Sep 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi area ruang trafo, terdapat terdapat titik korosi dan terdapat beberapa baut yg kendor akibat vibrasi di pintu panel cubicle trafonya, Pantau
LAIK PAKAI
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi Dokumentasi
Ready to Use
461
05 Sep 2026
Anton Diki W
PHC-02
CIGADING 1
Pengukuran suhu motor PHC-02 :

HOLDING
drive 40
Bearing 40
Fan 51
Brake 1 & 2 39 40

CLOSING
Drive 41
Bearing 40
Fan 57
Brake 1 & 2 46 44

SLEWING 1
Drive 44
Bearing 38
Fan 46
Brake 43

SLEWING 2
Drive 42
Bearing 40
Fan 40
Brake 45

LUFFING
Drive 34
Bearing 33
Fan 38
Brake 36
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
462
05 Sep 2026
Anton Diki W
PHC-02
CIGADING 1
Inspeksi area slipring PHC-02 sudah mulai berdebu tebal. Req. service & cleaning
KOTOR
REQUEST SERVICE
Medium
130000018903
Dokumentasi Dokumentasi
In Process
463
05 Sep 2026
Anton Diki W
PHC-02
CIGADING 1
suhu trafo PHC-02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
464
05 Sep 2026
Anton Diki W
PHC-02
CIGADING 1
ruang trafo PHC-2 korosi bolong di bagian pojok laut dekat pintu
RELEASE
REQUEST REPAIR
Medium
130000018066
Dokumentasi
Completed
465
05 Sep 2026
Anton Diki W
PHC-02
CIGADING 1
Inspeksi pada bagian Exhaust fan, terdapat noise kasar saat posisi running.
Req. Service
RUSAK RINGAN
REQUEST SERVICE
Medium
130000018901
Dokumentasi
In Process
466
05 Sep 2026
Anton Diki W
PHC-02
CIGADING 1
Inspeksi area top boom. Motor pin lock phc-02 tidak terpasang
RUSAK RINGAN
REQUEST GANTI
Medium
130000018902
Dokumentasi Dokumentasi
In Process
467
05 Sep 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Pengukuran suhu motor PHC-01 :

HOLDING
drive 44
Bearing 41
Fan 54
Brake 1 & 2 45 44

CLOSING
Drive 47
Bearing 44
Fan 52
Brake 1 & 2 54 52

SLEWING 1
Drive 44
Bearing 38
Fan 46
Brake 55

SLEWING 2
Drive 50
Bearing 40
Fan 41
Brake 56

LUFFING
Drive 38
Bearing 39
Fan 42
Brake 43
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
468
05 Sep 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Suhu trafo phc-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
469
05 Sep 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Lubrikasi motor creeper dan roll pendulum cable drum di PHC-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
470
04 Sep 2026
Hasyim Alhabsyi
Conveyor BCNO
CIGADING 1
Bekas sayatan kabel penerangan BCNO, pantau
LAIK PAKAI
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi Dokumentasi
Ready to Use
471
04 Sep 2026
Anton Diki W
Conveyor C02
CIGADING 1
kabel C02 sebelah merak tiang no 4 dari laut
LAIK PAKAI
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi Dokumentasi
Ready to Use
472
03 Sep 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 29.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
473
03 Sep 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 30.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
474
03 Sep 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 31.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
475
03 Sep 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 29.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
476
03 Sep 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 29.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
477
03 Sep 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 32.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
478
03 Sep 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 32.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
479
03 Sep 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 30.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
480
03 Sep 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-02 : 28.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
481
03 Sep 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-02 : 48.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
482
03 Sep 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-01 : 33.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
483
03 Sep 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-01 : 40.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
484
03 Sep 2026
Anton Diki W
DLLC-01
CIGADING 1
Kondisi Slipring DLLC 01 untuk saat ini masih terpantau OK
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
485
03 Sep 2026
Anton Diki W
DLLC-01
CIGADING 1
Cleaning panel cabin desk operator DLLC-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
486
02 Sep 2026
Anton Diki W
CCSU
CIGADING 1
Cleaning ruang panel elektrik CSU
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
487
02 Sep 2026
Anton Diki W
CCSU
CIGADING 1
Cleaning motor drive CC3 dan Motor fan CC3
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
488
02 Sep 2026
Anton Diki W
CCSU
CIGADING 1
Preventive elektrik program Cleaning slipring CSU
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
489
01 Sep 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 30.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
490
01 Sep 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 32.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
491
01 Sep 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 31.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
492
01 Sep 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 30.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
493
01 Sep 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 31.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
494
01 Sep 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 30.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
495
01 Sep 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 29.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
496
01 Sep 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 31.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
497
01 Sep 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-04 : 36.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
498
01 Sep 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-03 : 41.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
499
01 Sep 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-04 : 42.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
500
01 Sep 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-03 : 47.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
501
01 Sep 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Kondisi slipring DLLC-04 saat ini masih terpantau OK
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
502
01 Sep 2026
Anton Diki W
DLLC-03
CIGADING 1
Pengetesan gate Hooper open / close : OK DLLC 03
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
503
01 Sep 2026
Anton Diki W
DLLC-03
CIGADING 1
Cleaning panel cabin desk operator DLLC-03
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
504
01 Sep 2026
Anton Diki W
DLLC-03
CIGADING 1
Kondisi Slipring DLLC 03 untuk saat ini masih terpantau OK
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
505
01 Sep 2026
Anton Diki W
DLLC-03
CIGADING 1
Cleaning motor powerpack gate Hooper dan panel powerpack gate Hooper DLLC 03
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
506
01 Sep 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi kondisi getaran di ruang trafo DLLC-04 saat running inspection, normal.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
507
31 Aug 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Inspeksi dan Pengukuran suhu Trafo P1C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
508
31 Aug 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Holding GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
509
31 Aug 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Boom trolley Inverter GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
510
31 Aug 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Gantry Inverter GSU-01 : 27.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
511
31 Aug 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Trafo GSU-01 : 43.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
512
31 Aug 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu ruang panel elektrik GSU-04 : 30.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
513
31 Aug 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu panel Closing GSU-04 : 28.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
514
31 Aug 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu panel Holding inverter GSU-04 : 27.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
515
31 Aug 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu panel Gantry GSU-04 : 26.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
516
31 Aug 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel PLC Control GSU-01 : 29.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
517
31 Aug 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Hasil Megger Motor drive A103 sebelah Merak

G - G : 0 Mohm
U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
518
31 Aug 2026
Anton Diki W
Conveyor A103
CIGADING 2
Hasil Megger Motor drive A103 sebelah anyer

G - G : 0 Mohm
U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
519
31 Aug 2026
Anton Diki W
GSU-04
CIGADING 1
Pengukuran suhu motor Gsu-04

Holding
Drive 53
Bearing 41
Fan 44

Closing
Drive 57
Bearing 42
Fan 46

Trolley
Drive 49
Bearing 42
Fan 45

Suhu Motor belt feeder GSU 04
Motor 01
Drive 32
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
520
31 Aug 2026
Anton Diki W
GSU-04
CIGADING 1
Bearing roll festune lepas 4 pcs GSU-04, bagian anyer
rekues ganti
RELEASE
REQUEST GANTI
Medium
130000018835
Dokumentasi Dokumentasi
Completed
521
31 Aug 2026
Anton Diki W
GSU-04
CIGADING 1
Sling safety komunikasi putus di GSU 04 sebelah darat, req ganti
Sementara di vynil dan ( sudah di infokan ke elektrik eksekutor )
RELEASE
REQUEST GANTI
Medium
130000018836
Dokumentasi Dokumentasi
Completed
522
28 Aug 2026
Anton Diki W
Conveyor C02
CIGADING 1
Pengecekan suhu motor C02 :
Motor 1
Drive 45
Bearing 44
Brake 47

Motor 2
Drive 48
Bearing 41
Brake 48
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
523
28 Aug 2026
Anton Diki W
Conveyor BCNO
CIGADING 1
Pengecekan suhu motor BCNO :
Motor 1
Drive 39
Bearing 44
Brake 48

Motor 2
Drive 46
Bearing 40
Brake 49
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
524
28 Aug 2026
Anton Diki W
Conveyor C02
CIGADING 1
Pengukuran suhu panel variabel speed drive (VSD) C02 motor B terpantau aman
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
525
27 Aug 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1B Motor 3
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
526
27 Aug 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1B Motor 2
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
527
27 Aug 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1B Motor 1
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
528
27 Aug 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu ruang Trafo P1B
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
529
27 Aug 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu ruang panel elektrik P1B
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
530
27 Aug 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi lampu penerangan di area Conveyor A102, masih terdapat banyak lampu yang mati.

Sisi Merak : 14 titik
Sisi Anyer : 36 titik
RELEASE
BY EXECUTOR
Medium
Dokumentasi Dokumentasi
Completed
531
27 Aug 2026
Anton Diki W
Conveyor A102
CIGADING 2
Pengukuran suhu motor drive A102
Motor kanan
Drive 39
Fan 38
Bearing 36

Motor kiri
Drive 40
Bearing 38
Fan 41
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
532
27 Aug 2026
Anton Diki W
Conveyor A102
CIGADING 2
Pengukuran suhu motor single drive A102 :
Drive 40
Fan 37
Bearing 36
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
533
26 Aug 2026
Anton Diki W
CCSU
CIGADING 1
Kondisi slipring CSU saat ini terpantau bersih dan ok
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
534
26 Aug 2026
Anton Diki W
CCSU
CIGADING 1
Cleaning dan Penggantian filter fan ruang trafo CSU (before) dan ( after )
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
535
25 Aug 2026
Anton Diki W
DLLC-02
CIGADING 1
Hasil Megger Motor gantry no 1 sebelah darat DLLC 02

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
536
25 Aug 2026
Anton Diki W
DLLC-02
CIGADING 1
Hasil Megger Motor gantry no 03 sebelah darat DLLC 02

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
537
25 Aug 2026
Anton Diki W
DLLC-02
CIGADING 1
Hasil Megger Motor kabel drum medium voltage DLLC-02

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
538
25 Aug 2026
Anton Diki W
CCSU
CIGADING 1
Hasil Megger Motor kabel drum medium voltage CSU

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
539
24 Aug 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing PHC-01 : 36.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
540
24 Aug 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Slewing PHC-01 : 38.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
541
24 Aug 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Closing PHC-01 : 35.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
542
24 Aug 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Holding PHC-01 : 29.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
543
24 Aug 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Power Panel PHC-01 : 28.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
544
24 Aug 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Inspeksi dan Pengukuran suhu panel gantry PHC-02 : 47.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
545
24 Aug 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Inspeksi dan Pengukuran suhu trafo PHC-02: 44.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
546
24 Aug 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu trafo PHC-01 : 42.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
547
24 Aug 2026
Anton Diki W
PHC-01
CIGADING 1
emergency di power panel elektrik tidak terpasang PHC 01
LAIK PAKAI
REQUEST PENAMBAHAN
-
Dokumentasi
Outstanding
548
24 Aug 2026
Anton Diki W
PHC-01
CIGADING 1
Kondisi slipring PHC-01 saat ini terpantau aman
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
549
24 Aug 2026
Anton Diki W
PHC-01
CIGADING 1
Pengukuran suhu motor PHC-01 :

HOLDING
drive 42
Bearing 40
Fan 51
Brake 1 & 2 41 40

CLOSING
Drive 44
Bearing 41
Fan 49
Brake 1 & 2 49 48

SLEWING 1
Drive 42
Bearing 36
Fan 39
Brake 45

SLEWING 2
Drive 40
Bearing 36
Fan 41
Brake 49

LUFFING
Drive 37
Bearing 36
Fan 41
Brake 38
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
550
24 Aug 2026
Anton Diki W
PHC-01
CIGADING 1
Ruang trafo phc-01 dinding arah laut ada yang bolong 2 titik. Ditakutkan masuk air, rekues repair/foam
RELEASE
REQUEST REPAIR
Medium
Dokumentasi Dokumentasi
Completed
551
24 Aug 2026
Anton Diki W
PHC-01
CIGADING 1
Cleaning motor dan panel motor powerpack gate Hooper PHC 01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
552
24 Aug 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Inspeksi pengukuran vibrasi bearing slewing 2 dekat pintu PHC-02, overall good condition
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
553
24 Aug 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Kondisi slipring PHC-02 terpantau aman
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
554
22 Aug 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Dudukan konekan PHC-01 korosi, hasil megger ok
LAIK PAKAI
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi
Ready to Use
555
22 Aug 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Hasil Megger Motor gantry PHC-01 no 4 sisi laut sebelah Anyer

U1 - G : 20 Mohm
V1 - G : 12 Mohm
W1 - G : 20 Mohm
U2 - G : 17 Mohm
V2 - G : 2 Mohm
W2 - G : 20 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 20 Mohm
U1 - W2 : 20 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 20 Mohm
V1 - W2 : 20 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 20 Mohm
W1 - V2 : 20 Mohm
RUSAK RINGAN
PREVENTIVE MAINTENANCE
Medium
130000018796
Dokumentasi
In Process
556
22 Aug 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Hasil Megger Motor gantry PHC-01 no 6 sisi darat sebelah merak

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
557
22 Aug 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Hasil Megger Motor gantry PHC-01 no 8 sisi darat sebelah merak

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
558
22 Aug 2026
Anton Diki W
PHC-01
CIGADING 1
Hasil Megger Motor gantry PHC-01 no 7 sebelah darat

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
559
22 Aug 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Hasil Megger Motor gantry PHC-01 no 5 sisi darat sebelah merak

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
560
22 Aug 2026
Anton Diki W
PHC-01
CIGADING 1
Hasil Megger Motor gantry PHC-01 no 3 sisi laut sebelah Anyer

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
561
22 Aug 2026
Anton Diki W
PHC-01
CIGADING 1
Hasil Megger Motor gantry PHC-01 no 2 sisi laut sebelah merak

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
562
22 Aug 2026
Anton Diki W
PHC-01
CIGADING 1
Hasil Megger Motor gantry PHC-01 no 1 sisi laut sebelah merak

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
563
21 Aug 2026
Anton Diki W
Feeding SGT
CIGADING 1
Cleaning motor bucket elevator SGT before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
564
21 Aug 2026
Hasyim Alhabsyi
Feeding SGT
CIGADING 1
Cleaning safety device area bucket elevator SGT
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
565
20 Aug 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Inspeksi dan Pengukuran suhu Vibrating (Motor 2)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
566
20 Aug 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Inspeksi dan Pengukuran suhu Vibrating (Motor 1)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
567
19 Aug 2026
Anton Diki W
DLLC-04
CIGADING 1
Cleaning panel cabin desk operator DLLC-04 before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
568
19 Aug 2026
Anton Diki W
DLLC-04
CIGADING 1
Kondisi Slipring DLLC 04 untuk saat ini masih terpantau OK
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
569
19 Aug 2026
Anton Diki W
DLLC-04
CIGADING 1
Cleaning dan lubrikasi motor gantry dan creeper gantry DLLC 04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
570
19 Aug 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Joystick operator sebelah kiri robek, rekues ganti di DLLC-03
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
571
19 Aug 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Panel cabin desk operator banyak abu roko, sudah langsung di action(cleaning) di DLLC-03
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
572
18 Aug 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Pengukuran suhu motor Fan CCSU : 36.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
573
18 Aug 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Inspeksi dan Pengukuran suhu Motor Main Pump : 43.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
574
18 Aug 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Inspeksi dan Pengukuran suhu Panel 2 CCSU : 27.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
575
18 Aug 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Inspeksi dan Pengukuran suhu Panel 1 CCSU : 26.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
576
18 Aug 2026
Anton Diki W
CCSU
CIGADING 1
Suhu fan CC3 kanan , Oke
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
577
18 Aug 2026
Anton Diki W
CCSU
CIGADING 1
Suhu fan CC3 kiri , Oke
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
578
18 Aug 2026
Anton Diki W
CCSU
CIGADING 1
Suhu Motor drive CC3 , Oke
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
579
18 Aug 2026
Anton Diki W
CCSU
CIGADING 1
Suhu Motor emergency pump CSU , OKE
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
580
18 Aug 2026
Anton Diki W
CCSU
CIGADING 1
Suhu Motor feeding pump CSU , OKE
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
581
18 Aug 2026
Anton Diki W
CCSU
CIGADING 1
Suhu Motor fan CSU , OKE : 50.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
582
18 Aug 2026
Anton Diki W
CCSU
CIGADING 1
Suhu motor main pump hidrolik CSU ,OKE
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
583
14 Aug 2026
Anton Diki W
Conveyor PBCN 1
CIGADING 1
Tray kabel di area conveyor PBCN Tertimpa matrial, request cleaning
RELEASE
REQUEST BERSIHKAN
Medium
Dokumentasi Dokumentasi
Completed
584
14 Aug 2026
Anton Diki W
Conveyor PBCN 2
CIGADING 1
Belt rip PBCN-02 perlu identifikasi lanjutan pengecekan jalur kabel/inputan dari relay ke PLC di panel tower 11.
LAIK PAKAI
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi
Ready to Use
585
14 Aug 2026
Anton Diki W
Conveyor PBCN 1
CIGADING 1
Sensor proximity conveyor PBCN 01 dan PBCN 02 Kondisi Oke
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
586
14 Aug 2026
Anton Diki W
Conveyor PBCN 1
CIGADING 1
Pull cord no tiang 80 putus di conveyor PBCN 01 , request repair
RELEASE
REQUEST REPAIR
Medium
Dokumentasi Dokumentasi
Completed
587
14 Aug 2026
Anton Diki W
Conveyor PBCN 1
CIGADING 1
Lubrikasi zerospeed PBCN 01 dan PBCN 02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
588
14 Aug 2026
Anton Diki W
Conveyor PBCN 1
CIGADING 1
Pengecekan dan cleaning zerospeed PBCN 01 dan PBCN 02 Kondisi Oke
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
589
14 Aug 2026
Hasyim Alhabsyi
Conveyor PBCN 2
CIGADING 1
Zerospeed GSU-01 kemasukan semut, langsung di cleaning
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
590
13 Aug 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Dudukan sling pullcord sebelah anyer A102 patah di tiang nomor 692, rekues repair
RELEASE
BY EXECUTOR
Medium
130000018728
Dokumentasi
Completed
591
13 Aug 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Dudukan sling pullcord sebelah anyer A102 patah di tiang nomor 697, rekues repair
RELEASE
BY EXECUTOR
Medium
130000018728
Dokumentasi
Completed
592
11 Aug 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1A
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
593
11 Aug 2026
Anton Diki W
Dermaga 5
CIGADING 2
Lampu penerangan dermaga 05 mati 1pcs , request ganti
RELEASE
BY EXECUTOR
Medium
130000016165
Dokumentasi
Completed
594
10 Aug 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Cleaning area Slipring, kondisi saat ini terpantau bersih.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
595
10 Aug 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Cleaning paddleswitch CC3 CSU
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
596
10 Aug 2026
Anton Diki W
CCSU
CIGADING 1
Cleaning ruang panel elektrik CSU
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
597
10 Aug 2026
Anton Diki W
CCSU
CIGADING 1
Cleaning dan Penggantian filter fan ruang trafo CSU (before) , proses dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
598
08 Aug 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 27.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
599
08 Aug 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 32.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
600
08 Aug 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 33.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
601
08 Aug 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 29.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
602
08 Aug 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 34.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
603
08 Aug 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 29.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
604
08 Aug 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 29.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
605
08 Aug 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 34.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
606
08 Aug 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-02 : 28.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
607
08 Aug 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-02 : 40.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
608
08 Aug 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-01 : 29.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
609
08 Aug 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-01 : 48.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
610
08 Aug 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Konekan di medium voltage ada indikasi korosi, rekues servis
RUSAK RINGAN
REQUEST SERVICE
Medium
130000018682
Dokumentasi
In Process
611
08 Aug 2026
Anton Diki W
DLLC-01
CIGADING 1
Hasil Megger Motor gantry DLLC 01 no 04 sebelah darat

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
612
08 Aug 2026
Anton Diki W
DLLC - 01
CIGADING 1
Hasil Megger Motor gantry DLLC 01 no 03 sebelah laut

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
613
08 Aug 2026
Anton Diki W
DLLC - 01
CIGADING 1
Hasil Megger Motor gantry DLLC 01 no 01 sebelah darat

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
614
08 Aug 2026
Anton Diki W
DLLC - 01
CIGADING 1
Hasil Megger Motor gantry DLLC 01 no 02 sebelah darat

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
615
06 Aug 2026
Anton Diki W
GSU-06
CIGADING 2
Hasil Megger Motor gantry GSU 06 no 2 sebelah laut

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
616
06 Aug 2026
Anton Diki W
GSU-06
CIGADING 2
Hasil Megger Motor gantry GSU 06 no 01 sebelah laut

U1 - G : 265 Mohm
V1 - G : 273 Mohm
W1 - G : 155 Mohm
U2 - G : 343 Mohm
V2 - G : 285 Mohm
W2 - G : 330 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
617
05 Aug 2026
Hasyim Alhabsyi
TFH & Feeding
CIGADING 2
Hasil Megger Motor Drive TFH :

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
618
04 Aug 2026
Anton Diki W
TFH & Feeding
CIGADING 2
Cleaning motor powerpack TFH before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
619
04 Aug 2026
Anton Diki W
TFH & Feeding
CIGADING 2
Cleaning motor drive TFH before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
620
03 Aug 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 32.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
621
03 Aug 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 31.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
622
03 Aug 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 31.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
623
03 Aug 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 36.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
624
03 Aug 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 28.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
625
03 Aug 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 33.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
626
03 Aug 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 34.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
627
03 Aug 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 29.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
628
03 Aug 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-04 : 40.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
629
03 Aug 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-03 : 31.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
630
03 Aug 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-04 : 40.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
631
03 Aug 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-03 : 49.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
632
03 Aug 2026
Anton Diki W
DLLC-03
CIGADING 1
Motor vibro Hopper DLLC 03 kondisi saat ini terpantau Oke
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
633
03 Aug 2026
Anton Diki W
DLLC-03
CIGADING 1
Cleaning motor powerpack gate Hooper DLLC 03 before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
634
01 Aug 2026
Anton Diki W
GSU-04
CIGADING 1
Program megger motor drive BOOM GSU-04 :

GROUND-GROUND pengukuran 0 Mohm,

GROUND-POSITIF, GROUND-NEGATIF hasil pengukuran 550Mohm

POSITIF - NEGATIF hasil pengukuran 0 Mohm

Exsitasi
Ground F1
Ground F2
Hasil pengukuran 550Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
635
01 Aug 2026
Anton Diki W
GSU-04
CIGADING 1
Hasil Megger Motor cabel reel medium voltage GSU 04 :

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
636
01 Aug 2026
Anton Diki W
GSU-04
CIGADING 1
Cleaning dan Penggantian filter motor fan holding closing trolley GSU-04 before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
637
30 Jul 2026
Anton Diki W
Conveyor A102
CIGADING 2
Panel lampu penerangan dermaga 06 no13 engsel rusak / patah request repair , sementara di tirap
RUSAK RINGAN
REQUEST REPAIR
Medium
Dokumentasi Dokumentasi
Outstanding
638
30 Jul 2026
Anton Diki W
Conveyor A102
CIGADING 2
MCB 6 ampere lampu penerangan dermaga 06 panel no15 short, request ganti MCB
RELEASE
BY EXECUTOR
Medium
Dokumentasi
Completed
639
30 Jul 2026
Hasyim Alhabsyi
Dermaga 6
CIGADING 2
Lampu penerangan 120W di tiang No.10, mati. Request Ganti
RELEASE
BY EXECUTOR
Medium
130000018596
Dokumentasi Dokumentasi
Completed
640
29 Jul 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 30.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
641
29 Jul 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 31.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
642
29 Jul 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 34.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
643
29 Jul 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 34.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
644
29 Jul 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 28.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
645
29 Jul 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 28.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
646
29 Jul 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 29.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
647
29 Jul 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 30.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
648
29 Jul 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-02 : 31.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
649
29 Jul 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-02 : 46.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
650
29 Jul 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-01 : 30.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
651
29 Jul 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-01 : 45.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
652
29 Jul 2026
Anton Diki W
DLLC-01
CIGADING 1
Kondisi Slipring DLLC 01 untuk saat ini masih terpantau amann
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
653
29 Jul 2026
Anton Diki W
DLLC-01
CIGADING 1
Cleaning motor powerpack gate Hooper DLLC 01 before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
654
29 Jul 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Cleaning cabin desk operator DLLC-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
655
28 Jul 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Inspeksi dan Pengukuran suhu Vibrating (Motor 2)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
656
28 Jul 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Inspeksi dan Pengukuran suhu Vibrating (Motor 1)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
657
28 Jul 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Cleaning dan lubrikasi underspeed GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
658
28 Jul 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Cleaning underspeed GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
659
28 Jul 2026
Anton Diki W
GSU-06
CIGADING 2
Pengencangan baud panel LSA CPA Gantry GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
660
28 Jul 2026
Anton Diki W
GSU-06
CIGADING 2
Lubrikasi roll pendulum medium voltage GSU 06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
661
28 Jul 2026
Anton Diki W
GSU-06
CIGADING 2
Lubrikasi roll festune cabin operator GSU 06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
662
28 Jul 2026
Anton Diki W
GSU-06
CIGADING 2
Chamswitch closing terpantau OK GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
663
28 Jul 2026
Anton Diki W
GSU-06
CIGADING 2
Chamswitch holding terpantau OK GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
664
28 Jul 2026
Anton Diki W
GSU-05
CIGADING 2
Kabel glend motor vibrating GSU 05 luka/sobek , langsung action , sementara di rubber lalu di vinyl
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
665
28 Jul 2026
Anton Diki W
GSU-05
CIGADING 2
Pengencangan baud panel LSA CPA Gantry GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
666
28 Jul 2026
Anton Diki W
GSU-05
CIGADING 2
Lubrikasi roll pendulum medium voltage GSU 05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
667
28 Jul 2026
Anton Diki W
GSU-05
CIGADING 2
Lubrikasi roll festune cabin operator GSU 05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
668
28 Jul 2026
Anton Diki W
GSU-05
CIGADING 2
Chamswitch closing terpantau OK GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
669
28 Jul 2026
Anton Diki W
GSU-05
CIGADING 2
Chamswitch holding terpantau OK GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
670
27 Jul 2026
Anton Diki W
PHC-01
CIGADING 1
Pengukuran suhu motor PHC-01 :

HOLDING
drive 40
Bearing 36
Fan 52
Brake 1 & 2 41 41

CLOSING
Drive 44
Bearing 38
Fan 48
Brake 1 & 2 47 45

SLEWING 1
Drive 40
Bearing 35
Fan 38
Brake 45

SLEWING 2
Drive 38
Bearing 33
Fan 40
Brake 42

LUFFING
Drive 38
Bearing 35
Fan 40
Brake 36
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
671
27 Jul 2026
Anton Diki W
PHC-01
CIGADING 1
Karet couple holding di PHC 01 tidak terpasang , request repair dan pasang karet couple
RUSAK RINGAN
REQUEST REPAIR
Medium
Dokumentasi
Outstanding
672
27 Jul 2026
Anton Diki W
PHC-01
CIGADING 1
Slipring PHC 01 kotor request cleaning
RELEASE
BY EXECUTOR
Medium
Dokumentasi
Completed
673
27 Jul 2026
Anton Diki W
PHC-01
CIGADING 1
Ruang trafo PHC-01 kotor, rekues cleaning
RELEASE
BY EXECUTOR
Medium
Dokumentasi Dokumentasi
Completed
674
25 Jul 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Holding GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
675
25 Jul 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Boom trolley Inverter GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
676
25 Jul 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Gantry Inverter GSU-01 : 30.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
677
25 Jul 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Trafo GSU-01 : 42.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
678
25 Jul 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu ruang panel elektrik GSU-04 : 32.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
679
25 Jul 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu panel Closing GSU-04 : 28.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
680
25 Jul 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu panel Holding inverter GSU-04 : 30.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
681
25 Jul 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu panel Gantry GSU-04 : 26.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
682
25 Jul 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel PLC Control GSU-01 : 34.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
683
25 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Hasil magger motor latch boom GSU 01 hasil nilai 2,29Mohm ( no oke ) , request service
RELEASE
REQUEST SERVICE
Medium
130000018602
Dokumentasi Dokumentasi
Completed
684
25 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Cleaning dan Penggantian filter motor fan holding closing trolley GSU-01 before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
685
24 Jul 2026
Hasyim Alhabsyi
Feeding SGT
CIGADING 1
Cleaning fan blower dan Inspeksi panel elektrik di Feeding SGT
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
686
24 Jul 2026
Anton Diki W
Feeding SGT
CIGADING 1
Cleaning motor bucket elevator SGT before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
687
23 Jul 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1A
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
688
23 Jul 2026
Anton Diki W
Conveyor A101
CIGADING 2
Kondisi panel vsd kotor rekues cleaning, di P1A
KOTOR
REQUEST BERSIHKAN
Medium
130000018603
Dokumentasi
In Process
689
23 Jul 2026
Anton Diki W
Conveyor A101
CIGADING 2
Pengukuran suhu motor drive A101 :
Drive 41
Bearing 47
Fan 36
Brake 41
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
690
23 Jul 2026
Hasyim Alhabsyi
Dermaga 6
CIGADING 2
Lampu penerangan 120W di tiang No.10 (dihitung dari arah Anyer), nyala sebagian (rusak). Request Ganti
RELEASE
BY EXECUTOR
Medium
130000018596
Dokumentasi Dokumentasi
Completed
691
22 Jul 2026
Hasyim Alhabsyi
Conveyor BCNO
CIGADING 1
Cleaning motor drive, motor brake, motor fan dan cleaning panel di conveyor BCNO
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
692
22 Jul 2026
Hasyim Alhabsyi
Conveyor C02
CIGADING 1
Cleaning motor drive, motor brake, motor fan dan cleaning panel di conveyor C02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
693
20 Jul 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Pengukuran suhu motor Fan CCSU : 33.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
694
20 Jul 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Pengukuran suhu motor Feeding Pump : 35.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
695
20 Jul 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Inspeksi dan Pengukuran suhu Motor Main Pump : 52.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
696
20 Jul 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Inspeksi dan Pengukuran suhu Panel 2 CCSU : 27.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
697
20 Jul 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Inspeksi dan Pengukuran suhu Panel 1 CCSU : 28.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
698
20 Jul 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Cleaning area Slipring CCSU, kondisi OK.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
699
20 Jul 2026
Anton Diki W
CCSU
CIGADING 1
Cleaning ruang panel elektrik CSU
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
700
20 Jul 2026
Anton Diki W
CCSU
CIGADING 1
Cleaning dan Penggantian filter fan ruang trafo CSU (before) dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
701
18 Jul 2026
Anton Diki W
DLLC-03
CIGADING 1
Hasil Megger Motor drive holding DLLC 03 hasil oke.

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
702
18 Jul 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Hasil Megger Motor brake slewing sisi laut

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
703
18 Jul 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Hasil Megger Motor closing :

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
704
17 Jul 2026
Anton Diki W
Conveyor PBCN 1
CIGADING 1
Pengukuran suhu motor :
PBCN-01 :
Drive 50
Bearing 43
Brake 48

PBCN-02 :
Drive 47
Bearing 51
Brake 53
Fan 43
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
705
17 Jul 2026
Anton Diki W
Conveyor PBCN 1
CIGADING 1
Pullcord sling safety conveyor PBCN 01 putus di tiang nomor 80 , request repair
RELEASE
REQUEST REPAIR
Medium
130000018569
Dokumentasi Dokumentasi
Completed
706
17 Jul 2026
Hasyim Alhabsyi
Conveyor PBCN 2
CIGADING 1
Cleaning motor drive PBCN-02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
707
17 Jul 2026
Hasyim Alhabsyi
Conveyor PBCN 1
CIGADING 1
Cleaning motor drive PBCN01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
708
16 Jul 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1B Motor 3
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
709
16 Jul 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1B Motor 2
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
710
16 Jul 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1B Motor 1
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
711
16 Jul 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu ruang Trafo P1B
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
712
16 Jul 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu ruang panel elektrik P1B
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
713
16 Jul 2026
Anton Diki W
Conveyor A102
CIGADING 2
Lampu led ruang panel P1B lepas dari dudukan lampu "request perbaikan"
LAIK PAKAI
REQUEST REPAIR
-
Dokumentasi
Outstanding
714
16 Jul 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Kondisi trafo P1B terlihat kotor, rekues cleaning
LAIK PAKAI
REQUEST BERSIHKAN
-
Dokumentasi Dokumentasi
Outstanding
715
15 Jul 2026
Anton Diki W
DLLC-02
CIGADING 1
Cleaning motor brake luffing DLLC 02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
716
15 Jul 2026
Anton Diki W
DLLC-02
CIGADING 1
Hasil Megger Motor fan luffing DLLC 02

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
717
15 Jul 2026
Anton Diki W
DLLC-02
CIGADING 1
Hasil Megger Motor luffing DLLC 02

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
718
15 Jul 2026
Anton Diki W
DLLC-02
CIGADING 1
Hasil Megger Motor brake holding sebelah anyer DLLC 02

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
719
15 Jul 2026
Anton Diki W
DLLC-02
CIGADING 1
Hasil Megger Motor brake holding sebelah merak DLLC 02

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
720
15 Jul 2026
Anton Diki W
DLLC-02
CIGADING 1
Hasil Megger Motor brake closing sebelah anyer DLLC 02

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
721
15 Jul 2026
Anton Diki W
DLLC-02
CIGADING 1
Hasil Megger Motor brake closing sebelah merak DLLC 02

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
722
15 Jul 2026
Anton Diki W
DLLC-02
CIGADING 1
Hasil Megger Motor holding DLLC 02

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
723
15 Jul 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Hasil Megger Motor closing DLLC-02

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
724
15 Jul 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Hasil Megger Motor slewing DLLC sebelah darat

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
725
15 Jul 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Hasil Megger motor slewing DLLC-02 Csebelah laut

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
726
15 Jul 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Grounding di dekat pintu motor room sebelah laut putus. Rekues ganti
RUSAK RINGAN
REQUEST GANTI
Medium
Dokumentasi
Outstanding
727
13 Jul 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Cleaning sensor shink in/out HLSKT CCSU
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
728
13 Jul 2026
Anton Diki W
CCSU
CIGADING 1
Hasil Megger Motor gantry CSU no 24 sebelah laut

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
729
13 Jul 2026
Anton Diki W
CCSU
CIGADING 1

Hasil Megger Motor gantry CSU no 21 sebelah laut

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
730
11 Jul 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing PHC-01 : 41.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
731
11 Jul 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Slewing PHC-01 : 32.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
732
11 Jul 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Closing PHC-01 : 32.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
733
11 Jul 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Holding PHC-01 : 32.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
734
11 Jul 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Power Panel PHC-01 : 29.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
735
11 Jul 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Inspeksi dan Pengukuran suhu panel gantry PHC-02 : 37.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
736
11 Jul 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Inspeksi dan Pengukuran suhu trafo PHC-02 : 42.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
737
11 Jul 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu trafo PHC-01 : 43.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
738
11 Jul 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Hasil Megger Motor Slewing 01 Sebelah Darat di PHC 02 :

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm

V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm

W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
739
11 Jul 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Hasil Megger Motor Holding PHC 02 :

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm

V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm

W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
740
11 Jul 2026
Anton Diki W
PHC-02
CIGADING 1
Hasil Megger Motor slewing 02 sebelah laut PHC 02 :

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
741
11 Jul 2026
Anton Diki W
PHC-02
CIGADING 1
Hasil Megger Motor closing PHC 02 :

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
742
09 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Hasil Megger Motor gantry GSU 01 sebelah darat no.08:

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
743
09 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Hasil Megger Motor gantry GSU 01 sebelah darat no.07:

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
744
09 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Hasil Megger Motor gantry GSU 01 sebelah darat no.06:

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
745
09 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Hasil Megger Motor gantry GSU 01 sebelah darat no.05:

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
746
09 Jul 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
kabel RST motor vibrating GSU-06 sebelah anyer sisi laut tidak ada skun nya, rekues pasang skun
RELEASE
BY EXECUTOR
Medium
130000018503
Dokumentasi
Completed
747
09 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Hasil Megger Motor gantry GSU 01 sebelah darat no.04:

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
748
09 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Hasil Megger Motor gantry GSU 01 sebelah darat no.03:

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
749
09 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Hasil Megger Motor gantry GSU 01 sebelah darat no.02:

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
750
09 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Hasil Megger Motor gantry GSU 01 sebelah darat no.01:

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
751
09 Jul 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Hasil Megger Motor Vibro arah laut GSU 06 :

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
752
09 Jul 2026
Anton Diki W
GSU-06
CIGADING 2
Hasil Megger Motor vibrating GSU 06 sebelah Anyer :

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
753
09 Jul 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Hasil Megger Motor vibro sebelah merak GSU 06 :

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
754
08 Jul 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Lubrikasi roll festun cabin operator GSU-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
755
08 Jul 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Cleaning motor power pack
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
756
08 Jul 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Motor trastle brake tidak terpasang 2 pcs di sisi merak darat dan merak laut. Req. Pasangkan
RUSAK RINGAN
REQUEST REPAIR
Medium
130000017501
Dokumentasi Dokumentasi
In Process
757
08 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Pengecekkan lidah kontaktor holding closing trolley GSU-01 (kondisi kontaktor ok)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
758
08 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Cleaning motor drive holding closing dan trolley GSU 01
Note: filter GSU 01 terpantau masih Oke
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
759
08 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
Cleaning motor gate power pack GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
760
08 Jul 2026
Anton Diki W
GSU-01
CIGADING 1
motor eldro brake gantry GSU 01 tidak terpasang 3pcs , sebelah laut Anyer 1pcs dan 2pcs sebelah daratt , request pasang
RUSAK RINGAN
REQUEST PENAMBAHAN
Medium
Dokumentasi Dokumentasi
Outstanding
761
07 Jul 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Inspeksi dan Pengukuran suhu Trafo P1C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
762
07 Jul 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Kondisi Ruang trafo P1C kotor banyak sawangnya. Rekues cleaning
RELEASE
BY EXECUTOR
Medium
130000018486
Dokumentasi Dokumentasi
Completed
763
07 Jul 2026
Anton Diki W
Conveyor A103
CIGADING 2
Pengukuran suhu motor drive A103
Motor 1
Drive 42
Fan 38
Bearing 38
Brake 40

Motor 2
Drive 40
Bearing 37
Fan 36
Brake 38
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
764
07 Jul 2026
Anton Diki W
Conveyor A103
CIGADING 2
Filter vsd ruang panel P1C kondisi kotor, rekues ganti
RELEASE
BY EXECUTOR
Medium
Dokumentasi
Completed
765
07 Jul 2026
Anton Diki W
Conveyor A103
CIGADING 2
Filter vsd ruang panel P1B kondisi OKE.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
766
02 Jul 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Hasil Megger Motor Trolley GSU 05 :

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
767
02 Jul 2026
Anton Diki W
GSU-05
CIGADING 2
Motor vibrating sebelah Anyer GSU 05 , tidak ada skun nyaa , request penambahan skun
RUSAK RINGAN
REQUEST PENAMBAHAN
Medium
130000018502
Dokumentasi
In Process
768
02 Jul 2026
Anton Diki W
GSU-05
CIGADING 2
Hasil Megger Motor closing GSU 05 :

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
769
02 Jul 2026
Anton Diki W
GSU-05
CIGADING 2
Hasil Megger Motor holding GSU 05 :

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
770
02 Jul 2026
Anton Diki W
GSU-05
CIGADING 2
Hasil Megger Motor Boom GSU 05 :

U1 - G : 180 Mohm
V1 - G : 174 Mohm
W1 - G : 140 Mohm
U2 - G : 150 Mohm
V2 - G : 160 Mohm
W2 - G : 170 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 242 Mohm
U1 - W2 : 240 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 230 Mohm
V1 - W2 : 244 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 236 Mohm
W1 - V2 : 245 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
771
01 Jul 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 31.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
772
01 Jul 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 31.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
773
01 Jul 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 35.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
774
01 Jul 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 29.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
775
01 Jul 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 28.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
776
01 Jul 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 34.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
777
01 Jul 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 29.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
778
01 Jul 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 30.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
779
01 Jul 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-04 : 42.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
780
01 Jul 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-03 : 30.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
781
01 Jul 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-04 : 44.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
782
01 Jul 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-03 : 38.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
783
01 Jul 2026
Anton Diki W
DLLC-03
CIGADING 1
Baut chamswitch holding DLLC 03 terpantau lengkap
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
784
01 Jul 2026
Anton Diki W
DLLC-03
CIGADING 1
Cleaning dan lubrikasi motor creeper gantry DLLC 03
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
785
01 Jul 2026
Anton Diki W
DLLC-03
CIGADING 1
Cleaning panel gate Hooper DLLC 03
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
786
01 Jul 2026
Anton Diki W
DLLC-03
CIGADING 1
Cleaning motor powerpack gate Hooper DLLC 03 , before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
787
01 Jul 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Motor vibro gate hooper sisi Laut di DLLC-04 mengalami kerusakan (suara kasar). Indikasi dari kerusakan bearing.
RELEASE
BY EXECUTOR
Medium
Dokumentasi Dokumentasi
Completed
788
30 Jun 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1B Motor 3
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
789
30 Jun 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1B Motor 2
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
790
30 Jun 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1B Motor 1
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
791
30 Jun 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu ruang Trafo P1B
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
792
30 Jun 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu ruang panel elektrik P1B
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
793
30 Jun 2026
Anton Diki W
Conveyor A102
CIGADING 2
Cleaning dan lubrikasi safety device area conveyor A102
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
794
29 Jun 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Cleaning panel desk control operator kiri dan kanan di PHC-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
795
29 Jun 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Grouding area gantry tidak terpasang 2 pcs PHC-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
796
29 Jun 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Kondisi slipring PHC-01 terpantau ok
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
797
29 Jun 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Cleaning motor pack gate hopper PHC-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
798
27 Jun 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Motor Gantry Nomor 2 (Sisi Laut arah Anyer)

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm

Hasil Megger motor dinyatakan bagus (OK)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
799
27 Jun 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Motor Gantry Nomor 4 (Sisi Laut arah Merak)

U1 - G : 0,11 Mohm
V1 - G : 0,22 Mohm
W1 - G : 0,11 Mohm
U2 - G : 0,22 Mohm
V2 - G : 0,18 Mohm
W2 - G : 0,11 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 0,09 Mohm
U1 - W2 : 0,07 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 0,16 Mohm
V1 - W2 : 0,17 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 0,17 Mohm
W1 - V2 : 0,16 Mohm

Hasil Megger motor rendah dan terdapat genangan air dalam covernya
RELEASE
REQUEST SERVICE
Medium
130000018389
Dokumentasi Dokumentasi
Completed
800
27 Jun 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Motor Gantry Nomor 3 (Sisi Laut arah Merak)

U1 - G : 280 Mohm
V1 - G : 311 Mohm
W1 - G : 320 Mohm
U2 - G : 119 Mohm
V2 - G : 116 Mohm
W2 - G : 114 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 0,14 Mohm
U1 - W2 : 0,16 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 0,14 Mohm
V1 - W2 : 0,16 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 0,14 Mohm
W1 - V2 : 0,16 Mohm

Hasil Megger motor rendah dan terdapat genangan air dalam covernya
RELEASE
REQUEST SERVICE
Medium
130000018388
Dokumentasi Dokumentasi
Completed
801
27 Jun 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Pengecekan & Cleaning seluruh Motor Gantry sisi darat di GSU-01 (Hasil Megger OK = 550 MOhm)
Untuk motor gantry sebelah darat yang mengalami korosi sudah di bersihkan dan di amplas.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
802
26 Jun 2026
Anton Diki W
Feeding SGT
CIGADING 1
Magnetic contactor K11 indikasi terdapat percikan api Saat motor bucket elevator SGT di running , posisi ada di panel SGT , request service
RELEASE
REQUEST SERVICE
Medium
130000018387
Dokumentasi Dokumentasi
Completed
803
26 Jun 2026
Anton Diki W
Feeding SGT
CIGADING 1
Tes running bucket elevator SGT after magger
Note : horn bucket elevator SGT tidak terpasang
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
804
26 Jun 2026
Anton Diki W
Feeding SGT
CIGADING 1
Motor bucket elevator SGT hasil megger ok 550 Mohm. Ground-ground, Ground-phase, Phase-phase
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
805
26 Jun 2026
Anton Diki W
Feeding SGT
CIGADING 1
Kondisi sebelum dan sesudah di magger motor bucket elevator SGT
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
806
26 Jun 2026
Anton Diki W
Feeding SGT
CIGADING 1
Cleaning motor bucket elevator SGT (dokumentasi before dan after)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
807
25 Jun 2026
Hasyim Alhabsyi
Dermaga 5
CIGADING 2
Lampu dermaga 5 mati 1 pcs di tiang nomor 3 & 4
RELEASE
BY EXECUTOR
Medium
130000016165
Dokumentasi Dokumentasi
Completed
808
24 Jun 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Kondisi slipring saat ini cukup bersih dan ok
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
809
24 Jun 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Jalur kabel sudah di tutup foam sealant oleh elektrik, kondisi jalur saat ini sudah ok
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
810
23 Jun 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1A
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
811
23 Jun 2026
Anton Diki W
GSU-06
CIGADING 2
Hasil Megger Motor Trolley

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
812
23 Jun 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Hasil Megger Motor Boom

U1 - G : 109 Mohm
V1 - G : 107 Mohm
W1 - G : 106 Mohm
U2 - G : 108 Mohm
V2 - G : 112 Mohm
W2 - G : 110 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 114 Mohm
U1 - W2 : 125 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 125 Mohm
V1 - W2 : 112 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 112 Mohm
W1 - V2 : 114 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi Dokumentasi
Ready to Use
813
22 Jun 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 28.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
814
22 Jun 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 29.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
815
22 Jun 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 30.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
816
22 Jun 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 33.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
817
22 Jun 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 28.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
818
22 Jun 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 33.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
819
22 Jun 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 29.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
820
22 Jun 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 31.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
821
22 Jun 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-02 : 38.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
822
22 Jun 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-02 : 43.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
823
22 Jun 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-01 : 29.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
824
22 Jun 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-01 : 49.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
825
22 Jun 2026
Anton Diki W
DLLC-01
CIGADING 1
kondisi slipring kabel drum 6kV untuk saat ini masih terpantau amann DLLC 01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
826
22 Jun 2026
Anton Diki W
DLLC-01
CIGADING 1
Kondisi Slipring DLLC 01 untuk saat ini masih terpantau amann
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
827
22 Jun 2026
Anton Diki W
DLLC-01
CIGADING 1
Cleaning Motor kabel drum medium voltage DLLC 01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
828
22 Jun 2026
Anton Diki W
DLLC-01
CIGADING 1
Kontak NC PB stop rusak ( panel motor powerpack gate Hopper ) DLLC 01, request ganti
RELEASE
REQUEST GANTI
Medium
130000018346
Dokumentasi
Completed
829
22 Jun 2026
Anton Diki W
DLLC-01
CIGADING 1
Motor vibro Hopper DLLC 01 sebelah laut terdapat kelainan bunyi , indikasi untuk saat ini darii bearing , request service
RELEASE
REQUEST SERVICE
Medium
130000018345
Dokumentasi
Completed
830
22 Jun 2026
Anton Diki W
DLLC-01
CIGADING 1
Motor vibro Hopper DLLC 01 sebelah merakk bagian daratt terdapat kelainan bunyi , indikasi untuk saat ini darii bearing , request service
RELEASE
REQUEST SERVICE
Medium
130000018373
Dokumentasi
Completed
831
22 Jun 2026
Anton Diki W
DLLC-01
CIGADING 1
Cleaning motor creeper gantry DLLC 01 , before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
832
22 Jun 2026
Anton Diki W
DLLC-01
CIGADING 1
Cleaning motor powerpack gate Hooper DLLC 01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
833
22 Jun 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Cleaning motorpack gate hopper DLLC-02
LAIK PAKAI
REQUEST REPAIR
TIDAK
Dokumentasi
Ready to Use
834
20 Jun 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Hasil Megger Motor Closing

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
835
20 Jun 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Hasil Megger Motor Holding

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
836
19 Jun 2026
Anton Diki W
Feeding SGT
CIGADING 1
Cleaning dan lubrikasi safety device area bucket elevator SGT
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
837
19 Jun 2026
Anton Diki W
Feeding SGT
CIGADING 1
Tes running bucket elevator SGT, kondisi ok
Note : horn bucket elevator SGT tidak terpasang
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
838
19 Jun 2026
Anton Diki W
Feeding SGT
CIGADING 1
Cleaning motor bucket elevator SGT before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
839
18 Jun 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Hasil magger brake Slewing 02 tahanan isolasi 550 Mohm, Ground-ground. Ground-phase. Phase-phase
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
840
18 Jun 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Hasil Megger Motor Slewing 02

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
841
18 Jun 2026
Anton Diki W
PHC-01
CIGADING 1
Hasil magger brake Slewing 01 tahanan isolasi 550 Mohm, Ground-ground. Ground-phase. Phase-phase
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
842
18 Jun 2026
Anton Diki W
PHC-01
CIGADING 1
Hasil Megger Motor Slewing 01

U1 - G : 550 Mohm
V1 - G : 550 Mohm
W1 - G : 550 Mohm
U2 - G : 550 Mohm
V2 - G : 550 Mohm
W2 - G : 550 Mohm

Antar Phase
U1 - U2 : 0 Mohm
U1 - V2 : 550 Mohm
U1 - W2 : 550 Mohm
V1 - V2 : 0 Mohm
V1 - U2 : 550 Mohm
V1 - W2 : 550 Mohm
W1 - W2 : 0 Mohm
W1 - U2 : 550 Mohm
W1 - V2 : 550 Mohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
843
17 Jun 2026
Anton Diki W
PHC-01
CIGADING 1
Motor fan holding hasil megger ok 550 Mohm, Ground-ground. Ground-phase. Phase-phase ok
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
844
17 Jun 2026
Anton Diki W
PHC-01
CIGADING 1
Motor fan luffing hasil megger ok 550 Mohm, Ground-ground. Ground-phase. Phase-phase ok
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
845
17 Jun 2026
Anton Diki W
PHC-01
CIGADING 1
Motor brake luffing hasil megger ok 550 Mohm, Ground-ground. Ground-phase. Phase-phase ok
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
846
17 Jun 2026
Anton Diki W
PHC-01
CIGADING 1
Motor drive luffing hasil megger ok 550 Mohm, Ground-ground. Ground-phase. Phase-phase ok
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
847
17 Jun 2026
Anton Diki W
PHC-01
CIGADING 1
Motor drive closing hasil megger ok 550 Mohm, Ground-ground. Ground-phase. Phase-phase ok
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
848
17 Jun 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Program megger motor drive TROLLEY GSU-04 :

Antar Phase
GROUND - GROUND = 0 MOhm,
GROUND - POSITIF = 550 MOhm
GROUND - NEGATIF = 550 MOhm
POSITIF - NEGATIF = 0 MOhm

Exsitasi
Ground - F1 : 550 MOhm
Ground - F2 : 550 MOhm

Kode Motor : M6
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
849
15 Jun 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Pengencangan baut di ruang panel room CCSU, dan cleaning ruang trafo.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
850
15 Jun 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Cleaning dan Penggantian filter fan ruang trafo CSU. dokumentasi before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
851
13 Jun 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Holding GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
852
13 Jun 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Boom trolley Inverter GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
853
13 Jun 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Gantry Inverter GSU-01 : 34.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
854
13 Jun 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Trafo GSU-01 : 36.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
855
13 Jun 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu ruang panel elektrik GSU-04 : 27.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
856
13 Jun 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu panel Closing GSU-04 : 38.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
857
13 Jun 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu panel Holding inverter GSU-04 : 31.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
858
13 Jun 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu panel Gantry GSU-04 : 26.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
859
13 Jun 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel PLC Control GSU-01 : 30.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
860
13 Jun 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Pengecekan lidah kontaktor motor brake di GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
861
13 Jun 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Cleaning dan Penggantian filter motor fan holding closing trolley GSU-01 (dokumentasi before dan after)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
862
13 Jun 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Cleaning dan Penggantian filter motor fan holding closing trolley GSU-04 (dokumentasi before dan after)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
863
13 Jun 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Program megger motor drive HOLDING GSU-04 :

Antar Phase
GROUND - GROUND = 0 MOhm,
GROUND - POSITIF = 46 MOhm
GROUND - NEGATIF = 47 MOhm
POSITIF - NEGATIF = 0 MOhm

Exsitasi
Ground - F1 : 550 MOhm
Ground - F2 : 550 MOhm

Pantau berkala
Kode Motor : M4
LAIK PAKAI
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi Dokumentasi
Ready to Use
864
13 Jun 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Program megger motor drive CLOSING GSU-04 :

Antar Phase
GROUND - GROUND = 0 MOhm,
GROUND - POSITIF = 24 MOhm
GROUND - NEGATIF = 24 Mohm
POSITIF - NEGATIF = 0 MOhm

Exsitasi
Ground - F1 : 550 MOhm
Ground - F2 : 550 MOhm

Request Service
Kode Motor : M5
RELEASE
REQUEST SERVICE
Medium
130000018329
Dokumentasi Dokumentasi
Completed
865
13 Jun 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Cleaning motor powerpack belt feeder GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
866
13 Jun 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Cleaning motor drive & fan holding, closing, dan trolley GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
867
12 Jun 2026
Anton Diki W
Tower 2
CIGADING 1
Cleaning motor drive BCNO 01 dan BCNO 02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
868
11 Jun 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Pengukuran suhu motor Fan CCSU : 33.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
869
11 Jun 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Pengukuran suhu motor Feeding Pump : 34.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
870
11 Jun 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Inspeksi dan Pengukuran suhu Motor Main Pump : 52.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
871
11 Jun 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Inspeksi dan Pengukuran suhu Panel 2 CCSU : 26.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
872
11 Jun 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Inspeksi dan Pengukuran suhu Panel 1 CCSU : 26.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
873
11 Jun 2026
Anton Diki W
CCSU
CIGADING 1
test running setelah di magger CSU , ready for use
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
874
11 Jun 2026
Anton Diki W
CCSU
CIGADING 1
After magger cleaning motor fan , motor feeding pump , emergency pump
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
875
11 Jun 2026
Anton Diki W
CCSU
CIGADING 1
Hasil megger motor fan 550 Mohm. Ground-ground, ground-phase, phase-phase
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
876
11 Jun 2026
Anton Diki W
CCSU
CIGADING 1
Hasil megger motor emergency pump 550 Mohm. Ground-ground, ground-phase, phase-phase
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
877
11 Jun 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Kabel ground putus di area CC2 CSU
RELEASE
REQUEST REPAIR
Medium
130000016631
Dokumentasi
Completed
878
10 Jun 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing PHC-01 : 40.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
879
10 Jun 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Slewing PHC-01 : 35.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
880
10 Jun 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Closing PHC-01 : 33.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
881
10 Jun 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Holding PHC-01 : 33.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
882
10 Jun 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Power Panel PHC-01 : 32.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
883
10 Jun 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Inspeksi dan Pengukuran suhu panel gantry PHC-02 : 38.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
884
10 Jun 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Inspeksi dan Pengukuran suhu trafo PHC-02 : 41.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
885
10 Jun 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu trafo PHC-01 : 41.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
886
10 Jun 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Preventive elektrik program Megger / Pengujian tahanan (resistansi) isolasi di DLLC-01 :
1. Megger insulation tes motor drive Holding. Ground-ground, ground-phase, phase-phase hasil 550Mohm
2. ⁠Megger insulation tes motor drive Closing. Ground-ground, ground-phase, phase-phase hasil 550Mohm
3. ⁠Megger insulation tes motor drive slewing 1. Ground-ground, ground-phase, phase-phase hasil 550Mohm
4. ⁠Megger insulation tes motor drive slewing 2. Ground-ground, ground-phase, phase-phase hasil 550Mohm
5. ⁠Megger insulation tes motor brake holding. Ground-ground, ground-phase, phase-phase hasil 550Mohm
6. ⁠Megger insulation tes motor brake closing. Ground-ground, ground-phase, phase-phase hasil 550Mohm
7. ⁠Megger insulation tes motor brake slewing 1&2 Ground-ground, ground-phase, phase-phase hasil 550Mohm
8. ⁠Megger insulation tes motor drive luffing. Ground-ground, ground-phase, phase-phase hasil 550Mohm
9. ⁠Megger insulation tes motor fan holding, closing. Ground-ground, ground-phase, phase-phase hasil 550Mohm
10. Megger insulation tes motor fan luffing. Ground-ground, ground-phase, phase-phase hasil 550Mohm ⁠
11. ⁠Cleaning semua motor yang di Megger
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
887
09 Jun 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Inspeksi dan Pengukuran suhu Trafo P1C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
888
09 Jun 2026
Anton Diki W
TFH & Feeding
CIGADING 2
Dudukan Motor drive TFH korosi request repair
RUSAK RINGAN
REQUEST REPAIR
Medium
130000018325
Dokumentasi Dokumentasi
In Process
889
09 Jun 2026
Anton Diki W
Conveyor A103
CIGADING 2
Pengukuran suhu motor drive A103
Motor 1
Drive 39
Fan 40
Bearing 37
Brake 38

Motor 2
Drive 37
Bearing 36
Fan 38
Brake 37
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
890
09 Jun 2026
Anton Diki W
TFH & Feeding
CIGADING 2
Pengukuran suhu motor drive TFH :
Drive 48
Fan 48
Bearing 38
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
891
08 Jun 2026
Anton Diki W
DLLC-02
CIGADING 1
AC ruang ruang trafo mengeluarkan angin panas DLLC-02, Sudah di eksekusi oleh tim Tampomas.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
892
08 Jun 2026
Anton Diki W
DLLC-02
CIGADING 1
Pengukuran suhu motor DLLC-02:
HOLDING
Fan 46
Drive 43
Bearing 42
Brake 1 & 2 46 & 48

CLOSING
Fan 45
Drive 44
Bearing 39
Brake 1 & 2 47 & 50

SLEWING 1
Fan 46
Drive 38
Bearing 37
Brake 1 41

SLEWING 2
Fan 45
Drive 38
Bearing 36
Brake 1 40

LUFFING
Fan 40
Drive 38
Bearing 36
Brake 1 42
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
893
06 Jun 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Preventive elektrik program magger A101 :
1. ⁠motor fan A101 hasil magger 550 Mohm, ground-ground, ground-phase, phase-phase ok
2. ⁠cleaning motor drive
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
894
06 Jun 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Preventive elektrik program magger A101 :
1. Motor drive A101 hasil magger 550 Mohm, ground-ground, ground-phase, phase-phase ok
2. ⁠cleaning motor drive
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
895
05 Jun 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Hasil magger Motor gantry CSU hasill Oke ( sample Motor no 1 , 10 , 11 , 12 sudah di lakukan )
Catatan : beberapa baut cover patah karena getass ( sementara di silikon dan tyrap )
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
896
05 Jun 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Preventive elektrik program cleaning 4 motor screw HLS-KT
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
897
05 Jun 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Preventive elektrik program magger motor CSU :
Magger motor screw nomor 1.2.3.4 hasil magger 550Mohm, ground-ground ok, ground-phase ok, phase-phase ok
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
898
03 Jun 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 30.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
899
03 Jun 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 31.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
900
03 Jun 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 41.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
901
03 Jun 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 33.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
902
03 Jun 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 27.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
903
03 Jun 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 32.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
904
03 Jun 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 29.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
905
03 Jun 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 30.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
906
03 Jun 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-04 : 32.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
907
03 Jun 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-03 : 33.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
908
03 Jun 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-04 : 45.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
909
03 Jun 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-03 : 43.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
910
03 Jun 2026
Anton Diki W
DLLC-03
CIGADING 1
Cleaning powerpack gate Hooper DLLC 03 before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
911
03 Jun 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi area gate hooper dan test fungsi, berjalan dengan normal.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
912
02 Jun 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1B Motor 3
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
913
02 Jun 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1B Motor 2
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
914
02 Jun 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1B Motor 1
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
915
02 Jun 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu ruang Trafo P1B
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
916
02 Jun 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu ruang panel elektrik P1B
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
917
02 Jun 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Inspeksi dan Pengukuran suhu Vibrating (Motor 2)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
918
02 Jun 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Inspeksi dan Pengukuran suhu Vibrating (Motor 1)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
919
02 Jun 2026
Anton Diki W
Conveyor A102
CIGADING 2
Indikasi terdapat kabel yang short di area jalur penerangan Conveyor A102. Untuk sementara MCB nomor 6 di Panel di Off kan. Req. Perbaiki jalur
RUSAK RINGAN
REQUEST REPAIR
Medium
130000018328
Dokumentasi
In Process
920
02 Jun 2026
Anton Diki W
Conveyor A102
CIGADING 2
Lubrikasi safety device area conveyor A102
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
921
02 Jun 2026
Anton Diki W
Conveyor A102
CIGADING 2
Filter vsd ruang panel P1B kondisi kotor, rekues ganti
RELEASE
BY EXECUTOR
Medium
Dokumentasi
Completed
922
02 Jun 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Pengukuran suhu motor drive A102
Drive 43
Bearing 40
Fan 40
KOTOR
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
923
02 Jun 2026
Hasyim Alhabsyi
Dermaga 6
CIGADING 2
Pengecekan lampu penerangan trestel area dermaga 6 di semua titik. Kondisi OK dan fotocell berfungsi semua.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
924
30 May 2026
Anton Diki W
GSU-01
CIGADING 1
Program megger motor drive HOLDING GSU-01:

Antar Phase
GROUND - GROUND = 0 MOhm,
GROUND - POSITIF = 550 MOhm
GROUND - NEGATIF = 550 MOhm
POSITIF - NEGATIF = 0 MOhm

Exsitasi
Ground - F1 : 550 MOhm
Ground - F2 : 550 MOhm

Kode Motor : M1
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
925
30 May 2026
Anton Diki W
GSU-01
CIGADING 1
Program megger motor drive CLOSING GSU-01 :

Antar Phase
GROUND - GROUND = 0 MOhm,
GROUND - POSITIF = 550 MOhm
GROUND - NEGATIF = 550 MOhm
POSITIF - NEGATIF = 0 MOhm

Exsitasi
Ground - F1 : 550 MOhm
Ground - F2 : 550 MOhm

Kode Motor : M2
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
926
29 May 2026
Hasyim Alhabsyi
Conveyor PBCN 1
CIGADING 1
Program pengujian tahanan isolasi (megger test) motor drive PBCN1, motor brake, dan motor fan. Hasil pengujian nilainya masih OK (550 MOhm)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
927
29 May 2026
Hasyim Alhabsyi
Conveyor PBCN 2
CIGADING 1
Program pengujian tahanan isolasi (megger test) motor drive PBCN2, motor brake, dan motor fan. Hasil pengujian nilainya masih OK (550 MOhm)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
928
26 May 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Melanjutkan program test tahanan isolasi (megger test) untuk 8 pcs AC motor gantry, dan 1 motor kabel drum Medium Voltage. Nilai tahanan : 550 M Ohm semuanya (Kondisi Baik)
Catatan : OK w/ note untuk AC motor nomor 6 (req. ganti Dioda brake SEW Eurodrive tipe BGE 1.5)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
929
25 May 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Program Insulation tester (test Megger) motor drive dan brake Holding, Clossing, Slewing 1&2 di area motor room dan motor drive Luffing. Hasil nilai tahanannya : 550M Ohm
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
930
23 May 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Cleaning dan inspeksi elektrikal area Slipring
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
931
23 May 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Cleaning dan inspeksi sensor Paddleswitch di area CC3
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
932
23 May 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Cleaning area panel room CCSU
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
933
23 May 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Cleaning area Trafo room
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
934
23 May 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Penggantian filter motor fan trafo di area trofo room
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
935
23 May 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Cleaning sensor Sink-in area motor screw HL-SKT
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
936
23 May 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Cleaning 4 motor screw HL-SKT CCSU
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
937
21 May 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Inspeksi dan Pengukuran suhu Vibrating (Motor 2)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
938
21 May 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Inspeksi dan Pengukuran suhu Vibrating (Motor 1)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
939
21 May 2026
Anton Diki W
GSU-06
CIGADING 2
Chamswitch holding dan closing terpantau OK GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
940
21 May 2026
Anton Diki W
GSU-05
CIGADING 2
Chamswitch holding dan closing terpantau OK GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
941
21 May 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Pengencangan baud panel LSA/CPA Gantry GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
942
21 May 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Cleaning zerospeed GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
943
20 May 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Inspeksi dan Pengukuran suhu Panel 2 CCSU : 28.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
944
20 May 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Inspeksi dan Pengukuran suhu Panel 1 CCSU : 28.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
945
20 May 2026
Anton Diki W
CCSU
CIGADING 1
suhu motor fan CC3 kiri
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
946
20 May 2026
Anton Diki W
CCSU
CIGADING 1
suhu Motor fan CC3 kanan ( oke )
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
947
20 May 2026
Anton Diki W
CCSU
CIGADING 1
suhu Motor drive CC3 CSU ( oke )
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
948
20 May 2026
Anton Diki W
CCSU
CIGADING 1
suhu Motor emergency pump CSU
( OKE )
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
949
20 May 2026
Anton Diki W
CCSU
CIGADING 1
suhu Motor feeding pump CSU ( OKE )
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
950
20 May 2026
Anton Diki W
CCSU
CIGADING 1
suhu Motor fan CSU ( OKE ) : 40.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
951
20 May 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Pengecekan area slipring dari bagian mainhole atas. Kondisi saat ini sudah cukup bersih dan tidak ditemukan tumpahan material saat kondisi running.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
952
20 May 2026
Anton Diki W
CCSU
CIGADING 1
Suhu motor main pump hidrolik CSU
( OKE )
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
953
20 May 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Inspeksi panel-panel di area panel room CCSU, tidak ditemukan indikasi. OK
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
954
20 May 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Pengecekan Kompresor CCSU, kondisi OK. Hanya area sekitar, masih perlu di cleaning.
LAIK PAKAI
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi
Ready to Use
955
20 May 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Running inspection motor cable drum CCSU. Kondisi OK
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
956
20 May 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Inspeksi equipment Motor gate trucking area CC3 di CCSU, kondisi OK (berikut nameplate motornya)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
957
19 May 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1A
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
958
19 May 2026
Anton Diki W
Conveyor A101
CIGADING 2
Filter panel vsd P1A kotor, rekues ganti
RUSAK RINGAN
REQUEST GANTI
Medium
130000018136
Dokumentasi
In Process
959
19 May 2026
Anton Diki W
Conveyor A101
CIGADING 2
Pengukuran suhu motor drive A101 :
Drive 39
Bearing 41
Fan 38
Brake 41
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
960
19 May 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Kabel medium voltage 6kV bekas raychem sudah terkelupas, rekuest raychem ulang. Ada 6 titik
RELEASE
BY EXECUTOR
Medium
130000014227
Dokumentasi
Completed
961
18 May 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing PHC-01 : 37.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
962
18 May 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Slewing PHC-01 : 40.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
963
18 May 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Closing PHC-01 : 33.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
964
18 May 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Holding PHC-01 : 33.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
965
18 May 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Power Panel PHC-01 : 32.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
966
18 May 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Inspeksi dan Pengukuran suhu panel gantry PHC-02 : 38.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
967
18 May 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Inspeksi dan Pengukuran suhu trafo PHC-02 : 42.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
968
18 May 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu trafo PHC-01 : 42.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
969
18 May 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Lampu upper / boom tengah PHC-01 masih mati. (Req. Ganti jika crane di posisi laydown)
RUSAK RINGAN
REQUEST GANTI
TIDAK
Dokumentasi
Ready to Use
970
18 May 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Lubrikasi dan repair ringan pada area rol pengarah kabel drum, beberapa ada yang keras (tidak berputar) sudah di normalkan.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
971
18 May 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Pengecekan dan cleaning limit switch pada sliding gate hooper PHC-01. Test fungsi gate hooper, OK.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
972
18 May 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Cleaning motor power pack di hooper PHC-01 (dokumentasi before dan after)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
973
18 May 2026
Anton Diki W
PHC-02
CIGADING 1
Pengukuran suhu motor PHC-02 :

HOLDING
drive 45
Bearing 42
Fan 51
Brake 1 & 2 46 45

CLOSING
Drive 49
Bearing 44
Fan 57
Brake 1 & 2 54 50

SLEWING 1
Drive 46
Bearing 42
Fan 47
Brake 49

SLEWING 2
Drive 41
Bearing 40
Fan 43
Brake 47

LUFFING
Drive 37
Bearing 35
Fan 40
Brake 34
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
974
18 May 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Ac standing 7 PK sebelah anyer jatuh posisi crane a PHC-02 sedang running, indikasi kawat penahan putus (langsung action) posisi ac saat ini sudah aman
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
975
18 May 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Ruang trafo phc-02 dinding arah anyer ada yang bolong. Ditakutkan masuk air, rekues repair/foam
RELEASE
REQUEST REPAIR
Medium
Dokumentasi
Completed
976
14 May 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Holding GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
977
14 May 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Boom trolley Inverter GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
978
14 May 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Inverter Gantry GSU-01 : 31.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
979
14 May 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Trafo GSU-01 : 43.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
980
14 May 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu ruang panel elektrik GSU-04 : 29.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
981
14 May 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu panel Closing GSU-04 : 27.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
982
14 May 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu panel Holding inverter GSU-04 : 25.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
983
14 May 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu panel Gantry GSU-04 : 26.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
984
14 May 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel PLC Control GSU-01 : 41.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
985
14 May 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Konekan Motor gantry ditemukan lepas 1 pcs (akan dilakukan program megger)
LAIK PAKAI
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi Dokumentasi
Ready to Use
986
14 May 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Motor Eldo brake tidak terpasang di sebelah laut-anyer dan Limit Switch Rusak, Request Perbaiki
RUSAK RINGAN
REQUEST REPAIR
Medium
130000017501
Dokumentasi
In Process
987
14 May 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Motor Eldo brake tidak terpasang di sebelah darat-anyer dan Limit Switch Rusak, Request Perbaiki
RUSAK RINGAN
REQUEST REPAIR
Medium
130000017501
Dokumentasi
In Process
988
14 May 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Lampu LED Desk Control 24 VDC mati sebanyak 3 pcs, Request ganti
RELEASE
REQUEST GANTI
Medium
130000018124
Dokumentasi Dokumentasi
Completed
989
14 May 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Penggantian filter fan motor holding, clossing, dan trolley GSU-01 (dokumentasi before dan after)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
990
14 May 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Penggantian filter fan motor holding, clossing, dan trolley GSU-04 (dokumentasi before dan after)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
991
14 May 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
- Motor Eldo brake tidak terpasang di sebelah laut-anyer
- Motor Eldo brake tidak terpasang di sebelah darat-anyer
- Motor Eldo brake tidak terpasang di sebelah laut-merak
RUSAK RINGAN
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi
Ready to Use
992
14 May 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Cleaning motor power pack, dan motor belt feeder GSU-01 (Test running gate dan belt feeder, OK)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
993
14 May 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Konekan Motor gantry ditemukan lepas 1 pcs dan konekan brake ditemukan lepas sebanyak 2pcs (akan dilakukan program megger)
LAIK PAKAI
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi Dokumentasi
Ready to Use
994
14 May 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Ruangan Panel room bocor dan sebagian ada yang sudah jebol. Request Ganti plavon yang jebol
RUSAK RINGAN
REQUEST GANTI
Medium
130000018130
Dokumentasi
In Process
995
14 May 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Cleaning motor holding dan penggantian filter fan
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
996
14 May 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Cleaning motor clossing dan penggantian filter fan
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
997
14 May 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Cleaning motor trolley dan penggantian filter fan
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
998
14 May 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Ventilasi Fan/Ducting di bagian motor Trolley miring, kondisi saat ini diikat plat tipis. (Tidak ada sparepart nya)
LAIK PAKAI
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi
Ready to Use
999
14 May 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Emergency Button Gantry Macet/Keras di sebelah darat merak 1pcs dan laut merak 1pcs. Request untuk diganti
RELEASE
REQUEST GANTI
Medium
130000018129
Dokumentasi
Completed
1000
14 May 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Kabel Grounding Tidak terpasang/hilang. Request repair
RELEASE
REQUEST REPAIR
Medium
Dokumentasi Dokumentasi
Completed
1001
14 May 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Panel LCS Gantry lepas dari dudukannya. Request repair dudukan panel LCS
RELEASE
REQUEST REPAIR
Medium
130000018131
Dokumentasi
Completed
1002
13 May 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 30.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1003
13 May 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 30.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1004
13 May 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 37.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1005
13 May 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 34.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1006
13 May 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 28.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1007
13 May 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 31.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1008
13 May 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 30.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1009
13 May 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 33.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1010
13 May 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-04 : 31.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1011
13 May 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-02 : 30.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1012
13 May 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-04 : 45.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1013
13 May 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-03 : 42.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1014
13 May 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Motor vibro Hopper DLLC 03 sebelah merakk bagian daratt terdapat kelainan bunyi , indikasi untuk saat ini darii bearing , request service.
RELEASE
REQUEST SERVICE
Medium
130000018115
Dokumentasi
Completed
1015
13 May 2026
Anton Diki W
DLLC-03
CIGADING 1
Cleaning panel gate Hooper DLLC 03
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1016
13 May 2026
Anton Diki W
DLLC-03
CIGADING 1
Cleaning powerpack gate Hooper DLLC 03 before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1017
12 May 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1B Motor 3
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1018
12 May 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1B Motor 2
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1019
12 May 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1B Motor 1
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1020
12 May 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu ruang Trafo P1B
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1021
12 May 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Inspeksi dan Pengukuran suhu ruang panel elektrik P1B
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1022
12 May 2026
Anton Diki W
Conveyor A102
CIGADING 2
Pengukuran suhu motor drive A102
Motor kanan
Drive 41
Fan 40
Bearing 39

Motor kiri
Drive 42
Bearing 38
Fan 41
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1023
12 May 2026
Anton Diki W
Conveyor A102
CIGADING 2
Pengukuran suhu motor single drive A102 :
Drive 38
Fan 36
Bearing 38
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1024
11 May 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 28.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1025
11 May 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 29.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1026
11 May 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 29.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1027
11 May 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 29.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1028
11 May 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 27.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1029
11 May 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 33.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1030
11 May 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 31.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1031
11 May 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 34.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1032
11 May 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-02 : 31.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1033
11 May 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-02 : 46.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1034
11 May 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-01 : 29.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1035
11 May 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-01 : 42.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1036
11 May 2026
Anton Diki W
DLLC-02
CIGADING 1
Baut chamswitch holding baut lepas 1 pcs, sementara di tyrap DLLC-02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1037
11 May 2026
Anton Diki W
DLLC-02
CIGADING 1
Kondisi Slipring DLLC 02 untuk saat ini masih terpantau amann
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1038
11 May 2026
Anton Diki W
DLLC-02
CIGADING 1
Cleaning panel cabin desk operator DLLC-02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1039
11 May 2026
Anton Diki W
DLLC-02
CIGADING 1
grounding gate Hooper tidak terpasang 4pcs di DLLC 02
RUSAK RINGAN
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi
Ready to Use
1040
11 May 2026
Anton Diki W
DLLC-02
CIGADING 1
Cleaning powerpack gate Hooper DLLC 02 before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1041
09 May 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Inspeksi dan Pengukuran suhu Trafo P1C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1042
09 May 2026
Hasyim Alhabsyi
TFH & Feeding
CIGADING 2
lighting system Conveyor TFH dan Feeding terdapat 2 titik lampu yang mati di sisi darat
- Tiang nomor 1 dan nomor 5

Request Ganti
RELEASE
BY EXECUTOR
Medium
Dokumentasi Dokumentasi
Completed
1043
09 May 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Ruang panel room (trafo room) di P1C kotor. Request Cleaning
RELEASE
BY EXECUTOR
Medium
Dokumentasi Dokumentasi
Completed
1044
09 May 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Di lighting system Conveyor A103 terdapat 2 titik lampu yang mati.
- Tiang nomor 1 sisi Merak
- Tiang nomor 4 sisi Anyer

Request Ganti
RUSAK RINGAN
REQUEST GANTI
Medium
Dokumentasi Dokumentasi
Outstanding
1045
09 May 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Lubrikasi dan cleaning safety device area Conveyor A103
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1046
09 May 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Pengukuran suhu motor drive A103
Motor 1
Drive 41
Fan 37
Bearing 40

Motor 2
Drive 45
Bearing 41
Fan 39
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1047
08 May 2026
Anton Diki W
Feeding SGT
CIGADING 1
Tes running bucket elevator SGT, kondisi ok
Note : horn bucket elevator SGT tidak terpasang
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1048
08 May 2026
Anton Diki W
Feeding SGT
CIGADING 1
Cleaning motor bucket elevator SGT. (Kondisi yang sebelumnya kotor, sudah langsung dibersihkan oleh tim Preventive. Dokumentasi before dan after)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1049
08 May 2026
Hasyim Alhabsyi
Feeding SGT
CIGADING 1
Preventive elektrik lighting system dan Cleaning area Bunker Feeding SGT. Kondisi kotor untuk lighting yang kotor dibersihkan
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1050
07 May 2026
Anton Diki W
CCSU
CIGADING 1
Slipring CSU sangat kotor, langsung di cleaning before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1051
07 May 2026
Anton Diki W
CCSU
CIGADING 1
Cleaning dan Penggantian filter fan ruang trafo CSU (before) dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1052
06 May 2026
Anton Diki W
PHC-01
CIGADING 1
Pengukuran suhu motor PHC-01 :

HOLDING
drive 42
Bearing 39
Fan 52
Brake 1 & 2 44 46

CLOSING
Drive 49
Bearing 44
Fan 50
Brake 1 & 2 52 50

SLEWING 1
Drive 41
Bearing 34
Fan 42
Brake 41

SLEWING 2
Drive 38
Bearing 38
Fan 44
Brake 50

LUFFING
Drive 35
Bearing 36
Fan 42
Brake 39
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1053
06 May 2026
Anton Diki W
PHC-02
CIGADING 1
Ditemukan Kontaktor Motor gantry No.5 (501Q1) di panel gantry PHC-02 posisi : dilepas
Req. Normalkan
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1054
06 May 2026
Anton Diki W
PHC-02
CIGADING 1
Ruang main trafo dan switchgear terindikasi masih bolong dan terdapat indikasi bolong baru di PHC-02.
RELEASE
REQUEST REPAIR
Medium
130000018066
Dokumentasi Dokumentasi
Completed
1055
05 May 2026
Anton Diki W
CCSU
CIGADING 1
Supporting kegiatan preventif mekanik dan eksekutor di area CC2 (CSU). Pengecekan rel, chain, dan shovel yang mengalami kerusakan. Langsung di tangani oleh tim Eksekutor Mekanik
LAIK PAKAI
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi Dokumentasi
Ready to Use
1056
05 May 2026
Anton Diki W
GSU-06
CIGADING 2
Chamswitch holding dan closing terpantau OK GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1057
05 May 2026
Anton Diki W
GSU-06
CIGADING 2
Kabel glend motor vibrating GSU 06 luka/sobek , sementara di rubber lalu di vinyl. Request ganti.
RUSAK RINGAN
REQUEST GANTI
Medium
130000018504
Dokumentasi Dokumentasi
In Process
1058
05 May 2026
Anton Diki W
GSU-06
CIGADING 2
Pengencangan baud di panel LSA/CPA gantry GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1059
05 May 2026
Anton Diki W
GSU-06
CIGADING 2
Lubrikasi roll pendulum medium voltage GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1060
04 May 2026
Anton Diki W
GSU-04
CIGADING 1
Pengukuran suhu motor Gsu-04

Holding
Drive 52
Bearing 45
Fan 43

Closing
Drive 56
Bearing 42
Fan 48

Trolley
Drive 60
Bearing 41
Fan 46

Suhu Motor belt feeder GSU 04
Motor 01
Drive 37
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1061
04 May 2026
Anton Diki W
GSU-01
CIGADING 1
Pengukuran suhu motor Gsu-01

Holding
Drive 59
Bearing 42
Fan 48

Closing
Drive 60
Bearing 47
Fan 50

Trolley
Drive 53
Bearing 42
Fan 50

Suhu motor belt feeder GSU 01
Motor 2
Drive 39
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1062
04 May 2026
Anton Diki W
GSU-04
CIGADING 1
Penggantian filter motor fan holding closing trolley GSU-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1063
04 May 2026
Anton Diki W
GSU-01
CIGADING 1
Penggantian filter motor fan holding closing trolley GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1064
30 Apr 2026
Anton Diki W
Tower 2
CIGADING 1
Pengecekan suhu motor BCNO :
Motor 1
Drive 49
Bearing 46
Brake 46

Motor 2
Drive 44
Bearing 43
Brake 50
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1065
29 Apr 2026
Hasyim Alhabsyi
Conveyor PBCN 1
CIGADING 1
Pengecekan safety device di area conveyor PBCN-01 sebelum running kapal batubara
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1066
29 Apr 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Lubrikasi roll pendulum/ pengarah kabel drum 6kV DLLC-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1067
29 Apr 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Pengecekan ruang trafo, main trafo dan switchgear DLLC-01, Kondisi OK
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1068
29 Apr 2026
Anton Diki W
DLLC-01
CIGADING 1
Pengecekan Bridge crane DLLC 01 untuk sistem elektriknya, kondisi OK.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1069
29 Apr 2026
Anton Diki W
DLLC-01
CIGADING 1
Kondisi Slipring DLLC 01 untuk saat ini masih terpantau amann
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1070
29 Apr 2026
Anton Diki W
DLLC-01
CIGADING 1
Chamswitch holding closing kondisi baut masih lengkap (ok) DLLC-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1071
29 Apr 2026
Anton Diki W
DLLC-01
CIGADING 1
Ruang gantry DLLC 01 kondisi OK
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1072
29 Apr 2026
Anton Diki W
DLLC-01
CIGADING 1
Cleaning powerpack gate Hooper DLLC 01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1073
29 Apr 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Lampu penerangan Downlight dan Upperlight OK. Lampu bisa di nyalakan dari local panel di gantry.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1074
28 Apr 2026
Hasyim Alhabsyi
Conveyor PBCN 2
CIGADING 1
Lubrikasi zero speed GSU-01 dan GSU-04 sisi laut dan sisi darat conveyor PBCN-02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1075
28 Apr 2026
Hasyim Alhabsyi
Conveyor PBCN 1
CIGADING 1
Lubrikasi zero speed GSU-01 dan GSU-04 sisi laut dan sisi darat conveyor PBCN-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1076
27 Apr 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Inspeksi dan Pengukuran suhu Panel 2 CCSU : 28.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1077
27 Apr 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Inspeksi dan Pengukuran suhu Panel 1 CCSU : 30.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1078
27 Apr 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Inspeksi area slipring CCSU, masih terdapat tumpukan sisa material di area slipring.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1079
27 Apr 2026
Anton Diki W
CCSU
CIGADING 1
Suhu Motor drive CC2 sisi laut
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1080
27 Apr 2026
Anton Diki W
CCSU
CIGADING 1
Suhu Motor drive CC2 sisi darat
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1081
27 Apr 2026
Anton Diki W
CCSU
CIGADING 1
Suhu fan CC3 kanan
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1082
27 Apr 2026
Anton Diki W
CCSU
CIGADING 1
Suhu fan CC3 kiri
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1083
27 Apr 2026
Anton Diki W
CCSU
CIGADING 1
suhu Motor drive CC3
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1084
27 Apr 2026
Anton Diki W
CCSU
CIGADING 1
Kabel grounding CC2 putus. Request Ganti
RELEASE
REQUEST GANTI
Medium
130000016631
Dokumentasi
Completed
1085
27 Apr 2026
Anton Diki W
CCSU
CIGADING 1
Suhu Motor emergency pump CSU
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1086
27 Apr 2026
Anton Diki W
CCSU
CIGADING 1
Suhu Motor feeding pump CSU
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1087
27 Apr 2026
Anton Diki W
CCSU
CIGADING 1
Suhu motor fan CSU : 57.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1088
27 Apr 2026
Anton Diki W
CCSU
CIGADING 1
Suhu motor main pump hidrolik CSU
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1089
25 Apr 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing PHC-01 : 36.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1090
25 Apr 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Slewing PHC-01 : 35.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1091
25 Apr 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Closing PHC-01 : 33.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1092
25 Apr 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Holding PHC-01 : 32.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1093
25 Apr 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Power Panel PHC-01 : 31.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1094
25 Apr 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Inspeksi dan Pengukuran suhu panel gantry PHC-02 : 37.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1095
25 Apr 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Inspeksi dan Pengukuran suhu trafo PHC-02 : 42.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1096
25 Apr 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi dan Pengukuran suhu trafo PHC-01 : 43.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1097
25 Apr 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Sakelar untuk lampu penerangan di motor room PHC-02 rusak. Request Ganti
RUSAK RINGAN
REQUEST GANTI
Medium
130000017986
Dokumentasi
In Process
1098
25 Apr 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Motor truster brake gantry No. 3 macet (Posisi : Darat arah Anyer). Request Repair
RUSAK RINGAN
REQUEST REPAIR
Medium
130000017981
Dokumentasi
In Process
1099
25 Apr 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Lampu boom tengah (400 W) dan lampu top boom (400 W) di PHC-02 mati (2 Pcs). Request Ganti
RUSAK BERAT
REQUEST GANTI
Medium
130000017985
Dokumentasi Dokumentasi
In Process
1100
25 Apr 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Sakelar untuk lampu penerangan di auxtrally trafo PHC-02 rusak. Request Ganti
RUSAK RINGAN
REQUEST GANTI
Medium
130000017984
Dokumentasi
In Process
1101
25 Apr 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Inspeksi cabel reel Medium Voltage, AC Motor 1 dan AC Motor 2.
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1102
25 Apr 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Pengecekan motor Pin lock sisi darat dan sisi laut di area top boom PHC-01. Kondisi OK
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1103
25 Apr 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Exhaust fan di area motor room tidak terpasang di kedua titiknya. Request Pasangkan
RUSAK RINGAN
REQUEST SERVICE
Medium
130000017983
Dokumentasi Dokumentasi
In Process
1104
25 Apr 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Motor truster brake gantry No. 3 macet (Posisi : Darat arah Anyer). Request Repair
RUSAK RINGAN
REQUEST REPAIR
Medium
130000017982
Dokumentasi
In Process
1105
25 Apr 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Sakelar untuk lampu penerangan di auxtrally trafo rusak. Request Ganti
RUSAK RINGAN
REQUEST GANTI
Medium
130000017979
Dokumentasi
In Process
1106
25 Apr 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Lampu penerangan di depan ruang trafo PHC-01 berkedip, Request Ganti
RELEASE
REQUEST GANTI
Medium
130000017978
Dokumentasi
Completed
1107
25 Apr 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Lampu boom tengah (400 W) di PHC-01 mati. Request Ganti
RUSAK RINGAN
REQUEST GANTI
Medium
130000017977
Dokumentasi
In Process
1108
25 Apr 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Cooling fan oil tidak terpasang di motor Powerpack gate hooper PHC-01
RELEASE
REQUEST REPAIR
Medium
130000016236
Dokumentasi Dokumentasi
Completed
1109
25 Apr 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Inspeksi cabel reel Medium Voltage, AC Motor 1 dan AC Motor 2
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1110
25 Apr 2026
Anton Diki W
PHC-02
CIGADING 1
cleaning power pack gate hopper PHC-02 (dokumentasi before dan after)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1111
25 Apr 2026
Anton Diki W
PHC-01
CIGADING 1
Cleaning panel elektrik gate hooper PHC-01 (dokumentasi before dan after)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1112
25 Apr 2026
Anton Diki W
PHC-01
CIGADING 1
cleaning power pack gate hopper PHC-01 (dokumentasi before dan after)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1113
24 Apr 2026
Anton Diki W
Feeding SGT
CIGADING 1
Cleaning motor bucket elevator SGT
Before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1114
23 Apr 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Inspeksi dan Pengukuran suhu Panel VSD P1A
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1115
23 Apr 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Cleaning dan lubrikasi safety device A101
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1116
23 Apr 2026
Hasyim Alhabsyi
Conveyor A101
CIGADING 2
Lubrikasi zerospeed GSU-05 dan GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1117
22 Apr 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 30.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1118
22 Apr 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 30.0°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1119
22 Apr 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 30.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1120
22 Apr 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 34.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1121
22 Apr 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 27.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1122
22 Apr 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 33.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1123
22 Apr 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 31.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1124
22 Apr 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 29.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1125
22 Apr 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-04 : 34.4°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1126
22 Apr 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-03 : 29.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1127
22 Apr 2026
Hasyim Alhabsyi
DLLC-04
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-04 : 41.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1128
22 Apr 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-03 : 50.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1129
22 Apr 2026
Anton Diki W
DLLC-04
CIGADING 1
Bridge crane DLLC 04 kondisi OK
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1130
22 Apr 2026
Anton Diki W
DLLC-04
CIGADING 1
Kondisi Slipring DLLC 04 untuk saat ini masih terpantau amann
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1131
22 Apr 2026
Anton Diki W
DLLC-04
CIGADING 1
Baut chamswitch holding baut lepas 1 pcs, sementara di tyrap DLLC-04
RELEASE
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi
Completed
1132
22 Apr 2026
Anton Diki W
DLLC-03
CIGADING 1
Kondisi Slipring DLLC 03 untuk saat ini masih terpantau amann
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1133
22 Apr 2026
Anton Diki W
DLLC-03
CIGADING 1
Baut chamswitch holding baut lepas 1 pcs, sementara di tyrap DLLC-03
RELEASE
REQUEST PENAMBAHAN
PANTAU
Dokumentasi
Completed
1134
22 Apr 2026
Anton Diki W
DLLC-03
CIGADING 1
Cleaning powerpack gate Hooper DLLC 03 before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1135
22 Apr 2026
Anton Diki W
DLLC-03
CIGADING 1
grounding gate Hooper tidak terpasang 2pcs di DLLC 03
RELEASE
BY EXECUTOR
PANTAU
Dokumentasi
Completed
1136
22 Apr 2026
Hasyim Alhabsyi
DLLC-03
CIGADING 1
Cleaning motor powerpack gate Hooper DLLC 03 (dokumentasi before dan after)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1137
21 Apr 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Inspeksi dan Pengukuran suhu Vibrating (Motor 2)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1138
21 Apr 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Inspeksi dan Pengukuran suhu Vibrating (Motor 1)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1139
21 Apr 2026
Anton Diki W
GSU-05
CIGADING 2
Cam switch holding dan closing terpantau OK di GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1140
21 Apr 2026
Anton Diki W
GSU-05
CIGADING 2
Roll festune cabin operator Kendor di GSU 05 ( langsung action ), dokumentasi before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1141
21 Apr 2026
Anton Diki W
GSU-05
CIGADING 2
Lubrikasi roll festune cabin operator GSU 05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1142
21 Apr 2026
Anton Diki W
GSU-05
CIGADING 2
Motor gantry GSU 05 tidak terpasang 1pcs no 2 Darii darat
LAIK PAKAI
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi
Ready to Use
1143
21 Apr 2026
Anton Diki W
GSU-05
CIGADING 2
Bearing roll festune cabin GSU 05 tidak terpasang 1 pcs no 2 Dari cabin
RUSAK RINGAN
REQUEST REPAIR
Medium
130000015110
Dokumentasi
In Process
1144
21 Apr 2026
Anton Diki W
GSU-06
CIGADING 2
Lubrikasi roll pendulum medium voltage GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1145
21 Apr 2026
Anton Diki W
GSU-06
CIGADING 2
Lubrikasi roll festune cabin operator GSU 06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1146
21 Apr 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Kabel glend motor vibrating GSU-05 luka, langsung action di rubber lalu di vinyl
RUSAK RINGAN
PREVENTIVE MAINTENANCE
Medium
130000017798
Dokumentasi Dokumentasi
In Process
1147
21 Apr 2026
Anton Diki W
GSU-06
CIGADING 2
Cover fan motor cabin operator tidak terpasang di GSU 06
LAIK PAKAI
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi
Ready to Use
1148
21 Apr 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Cleaning zerospeed GSU-05
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1149
21 Apr 2026
Anton Diki W
GSU-06
CIGADING 2
Chamswitch holding dan closing terpantau OK GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1150
21 Apr 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Pengencangan baud LSA/CPA GANTRY GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1151
21 Apr 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Cleaning zerospeed GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1152
20 Apr 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Motor room DLLC-01 berlubang, rekues service
LAIK PAKAI
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi
Ready to Use
1153
20 Apr 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Grounding hopper DLLC-01 tidak terpasang 3 pcs, Req pasang
LAIK PAKAI
REQUEST PENAMBAHAN
PANTAU
Dokumentasi
Ready to Use
1154
20 Apr 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Cleaning motor powerpack gate hopper DLLC-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1155
20 Apr 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Ruang trafo DLLC-01 kotor, Req Cleaning
RELEASE
REQUEST BERSIHKAN
Medium
130000016820
Dokumentasi
Completed
1156
20 Apr 2026
Anton Diki W
DLLC-02
CIGADING 1
Kondisi Slipring DLLC 02 untuk saat ini masih terpantau amann
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1157
18 Apr 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Holding GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1158
18 Apr 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Boom trolley Inverter GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1159
18 Apr 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Gantry Inverter GSU-01 : 32.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1160
18 Apr 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel Trafo GSU-01 : 38.6°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1161
18 Apr 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu ruang panel elektrik GSU-04 : 28.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1162
18 Apr 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu panel Closing GSU-04 : 31.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1163
18 Apr 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu panel Holding inverter GSU-04 : 33.1°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1164
18 Apr 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Inspeksi dan Pengukuran suhu panel Gantry GSU-04 : 25.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1165
18 Apr 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Inspeksi dan Pengukuran suhu panel PLC Control GSU-01 : 32.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1166
18 Apr 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Coupling motor kabel drum GSU-04 berkarat. Req. Service
RELEASE
REQUEST SERVICE
Medium
130000017930
Dokumentasi Dokumentasi
Completed
1167
18 Apr 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Cover fan motor kabel drum GSU-04 rusak dan korosi. Req. Ganti
RELEASE
REQUEST GANTI
Medium
130000017931
Dokumentasi Dokumentasi
Completed
1168
18 Apr 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Cover fan motor kabel drum GSU-01 rusak dan korosi. Req. Ganti
RELEASE
REQUEST GANTI
Medium
130000017928
Dokumentasi Dokumentasi
Completed
1169
18 Apr 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Karet coupling motor kabel drum GSU-01 lepas dari dudukannya. Req. Service
RELEASE
REQUEST SERVICE
Medium
130000017929
Dokumentasi Dokumentasi
Completed
1170
18 Apr 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Main trafo GSU 01 butuh di cleaning
RELEASE
REQUEST BERSIHKAN
Medium
130000017932
Dokumentasi Dokumentasi
Completed
1171
18 Apr 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Struktur kanopi panel LCS gantry GSU-04 rusak. Request Perbaikan
RELEASE
REQUEST REPAIR
Medium
130000018050
Dokumentasi
Completed
1172
18 Apr 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Motor eldo brake GSU-04 tidak ada 2 pcs (1 darat merak, 1 laut merak)
RUSAK RINGAN
REQUEST PENAMBAHAN
Medium
130000017501
Dokumentasi
In Process
1173
18 Apr 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Atap / Plavon ruang panel terlihat bekas bocor di GSU-04, req. Pantau
RUSAK RINGAN
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi Dokumentasi
Ready to Use
1174
18 Apr 2026
Anton Diki W
GSU-01
CIGADING 1
Motor eldro break GSU-01 tidak terpasang sebayak 3 Pcs ( ket : 2pcs sisi darat Anyer, 1pcs sisi laut Anyer). Request pasang
RUSAK BERAT
REQUEST PENAMBAHAN
Medium
Dokumentasi Dokumentasi
Outstanding
1175
18 Apr 2026
Anton Diki W
GSU-04
CIGADING 1
Roll pendulum kabel drum di GSU-04 sebanyak 6 pcs macet di sebelah merak. Request Repair
RELEASE
REQUEST REPAIR
Medium
130000017924
Dokumentasi Dokumentasi
Completed
1176
18 Apr 2026
Anton Diki W
GSU-01
CIGADING 1
Roll pendulum kabel drum di GSU-01 sebanyak 3 pcs macet di sebelah merak. Request Repair
RELEASE
REQUEST REPAIR
Medium
130000017923
Dokumentasi
Completed
1177
18 Apr 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Lubrikasi roll festune cabin operator di GSU-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1178
18 Apr 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Lubrikasi underspeed GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1179
18 Apr 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Cleaning underspeed GSU-01, ditemukannya semut di dalam underspeed (langsung di cleaning & tutup lobang menggunakan silikon)
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1180
18 Apr 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Penggantian filter motor fan boom GSU-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1181
17 Apr 2026
Hasyim Alhabsyi
CONV C02
CIGADING 1
Preventive program shutdown Cleaning motor BCNO
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1182
17 Apr 2026
Hasyim Alhabsyi
CONV BCNO
CIGADING 1
Preventive program shutdown Cleaning motor BCNO dan cleaning Panel Tower 11
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1183
16 Apr 2026
Anton Diki W
Conveyor A103
CIGADING 2
tray kabel area A103 rusak. Request Repair
RUSAK RINGAN
REQUEST REPAIR
Medium
Dokumentasi
Outstanding
1184
16 Apr 2026
M. Zainudin
Conveyor A103
CIGADING 2
Karet legging di drum bend head pulley (shuttle) indikasi sobek di area A103 request Repair
RUSAK RINGAN
REQUEST REPAIR
Medium
130000017916
Dokumentasi
In Process
1185
16 Apr 2026
Anton Diki W
TFH & Feeding
CIGADING 2
Cleaning motor power pack TFH
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1186
16 Apr 2026
Anton Diki W
Conveyor A103
CIGADING 2
Lampu LED conveyor A103 mati 7pcs sebelah merak dan 7pcs sebelah Anyer. Request Ganti
RELEASE
BY EXECUTOR
Medium
Dokumentasi
Completed
1187
16 Apr 2026
Anton Diki W
Conveyor A103
CIGADING 2
Pengukuran suhu motor drive Conveyor A103
Motor 1
Drive 41
Fan 38
Bearing 40

Motor 2
Drive 42
Bearing 39
Fan 42
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1188
16 Apr 2026
Anton Diki W
Conveyor A103
CIGADING 2
Ruang panel P1C banyak yang retak di dinding, Pantau
LAIK PAKAI
PREVENTIVE MAINTENANCE
PANTAU
Dokumentasi
Ready to Use
1189
16 Apr 2026
Hasyim Alhabsyi
MV CGD2
CIGADING 2
Trafo 30 KV Cigading 2 kotor, rekues cleaning
RUSAK RINGAN
REQUEST BERSIHKAN
Medium
130000017913
Dokumentasi
In Process
1190
15 Apr 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Pengukuran suhu motor PHC-01 :

HOLDING
drive 43
Bearing 40
Fan 57
Brake 1 & 2 46 46

CLOSING
Drive 54
Bearing 47
Fan 53
Brake 1 & 2 58 56

SLEWING 1
Drive 52
Bearing 42
Fan 46
Brake 58

SLEWING 2
Drive 50
Bearing 40
Fan 40
Brake 60

LUFFING
Drive 36
Bearing 35
Fan 42
Brake 37
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1191
15 Apr 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Perbaiki jalur lampu frame lights dan MCB 203f3 yg rusak di PHC 01
RELEASE
REQUEST REPAIR
Medium
130000017912<br/> 130000017907
Dokumentasi
Completed
1192
15 Apr 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Grounding area gantry tidak terpasang 2 pcs, rekues pasang PHC-01
RELEASE
REQUEST PENAMBAHAN
Medium
Dokumentasi
Completed
1193
14 Apr 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 29.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1194
14 Apr 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Luffing: 28.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1195
14 Apr 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 30.9°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1196
14 Apr 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Closing: 30.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1197
14 Apr 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 33.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1198
14 Apr 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Holding : 30.3°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1199
14 Apr 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 32.2°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1200
14 Apr 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel room elektrik Slewing : 31.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1201
14 Apr 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-02 : 29.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1202
14 Apr 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-02 : 40.5°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1203
14 Apr 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu Panel Gantry DLLC-01 : 30.8°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1204
14 Apr 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Inspeksi dan Pengukuran suhu trafo DLLC-01 : 49.7°C
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1205
14 Apr 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Cleaning motor powerpack gate hopper DLLC-01
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1206
14 Apr 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Underspeed conveyor A103 posisi di bawah, terdapat Grease dan kotor butuh di cleaning
RUSAK RINGAN
REQUEST BERSIHKAN
Medium
Dokumentasi
Outstanding
1207
14 Apr 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Pengukuran suhu motor drive A102
Motor kanan
Drive 42
Fan 40
Bearing 38

Motor kiri
Drive 42
Bearing 37
Fan 40
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1208
14 Apr 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
Pengukuran suhu motor single drive A102 :
Drive 39
Fan 36
Bearing 35
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1209
13 Apr 2026
Hasyim Alhabsyi
GSU-04
CIGADING 1
Lubrikasi roll festun cabin operator GSU-04
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1210
30 Mar 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Motor Screw No.4 (sisi laut arah merak) di Crane CSU macet. Request Repair
RELEASE
REQUEST REPAIR
Medium
130000017653
Dokumentasi Dokumentasi
Completed
1211
30 Mar 2026
Anton Diki W
GSU-01
CIGADING 1
lampu indikator shuttle pos 1 dan pos 2 mati. 1 mati dan 1 tidak terpasang.. 24 Vdc GSU-01
RELEASE
REQUEST GANTI
Medium
Dokumentasi
Completed
1212
30 Mar 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Tangkai Limit switch batas laut di rel belt feeder GSU-01 patah, Req. Repair
RELEASE
REQUEST REPAIR
Medium
Dokumentasi
Completed
1213
30 Mar 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Motor gantry GSU 01 tidak terpasang 3 pcs sebelah laut
RELEASE
BY EXECUTOR
Medium
Dokumentasi Dokumentasi
Completed
1214
30 Mar 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Eldro brake gantry GSU 01 tidak terpasang 3pcs. Request Tambahkan (pasang)
RUSAK RINGAN
REQUEST PENAMBAHAN
Medium
Dokumentasi
Outstanding
1215
30 Mar 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
Kondisi Panel Komunikasi di Gsu-01 lembab plus kemasukan air. Req. perbaiki seal panel yang sudah rusak. gsu-01 dan foam bagian lubang yang tidak tertutup.
RELEASE
REQUEST REPAIR
Medium
Dokumentasi Dokumentasi
Completed
1216
30 Mar 2026
Hasyim Alhabsyi
GSU-01
CIGADING 1
bebaskan proximity batas bawah gate hopper GSU-01 yang ke gencet plat pengarah. sudah dibebaskan. req. modifikasi plat pengarah proximity seperti bagian laut.
RELEASE
REQUEST REPAIR
Medium
Dokumentasi Dokumentasi
Completed
1217
27 Mar 2026
Hasyim Alhabsyi
FEEDING SGT
CIGADING 1
Perbaikan Motor Fan Feeding SGT karena short, kabel di panel Control di lepas.
RELEASE
REQUEST REPAIR
Medium
130000017706
Dokumentasi
Completed
1218
17 Mar 2026
Hasyim Alhabsyi
CONV C02
CIGADING 1
Cleaning motor drive conveyor C-02
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1219
17 Mar 2026
Hasyim Alhabsyi
CONV BCNO
CIGADING 1
Cleaning motor drive conveyor BCNO
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1220
13 Mar 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Cleaning jalur kabel slipring CSU. Dokumentasi before dan after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1221
13 Mar 2026
Anton Diki W
CCSU
CIGADING 1
Cleaning dan Penggantian filter fan ruang trafo CSU. Dokumentasi before-after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1222
13 Mar 2026
Anton Diki W
CCSU
CIGADING 1
Junction box Motor screw CSU lepas dari dudukan indikasi ketarik. Request Repair
RELEASE
REQUEST REPAIR
Medium
Dokumentasi Dokumentasi
Completed
1223
13 Mar 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Cleaning ruang panel elektrik CSU. Dokumentasi before-after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1224
13 Mar 2026
Hasyim Alhabsyi
CCSU
CIGADING 1
Cleaning sensor sink in HL SKT CSU. Dokumentasi before-after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1225
12 Mar 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
MCB no.07 di panel no.2 (LP0-G-102B) conveyor A102 untuk tiang lampu no.41, 42, 43 sering trip. Req. Perbaiki jalur kabel
RUSAK RINGAN
REQUEST REPAIR
Medium
130000016936
Dokumentasi Dokumentasi
In Process
1226
12 Mar 2026
Hasyim Alhabsyi
Conveyor A102
CIGADING 2
MCB 6A (no.05) untuk penerangan lampu conv A102 di panel arah darat sisi merak sering trip. Req. Repair jalur kabel
RUSAK RINGAN
REQUEST REPAIR
Medium
130000016473
Dokumentasi Dokumentasi
In Process
1227
11 Mar 2026
Hasyim Alhabsyi
DLLC-02
CIGADING 1
Grounding area gantry DLLC 02 terpantau lengkap
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1228
11 Mar 2026
Hasyim Alhabsyi
DLLC-01
CIGADING 1
Lampu LED 8 watt ruang panel gantry mati 2 pcs, rekues ganti DLLC-02
RUSAK RINGAN
REQUEST GANTI
Medium
130000017661
Dokumentasi
In Process
1229
10 Mar 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
"Pengukuran suhu motor drive A103
Motor 1
Drive 39
Fan 35
Bearing 38

Motor 2
Drive 39
Bearing 36
Fan 33"
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1230
10 Mar 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Filter panel drive P1C kotor, rekues ganti
RELEASE
BY EXECUTOR
Medium
130000017655
Dokumentasi
Completed
1231
10 Mar 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Filter panel vsd bagian belakang P1C tidak terpasang 4pcs. Request Tambahkan
RELEASE
BY EXECUTOR
Medium
130000017656
Dokumentasi
Completed
1232
10 Mar 2026
Hasyim Alhabsyi
Conveyor A103
CIGADING 2
Kondisi panel vsd kotor rekues cleaning, di P1C
RELEASE
BY EXECUTOR
Medium
130000017651
Dokumentasi Dokumentasi
Completed
1233
03 Mar 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Lampu LED 18W motor room GSU-06 tidak terpasang 6pcs, Req. Tambahkan
RUSAK RINGAN
REQUEST PENAMBAHAN
Medium
130000014231
Dokumentasi
In Process
1234
03 Mar 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Chamswitch holding dan closing terpantau OK GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1235
03 Mar 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Perbaikan kabel vibrating luka langsung action GSU 06. DOkumentasi before-after
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi Dokumentasi
Ready to Use
1236
03 Mar 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Lubrikasi roll festune cabin operator GSU 06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1237
03 Mar 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
pengencangan baud di panel LSA/CPA gantry GSU-06
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1238
03 Mar 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Raychem kabel medium voltage GSU-06 terkelupas 1 titik, rekues raychem ulang
RELEASE
BY EXECUTOR
Medium
130000014227
Dokumentasi
Completed
1239
03 Mar 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Lampu boom GSU 06 Kondisi OK
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1240
03 Mar 2026
Hasyim Alhabsyi
GSU-06
CIGADING 2
Dudukan emergency GSU 06 sebelah laut korosi , request repair
RELEASE
BY EXECUTOR
Medium
130000017592
Dokumentasi
Completed
1241
03 Mar 2026
Hasyim Alhabsyi
GSU-05
CIGADING 2
Posisi sensor proximity tidak ada dudukannya GSU-05, Rekues penambahan dudukan
RUSAK RINGAN
REQUEST REPAIR
Medium
130000017586
Dokumentasi
In Process
1242
02 Mar 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Dinding Ruang motor room PHC-01 bolong atau keropos. request repair
RELEASE
REQUEST REPAIR
Medium
130000017589
Dokumentasi Dokumentasi
Completed
1243
02 Mar 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Kontaktor di panel luffing (486K2) PHC-01 terdapat kelainan bunyi/pong. req ganti
RELEASE
REQUEST GANTI
Medium
130000017590
Dokumentasi
Completed
1244
02 Mar 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
fan panel di panel room elektrik mati 7pcs. req perbaiki instalasi dan ganti fan yang mati. PHC 01
- panel rectifier 1pcs
- panel holding 2pcs
- panel closing 1pcs
- panel luffing 2pcs
- panel spreader 1pcs
RELEASE
BY EXECUTOR
Medium
130000017581
Dokumentasi Dokumentasi
Completed
1245
02 Mar 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Exhaust fan di motor room PHC-01 tidak terpasang. Request Tambahkan
RUSAK BERAT
REQUEST PENAMBAHAN
Medium
130000017579
Dokumentasi Dokumentasi
In Process
1246
02 Mar 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Isolasi kabel power 6 KV rusak PHC 02. Req. raychem kabel ulang (Service)
RELEASE
REQUEST SERVICE
Medium
130000017574
Dokumentasi Dokumentasi
Completed
1247
02 Mar 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Isolasi kabel power 6 KV rusak PHC-01. Req. raychem kabel ulang (Service)
RELEASE
REQUEST SERVICE
Medium
130000017573
Dokumentasi Dokumentasi
Completed
1248
02 Mar 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
"Pengukuran suhu motor PHC-01 dalam derajat Celcius :
Holding
Drive 36
Bearing 34
Brake 1 39
Brake 2 39
Fan 49

Closing
Drive 44
Bearing 39
Brake 1 47
Brake 2 44
Fan 52

Slewing 1
Drive 38
Bearing 34
Fan 34
Brake 46

Slewing 2
Drive 40
Bearing 34
Fan 34
Brake 47

Luffing
Drive 33
Bearing 35
Brake 41
Fan 31"
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1249
02 Mar 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Ruang trafo PHC-01 dinding bolong 3 titik, rekues repair
RELEASE
REQUEST REPAIR
Medium
130000017361
Dokumentasi Dokumentasi
Completed
1250
02 Mar 2026
Hasyim Alhabsyi
PHC-01
CIGADING 1
Kabel Grounding area gantry PHC 01 hilang 2 pcs, Posisi sebelah darat. Req. Tambahkan
RELEASE
REQUEST TAMBAHKAN
Medium
130000014469
Dokumentasi Dokumentasi
Completed
1251
02 Mar 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Pengukuran suhu motor PHC-02 (dalam satuan Celcius) :
Holding : Drive 40 Bearing 39
Fan 50 Brake 1 & 2 43 & 41

Closing : Drive 42 Bearing 44
Fan 47 Brake 1 & 2 47 & 43

Slewing : Drive 41 Bearing 40
Fan 41 Brake 44

Slewing 2 : Drive 43 Bearing 42
Fan 41 Brake 46

Luffing : Drive 37 Bearing 36
Fan 39 Brake 40
LAIK PAKAI
PREVENTIVE MAINTENANCE
TIDAK
Dokumentasi
Ready to Use
1252
02 Mar 2026
Hasyim Alhabsyi
PHC-02
CIGADING 1
Kabel Grounding di area gantry Phc-02 tidak terpasang 5 pcs, Req. Tambahkan
RELEASE
REQUEST TAMBAHKAN
Medium
130000014470
Dokumentasi
Completed